CPKSoft Engineering

XWIMPACC.tlk Driver Reference

Westinghouse IMPACC System Communications Protocol Driver

This driver requires that you have TAS-HMITalk 8.04 installed.

Driver Overview

XWIMPACC driver allows you to connect to any other Westinghouse Electric

Corporation equipment using the IMPACC System Communications protocol

(according to IL-17384, revision 1.4, June 1992 & July 1996).

Communications are made through a RS-232 port. A special interface

Westinghouse MINT (Master INCOM Network Translator) is required when

more than one device must be connected. A multidrop of up to 999

devices can be connected.

For point-to-point communications with a unique device, the use of

a MINT interface is not required and the PC serial port can be

connected directly with the PONI interface of the device.

 

The commmunication cable between the PC and the MINT unit must have

the following pins assignment:

 

- PC PIN 2 --> MINT PIN 2

- PC PIN 3 --> MINT PIN 3

- PC PIN 7 --> MINT PIN 7

 

(Note that pins 2 and 3 are not inverted)

Supported Equipment Type

Power Meters

Supported Devices List

CUTLER HAMMER WESTINGHOUSE Addressable Relay

CUTLER HAMMER WESTINGHOUSE Advantage

CUTLER HAMMER WESTINGHOUSE Digitrip-II

CUTLER HAMMER WESTINGHOUSE Advantage-Control PONI

CUTLER HAMMER WESTINGHOUSE IQ-Energy Sentinel

CUTLER HAMMER WESTINGHOUSE IQ-1000 II

CUTLER HAMMER WESTINGHOUSE IQ-500

CUTLER HAMMER WESTINGHOUSE IQ-Data & IQ-Generator

CUTLER HAMMER WESTINGHOUSE IQ-Data-Plus-II

CUTLER HAMMER WESTINGHOUSE AEM-II

CUTLER HAMMER WESTINGHOUSE Universal-RTD

CUTLER HAMMER WESTINGHOUSE CMU (Central Monitoring Unit)

CUTLER HAMMER WESTINGHOUSE ACM (Advantage Control Module)

CUTLER HAMMER WESTINGHOUSE DP-4000

Supported Commands List

Addressable Relay Commands:

Energize Relay

De-energize Relay

Read Status

 

Advantage Commands:

Read Fast Status

Read Current Buffer

Read Flags Buffer

Read Setpoints Buffer

Read Time Stamped Trip Data Buffer

Write Slave Action

 

Digitrip II Commands:

Read Fast Status

Read Data Buffer

Reset Peak Demand

Shed Load

Restore Load

Reset Energy

 

Advantage Control PONI Commands:

Start

Stop

Read Status

 

IQ Energy Sentinel:

Read Fast Status

Read Power Buffer

Read Energy Buffer

Read Flags Buffer

Write Slave Action

Broadcast Save Energy Buffer

Broadcast Reset Demand Window

 

IQ 1000 II Commands:

Read Fast Status

Read Current Buffer

Read Temperature Buffer

Read Flags Buffer

Read Setpoints Buffer

Read Time-Stamped Trip Data Buffer

Write Slave Action

 

IQ 500 Commands:

Read Fast Status

Read Current Buffer

Read Flags Buffer

Read Setpoints Buffer

Read Time-Stamped Trip Data Buffer

Write Slave Action

 

IQ Data & IQ Generator Commands:

Read Fast Status

Read Current Buffer

Read Line-to-Line Voltage Buffer

Read Line-to-Neutral Voltage Buffer

Read Power Buffer

Read Flags Buffer

Read Setpoints Buffer

 

IQ Data Plus II Commands:

Read Trip Data Buffer

Read Fast Status

Read Current Buffer

Read Line-to-Line Voltage Buffer

Read Line-to-Neutral Voltage Buffer

Read Power Buffer 1

Read Power Buffer 2

Read Energy Buffer

Read Flags Buffer

Read Setpoints Buffer

Write Slave Action

 

AEM II Commands:

Read Fast Status

Read Setpoints Buffer

Write Current Date and Time

Write Slave Action

 

Universal RTD Commands:

Read Fast Status

Read Temperature Buffer

Read Flags Buffer

Read Setpoints Buffer

 

CMU (Central Monitoring Unit) Commands:

Read Fast Status

Read Setpoints Buffer

Write Current Date and Time

Write Slave Action

 

ACM (Advantage Control Module) Commands:

Read Fast Status

Read Current Buffer

Read Flags Buffer

Read Setpoints Buffer

Read Time-Stamped Trip Data Buffer

Read ACM Status

Write Slave Action

 

IQ DP-4000 Commands:

Read Current Buffer

Read Line-to-Line Voltage Buffer

Read Line-to-Neutral Voltage Buffer

Read Power Buffer

Read Expanded Power Buffer

Read THD Buffer

Read Trip Data Buffer

Read Flags Buffer

Read System Energy Buffer

Read Fast Status

Addressable Relay Commands : Energize Relay

COMMAND DESCRIPTION:

This command requests the specifically addressed slave device to

energize its relay.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 0

HMITalk1.DriverP2 = 2048 (800h)

Addressable Relay Commands : De-energize Relay

COMMAND DESCRIPTION:

This command requests the specifically addressed slave device to

de-energize its relay.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 0

HMITalk1.DriverP2 = 2304 (900h)

Addressable Relay Commands : Read Status

COMMAND DESCRIPTION:

This command requests the specifically addressed slave device to

transmit its status (ie. its two status bits/digital inputs).

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Input

HMITalk1.DriverNumPoints = 1-2

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 0

HMITalk1.DriverP2 = 5376 (1500h)

 

RETURNS:

- HMITalk1.PointValue(0) = Status of input #1

- HMITalk1.PointValue(1) = Status of input #2

 

Advantage Commands : Read Fast Status

COMMAND DESCRIPTION:

This command retrieves information about the current

status.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-8

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 1

HMITalk1.DriverP2 = 768 (300h)

 

RETURNS:

- HMITalk1.PointValue(0) = Division Code.

- HMITalk1.PointValue(1) = Communications Software Version.

- HMITalk1.PointValue(2) = Product ID.

6 = Size 3, 4 Starter, 3 PH.

8 = Size 1, 2 Starter, 3 PH.

9 = Size 5, 6 Starter, 3 PH.

10 = Size 3, 4 Overload, 3 PH.

11 = Size 1, 2 Overload, 3 PH.

13 = Size 5, 6 Overload, 3 PH.

14 = Size 3, 4 Contactor.

23 = Size 5, 6 Contactor.

24 = Size 1, 2 Contactor.

25 = Size 1L Starter, 3 PH.

26 = Size 1L Starter, 1 PH.

27 = Size 1L Overload, 3 PH.

28 = Size 1, 2 Starter, 1 PH.

- HMITalk1.PointValue(3) = Status.

0 = Opened, Off or Ready (Normal Inactive)

1 = Closed, On or Running (Normal Active)

2 = Tripped (Abnormal Inactive)

3 = Alarmed (Abnormal Active)

- HMITalk1.PointValue(4) = If 1, tripped or opened by remote communications.

- HMITalk1.PointValue(5) = If 1, powered on since last status read request.

- HMITalk1.PointValue(6) = Set when trip detected, cleared when the trip buffer is read.

- HMITalk1.PointValue(7) = Set indicates PONI-Advantage communications is functional.

Advantage Commands : Read Current Buffer

COMMAND DESCRIPTION:

This command retrieves information about the current phases

and current IX. Currents are expressed in amperes.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-4

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 1

HMITalk1.DriverP2 = 773 (305h)

 

RETURNS:

- HMITalk1.PointValue(0) = Phase current IA (Amperes).

- HMITalk1.PointValue(1) = Phase current IB (Amperes).

- HMITalk1.PointValue(2) = Phase current IC (Amperes).

- HMITalk1.PointValue(3) = Current IX (Amperes).

Note:

Current IX will usually be ground current. For some products, this

current may be either fourth pole current or neutral current. These

latter cases will not have ground current.

Advantage Commands : Read Flags Buffer

COMMAND DESCRIPTION:

This command retrieves extended information about the current

operating conditions.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-13

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 1

HMITalk1.DriverP2 = 968 (3C8h)

 

RETURNS:

- HMITalk1.PointValue(0) = Run/Closed indication.

- HMITalk1.PointValue(1) = Ready/Open indication.

- HMITalk1.PointValue(2) = Trip indication.

- HMITalk1.PointValue(3) = Overload.

- HMITalk1.PointValue(4) = If 1, Run Permit Signal present.

- HMITalk1.PointValue(5) = If 1, Start Signal present.

- HMITalk1.PointValue(6) = Not If 1, Remote Reset present.

- HMITalk1.PointValue(7) = Not If 1, Local Reset present.

- HMITalk1.PointValue(8) = Trip type:

1 = Overload

2 = Ground Current Trip

3 = Phase Loss Trip

4 = Phase Unbalance Trip

16 = Ground. Current exceeds interrupt capacity.

32 = Control Voltage too low. Unit will open.

48 = Control Voltage too low to pick up.

64 = Control Voltage too high to pick up.

80 = Current to low to close.

112 = External Trip (via remote communications).

- HMITalk1.PointValue(9) = Coil Voltage (units of volts).

- HMITalk1.PointValue(10) = Maximum Coil Current on closing.

- HMITalk1.PointValue(11) = Time equivalent of the delay from the middle

of each half cycle, to the beginning of

holding pulse.

- HMITalk1.PointValue(12) = The recorded holding current.

Advantage Commands : Read Setpoints Buffer

COMMAND DESCRIPTION:

This request gives a Setpoints Buffer description.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-12

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 1

HMITalk1.DriverP2 = 969 (3C9h)

 

RETURNS:

Dipheater:

- HMITalk1.PointValue(0) = Heater number (0-31).

- HMITalk1.PointValue(1) = Overload type:

0 = Class 10 Overload.

1 = Class 20 Overload.

2 = Class 30 Overload.

3 = No protection.

- HMITalk1.PointValue(2) = If 1, Automatic Reset.

Econfig:

- HMITalk1.PointValue(3) = If 1, Ground Fault enabled.

- HMITalk1.PointValue(4) = If 1, Phase Protection enabled.

- HMITalk1.PointValue(5) = If 1, Thermal Overload enabled.

- HMITalk1.PointValue(6) = If 1, unit is 50 Hz. If 0, unit is 60 Hz.

- HMITalk1.PointValue(7) = If 1, Unit is an Overload. If 0, Unit is

a Contactor/Starter.

- HMITalk1.PointValue(8) = If 1, Ultrasonic holding enabled.

- HMITalk1.PointValue(9) = If 1, Local Reset is disabled.

- HMITalk1.PointValue(10) = If 1, Unit will not reset thermal trip on

power up, even if reset conditions met.

- HMITalk1.PointValue(11) = ROM version of the Sure chip.

Advantage Commands : Read Time Stamped Trip Data Buffer

COMMAND DESCRIPTION:

This request is for use with products that provide "time stamping" or

trip data. When the product receives a Fast-Status request, it resets

an on-board Trip Time Offset clock. Should the product perform a

protective trip, the product records the value of the Trip Time Offset

clock at the instant of the trip. The value of the Trip Time

Offset clock then represents the elapsed time between the las time

mark (Fast-Status) received from the master and the time at

which the product tripped. The resolution of the product Trip

Time Offset clock is assumed to be 1/256 of a second.

When a protective trip ocurrs, the product records the following

data into a TIME STAMPED TRIP DATA buffer:

- Trip Time Offset clock

- Metered values

- Flags

- Setpoints

The Trip Time Offset clock continues to run. If a product has more

than one TIME STAMPED TRIP DATA buffer, it will over-write the oldest

buffer. If a product has only one TIME STAMPED TRIP DATA buffer, it

will be over-written.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-31

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 1

HMITalk1.DriverP2 = 971 (3CBh)

 

RETURNS:

- HMITalk1.PointValue(0) = TRIP DATA Buffer number.

- HMITalk1.PointValue(1) = Number of unread TRIP DATA Buffers.

- HMITalk1.PointValue(2) = TRIP TIME OFFSET.

- HMITalk1.PointValue(3) = Phase A Current.

- HMITalk1.PointValue(4) = Phase B Current.

- HMITalk1.PointValue(5) = Phase C Current.

Flags Buffer (same as Read Flags Buffer command):

- HMITalk1.PointValue(6) = Run/Closed indication.

- HMITalk1.PointValue(7) = Ready/Open indication.

- HMITalk1.PointValue(8) = Trip indication.

- HMITalk1.PointValue(9) = Overload.

- HMITalk1.PointValue(10) = If 1, Run Permit Signal present.

- HMITalk1.PointValue(11) = If 1, Start Signal present.

- HMITalk1.PointValue(12) = Not If 1, Remote Reset present.

- HMITalk1.PointValue(13) = Not If 1, Local Reset present.

- HMITalk1.PointValue(14) = Trip type:

1 = Overload

2 = Ground Current Trip

3 = Phase Loss Trip

4 = Phase Unbalance Trip

16 = Ground. Current exceeds interrupt capacity.

32 = Control Voltage too low. Unit will open.

48 = Control Voltage too low to pick up.

64 = Control Voltage too high to pick up.

80 = Current to low to close.

112 = External Trip (via remote communications).

- HMITalk1.PointValue(15) = Coil Voltage (units of volts).

- HMITalk1.PointValue(16) = Maximum Coil Current on closing.

- HMITalk1.PointValue(17) = Time equivalent of the delay from the middle

of each half cycle, to the beginning of

holding pulse.

- HMITalk1.PointValue(18) = The recorded holding current.

Setpoints Buffer (same as Read Setpoints Buffer command):

Dipheater:

- HMITalk1.PointValue(19) = Heater number (0-31).

- HMITalk1.PointValue(20) = Overload type:

0 = Class 10 Overload.

1 = Class 20 Overload.

2 = Class 30 Overload.

3 = No protection.

- HMITalk1.PointValue(21) = If 1, Automatic Reset.

Econfig:

- HMITalk1.PointValue(22) = If 1, Ground Fault enabled.

- HMITalk1.PointValue(23) = If 1, Phase Protection enabled.

- HMITalk1.PointValue(24) = If 1, Thermal Overload enabled.

- HMITalk1.PointValue(25) = If 1, unit is 50 Hz. If 0, unit is 60 Hz.

- HMITalk1.PointValue(26) = If 1, Unit is an Overload. If 0, Unit is

a Contactor/Starter.

- HMITalk1.PointValue(27) = If 1, Ultrasonic holding enabled.

- HMITalk1.PointValue(28) = If 1, Local Reset is disabled.

- HMITalk1.PointValue(29) = If 1, Unit will not reset thermal trip on

power up, even if reset conditions met.

- HMITalk1.PointValue(30) = ROM version of the Sure chip.

Advantage Commands : Write Slave Action

COMMAND DESCRIPTION:

This command results in the device performing an action as

detailed below. The value sent will be the current value

contained in the HMITalk1.PointValue(0) property.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 1

HMITalk1.DriverP2 = 976 (3D0h)

 

VALUE TO SEND:

0 = Reset Trip/Unit.

1 = Reset TRIP DATA Buffer.

2 = Start.

3 = Trip/Stop.

 

Digitrip II Commands : Read Fast Status

COMMAND DESCRIPTION:

This command retrieves information about the current

status.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-6

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 2

HMITalk1.DriverP2 = 768 (300h)

 

RETURNS:

- HMITalk1.PointValue(0) = Division Code.

- HMITalk1.PointValue(1) = Communications Software Version.

- HMITalk1.PointValue(2) = Product ID (= 1).

- HMITalk1.PointValue(3) = Status.

0 = Opened, Off or Ready (Normal Inactive)

1 = Closed, On or Running (Normal Active)

2 = Tripped (Abnormal Inactive)

3 = Alarmed (Abnormal Active)

- HMITalk1.PointValue(4) = If 1, opened by remote communications.

- HMITalk1.PointValue(5) = If 1, powered on since last status read request.

Digitrip II Commands : Read Data Buffer

COMMAND DESCRIPTION:

This command retrieves all the device's information in a

single request.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-29

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 2

HMITalk1.DriverP2 = 784 (310h)

 

RETURNS:

- HMITalk1.PointValue(0) = If 1, Long Delay Trip.

- HMITalk1.PointValue(1) = If 1, Short Delay Trip.

- HMITalk1.PointValue(2) = If 1, Instantaneous Trip.

- HMITalk1.PointValue(3) = If 1, Discriminator Trip.

- HMITalk1.PointValue(4) = If 1, Ground Fault.

- HMITalk1.PointValue(5) = If 1, Test Initiated.

- HMITalk1.PointValue(6) = If 1, Test Started.

- HMITalk1.PointValue(7) = If 1, Phase Test Initiated.

- HMITalk1.PointValue(8) = If 1, Breaker Trip.

- HMITalk1.PointValue(9) = If 1, RAM Error.

- HMITalk1.PointValue(10) = If 1, ROM Error.

- HMITalk1.PointValue(11) = If 1, Open as a result of a remote communications

shed command.

- HMITalk1.PointValue(12) = If 1, High Load Alarm.

- HMITalk1.PointValue(13) = If 1, Negative Power Reading.

- HMITalk1.PointValue(14) = If 1, Override Trip.

- HMITalk1.PointValue(15) = Hertz Flag (0 = 60 Hz, 1 = 50 Hz).

- HMITalk1.PointValue(16) = If 1, Long Delay Protection (LDPU) in progress.

- HMITalk1.PointValue(17) = If 1, Ground Test Initiated.

- HMITalk1.PointValue(18) = Status of breaker (1 = open, 0 = closed).

- HMITalk1.PointValue(19) = Plug Trip (1 = bad plug or no plug).

- HMITalk1.PointValue(20) = Average Power.

- HMITalk1.PointValue(21) = Peak Demand.

- HMITalk1.PointValue(22) = Energy.

- HMITalk1.PointValue(23) = Phase A Current.

- HMITalk1.PointValue(24) = Phase B Current.

- HMITalk1.PointValue(25) = Phase C Current.

- HMITalk1.PointValue(26) = Ground Current.

- HMITalk1.PointValue(27) = FRAME:

0 = Bad

1 = Reserved

2 = SPB3

3 = SPB5

4-5 = Reserved

6 = DS

7 = Hundt Weber

8-9 = Reserved

10 = RD-HW

11 = RD-CL

12-13 = Reserved

14-15 = Bad

- HMITalk1.PointValue(28) = Plug Factor:

0 = 100

2 = 200

4 = 250

6 = 300

8 = 400

10 = 600

12 = 800

14 = 1000

16 = 1200

18 = 1600

20 = 2000

22 = 2500

24 = 3000

26 = 3200

28 = 4000

30 = 5000

Digitrip II Commands : Reset Peak Demand

COMMAND DESCRIPTION:

This command resets the peak demand. Supported only by

communication software version of 1 or greater.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 2

HMITalk1.DriverP2 = 800 (320h)

Digitrip II Commands : Shed Load

COMMAND DESCRIPTION:

This command performs a shed load.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 2

HMITalk1.DriverP2 = 816 (330h)

Digitrip II Commands : Restore Load

COMMAND DESCRIPTION:

This command performs a restore load.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 2

HMITalk1.DriverP2 = 832 (340h)

Digitrip II Commands : Reset Energy

COMMAND DESCRIPTION:

This command performs an energy reset. Supported only by

communication software version of 2 or greater.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 2

HMITalk1.DriverP2 = 848 (350h)

 

Advantage Control PONI Commands : Start

COMMAND DESCRIPTION:

This command requests the specifically addressed slave device to

start.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 3

HMITalk1.DriverP2 = 2048 (800h)

Advantage Control PONI Commands : Stop

COMMAND DESCRIPTION:

This command requests the specifically addressed slave device to

stop.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 3

HMITalk1.DriverP2 = 2304 (900h)

Advantage Control PONI Commands : Read Status

COMMAND DESCRIPTION:

This command requests the specifically addressed slave device to

transmit its status.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 3

HMITalk1.DriverP2 = 5376 (1500h)

 

RETURNS:

- HMITalk1.PointValue(0) = Status

0 = Open.

1 = Closed.

2 = Tripped.

3 = Alarmed.

 

IQ Energy Sentinel : Read Fast Status

COMMAND DESCRIPTION:

This command retrieves information about the current

status.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-7

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 4

HMITalk1.DriverP2 = 768 (300h)

 

RETURNS:

- HMITalk1.PointValue(0) = Division Code.

- HMITalk1.PointValue(1) = Communications Software Version.

- HMITalk1.PointValue(2) = Product ID.

31 = F Frame Energy Monitor.

32 = J Frame Energy Monitor.

33 = K Frame Energy Monitor.

- HMITalk1.PointValue(3) = Status.

0 = Inactive

1 = Active

2 = Not Used

3 = Alarm (eg. Phase alarm)

- HMITalk1.PointValue(4) = If 1, opened by remote communications.

- HMITalk1.PointValue(5) = If 1, powered on since last Reset (sync) Demand Window.

- HMITalk1.PointValue(6) = Unread Energy Snapshot Available.

IQ Energy Sentinel : Read Power Buffer

COMMAND DESCRIPTION:

This command retrieves information about power, power demand

and energy.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 4

HMITalk1.DriverP2 = 776 (308h)

 

RETURNS:

- HMITalk1.PointValue(0) = Instantaneous Power (Watts).

- HMITalk1.PointValue(1) = 5-Minute Average of Power (Watts).

- HMITalk1.PointValue(2) = Energy (Watt hours).

IQ Energy Sentinel : Read Energy Buffer

COMMAND DESCRIPTION:

This command retrieves the value for energy, in units

of Kilowatts hour.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 4

HMITalk1.DriverP2 = 778 (30Ah)

 

RETURNS:

- HMITalk1.PointValue(0) = Energy (Ranges from 0 to 16,777,215 KWH).

IQ Energy Sentinel : Read Flags Buffer

COMMAND DESCRIPTION:

This command retrieves flags information, temperature, average

of power, etc.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-17

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 4

HMITalk1.DriverP2 = 968 (3C8h)

 

RETURNS:

- HMITalk1.PointValue(0) = If 1, Demand for Phase A is zero.

- HMITalk1.PointValue(1) = If 1, Demand for Phase B is zero.

- HMITalk1.PointValue(2) = If 1, Demand for Phase C is zero.

- HMITalk1.PointValue(3) = If 1, Energy for Phase A is negative.

- HMITalk1.PointValue(4) = If 1, Energy for Phase A is negative.

- HMITalk1.PointValue(5) = If 1, Energy for Phase A is negative.

- HMITalk1.PointValue(6) = If 1, Energy tally error (tally zeroed).

- HMITalk1.PointValue(7) = If 1, EEPROM Error.

- HMITalk1.PointValue(8) = If 1, RAM Error.

- HMITalk1.PointValue(9) = If 1, ROM Error.

- HMITalk1.PointValue(10) = If 1, Over temperature warning.

- HMITalk1.PointValue(11) = If 1, Calibration factor error.

- HMITalk1.PointValue(12) = If 1, Power failure first sample.

- HMITalk1.PointValue(13) = If 1, Power failure second sample.

- HMITalk1.PointValue(14) = Temperature.

- HMITalk1.PointValue(15) = 5-Minute average power update counter (0-251).

This counter resets to zero when the demand window

is reset. It rolls over after 21 hours (after

counting up to 251).

- HMITalk1.PointValue(16) = 5-Minute average of power.

IQ Energy Sentinel : Write Slave Action

COMMAND DESCRIPTION:

This command results in the device performing an action as

detailed below. The value sent will be the current value

contained in the HMITalk1.PointValue(0) property.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 4

HMITalk1.DriverP2 = 976 (3D0h)

 

VALUE TO SEND:

0 = No action.

1 = Reset Demand Window.

2 = Save Energy Buffer.

3 = Both actions.

IQ Energy Sentinel : Broadcast Save Energy Buffer

COMMAND DESCRIPTION:

This command informs all connected devices to save their

energy buffers. HMITalk1.PointValue(0) is ignored.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = 0

HMITalk1.DriverP1 = 4

HMITalk1.DriverP2 = 3328 (D00h)

IQ Energy Sentinel : Broadcast Reset Demand Window

COMMAND DESCRIPTION:

This command informs all connected devices to reset their

demand windows. HMITalk1.PointValue(0) is ignored.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = 0

HMITalk1.DriverP1 = 4

HMITalk1.DriverP2 = 3329 (D01h)

 

IQ 1000 II Commands : Read Fast Status

COMMAND DESCRIPTION:

This command retrieves information about the current

status.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-6

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 5

HMITalk1.DriverP2 = 768 (300h)

 

RETURNS:

- HMITalk1.PointValue(0) = Division Code.

- HMITalk1.PointValue(1) = Communications Software Version.

- HMITalk1.PointValue(2) = Product ID (= 3).

- HMITalk1.PointValue(3) = Status.

0 = Opened, Off or Ready (Normal Inactive)

1 = Closed, On or Running (Normal Active)

2 = Tripped (Abnormal Inactive)

3 = Alarmed (Abnormal Active)

- HMITalk1.PointValue(4) = If 1, opened by remote communications.

- HMITalk1.PointValue(5) = If 1, powered on since last status read request.

IQ 1000 II Commands : Read Current Buffer

COMMAND DESCRIPTION:

This command retrieves information about the current phases

and current IX. Currents are expressed in amperes.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-4

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 5

HMITalk1.DriverP2 = 773 (305h)

 

RETURNS:

- HMITalk1.PointValue(0) = Phase current IA (Amperes).

- HMITalk1.PointValue(1) = Phase current IB (Amperes).

- HMITalk1.PointValue(2) = Phase current IC (Amperes).

- HMITalk1.PointValue(3) = Current IX (Amperes).

Note:

Current IX will usually be ground current. For some products, this

current may be either fourth pole current or neutral current. These

latter cases will not have ground current.

IQ 1000 II Commands : Read Temperature Buffer

COMMAND DESCRIPTION:

This command retrieves the temperature in degrees for six motor

windings temperatures, two motor bearing temperatures, two load

bearing temperatures and one ambient temperature.

Temperatures range form 0 to 255 degrees centigrade.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-13

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 5

HMITalk1.DriverP2 = 783 (30Fh)

HMITalk1.DriverP3 = 1

 

RETURNS:

- HMITalk1.PointValue(0) = Windind Temperature 1.

- HMITalk1.PointValue(1) = Windind Temperature 2.

- HMITalk1.PointValue(2) = Windind Temperature 3.

- HMITalk1.PointValue(3) = Windind Temperature 4.

- HMITalk1.PointValue(4) = Windind Temperature 5.

- HMITalk1.PointValue(5) = Windind Temperature 6.

- HMITalk1.PointValue(6) = Motor Bearing Temperature 1.

- HMITalk1.PointValue(7) = Motor Bearing Temperature 2.

- HMITalk1.PointValue(8) = Load Bearing Temperature 1.

- HMITalk1.PointValue(9) = Load Bearing Temperature 2.

- HMITalk1.PointValue(10) = Auxiliary Temperature.

- HMITalk1.PointValue(11) = Temperature Validity 1.

- HMITalk1.PointValue(12) = Temperature Validity 2.

NOTE:

The Temperature Validity values are used to represent the presence

of a selector sensor.

IQ 1000 II Commands : Read Flags Buffer

COMMAND DESCRIPTION:

This command retrieves extended information about the current

operating conditions.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-45

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 5

HMITalk1.DriverP2 = 968 (3C8h)

 

RETURNS:

- HMITalk1.PointValue(0) = If 1, Instantaneous Over Current Trip.

- HMITalk1.PointValue(1) = If 1, I-Squared T Trip.

- HMITalk1.PointValue(2) = If 1, Phase Unbalance Trip.

- HMITalk1.PointValue(3) = If 1, Ground Fault Trip.

- HMITalk1.PointValue(4) = If 1, Jam Trip.

- HMITalk1.PointValue(5) = If 1, Under Load Trip.

- HMITalk1.PointValue(6) = If 1, Trip Bypass.

- HMITalk1.PointValue(7) = If 1, Remote Trip (via hardware input).

- HMITalk1.PointValue(8) = If 1, Motor Bearing Temperature Trip.

- HMITalk1.PointValue(9) = If 1, Load Bearing Temperature Trip.

- HMITalk1.PointValue(10) = If 1, Winding Temperature Trip.

- HMITalk1.PointValue(11) = If 1, Reverse Sequence Trip.

- HMITalk1.PointValue(12) = If 1, Incomplete Sequence Trip.

- HMITalk1.PointValue(13) = If 1, A/D Converter Error.

- HMITalk1.PointValue(14) = If 1, RAM Error.

- HMITalk1.PointValue(15) = If 1, ROM Error.

- HMITalk1.PointValue(16) = If 1, Opto-coupler Failure.

- HMITalk1.PointValue(17) = If 1, Transition Not Completed.

- HMITalk1.PointValue(18) = If 1, Full Load Amps/CT Value Error.

- HMITalk1.PointValue(19) = If 1, Battery Low.

- HMITalk1.PointValue(20) = If 1, External Trip (via INCOM).

- HMITalk1.PointValue(21) = If 1, Differential Trip on AC Input.

- HMITalk1.PointValue(22) = If 1, Ambient Temperature Trip.

- HMITalk1.PointValue(23) = If 1, Phase Unbalance Alarm

- HMITalk1.PointValue(24) = If 1, Winding Temperature Alarm.

- HMITalk1.PointValue(25) = If 1, Motor Bearing Temperature Alarm.

- HMITalk1.PointValue(26) = If 1, Load Bearing Temperature Alarm.

- HMITalk1.PointValue(27) = If 1, Jam Alarm.

- HMITalk1.PointValue(28) = If 1, Under Load Alarm.

- HMITalk1.PointValue(29) = If 1, Ambient Temperature Alarm.

- HMITalk1.PointValue(30) = If 1, I Squared T Alarm/Trip.

- HMITalk1.PointValue(31) = If 1, Starts per Hour Alarm/Trip.

- HMITalk1.PointValue(32) = Operations Count.

- HMITalk1.PointValue(33) = Run Time.

- HMITalk1.PointValue(34) = Remaining Starts.

- HMITalk1.PointValue(35) = Oldest Start Time.

- HMITalk1.PointValue(36) = Percent I2T.

- HMITalk1.PointValue(37) = Highest Phase Current.

- HMITalk1.PointValue(38) = Highest RTD Temperature.

- HMITalk1.PointValue(39) = Number of I2T Trips.

- HMITalk1.PointValue(40) = Number of Instantaneous Over Current Trips.

- HMITalk1.PointValue(41) = Number of Under Load Trips.

- HMITalk1.PointValue(42) = Number of Jam Trips.

- HMITalk1.PointValue(43) = Number of Ground Fault Trips.

- HMITalk1.PointValue(44) = Number of RTD Trips.

IQ 1000 II Commands : Read Setpoints Buffer

COMMAND DESCRIPTION:

This request gives a Setpoints Buffer description.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-46

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 5

HMITalk1.DriverP2 = 969 (3C9h)

 

RETURNS:

- HMITalk1.PointValue(0) = If 1, auto reset for I2T. If 0, manual reset for I2T.

- HMITalk1.PointValue(1) = If 1, 2 second trip delay on Phase Unbalance.

- HMITalk1.PointValue(2) = If 1, transition on time out. Else trip on time out.

- HMITalk1.PointValue(3) = If 1, unit is 50 Hz. If 0, unit is 60 Hz.

- HMITalk1.PointValue(4) = If 1, Trip Mode 2. If 0, Trip Mode 1.

- HMITalk1.PointValue(5) = If 1, reversing is allowed. If 0, non reversing mode.

- HMITalk1.PointValue(6) = If 1, Single Phase Operation. If 0, 3 Phase.

- HMITalk1.PointValue(7) = If 1, IOC Protection Disabled. If 0, IOC Enabled.

- HMITalk1.PointValue(8) = Current Loop Out Prop.:

0 = Current Loop Out Prop. to 100% Full Load

1 = Current Loop Out Prop. to 125% Full Load

2 = Current Loop Out Prop. to Max Winding RTD

3 = Current Loop Out Prop. to I2T Trip Level

- HMITalk1.PointValue(9) = Mode:

0 = Remote Reset

1 = Remote Trip

2 = Remote Differential Trip

3 = Motor Stop

4 = Reset Disabled

- HMITalk1.PointValue(10) = Winding Temperature Trip Setpoint.

- HMITalk1.PointValue(11) = Motor Bearing Temp Trip Setpoint.

- HMITalk1.PointValue(12) = Load Bearing Temp Trip Setpoint.

- HMITalk1.PointValue(13) = Ambient Temp Trip Setpoint.

- HMITalk1.PointValue(14) = Winding Temperature Alarm Setpoint.

- HMITalk1.PointValue(15) = Motor Bearing Temp Alarm Setpoint.

- HMITalk1.PointValue(16) = Load Bearing Temp Alarm Setpoint.

- HMITalk1.PointValue(17) = Ambient Temp Alarm Setpoint.

- HMITalk1.PointValue(18) = Ground Fault Trip Setpoint.

- HMITalk1.PointValue(19) = Ground Fault Start Delay Setpoint.

- HMITalk1.PointValue(20) = Ground Fault Run Delay Setpoint.

- HMITalk1.PointValue(21) = Inst Over Current Trip Setpoint.

- HMITalk1.PointValue(22) = Inst Over Current Start Delay Setpoint.

- HMITalk1.PointValue(23) = Locked Rotor Current Setpoint.

- HMITalk1.PointValue(24) = Locked Rotor Stall Time Setpoint.

- HMITalk1.PointValue(25) = Ultimate Trip Current Setpoint.

- HMITalk1.PointValue(26) = I Squared T Alarm Setpoint.

- HMITalk1.PointValue(27) = Jam Alarm Setpoint.

- HMITalk1.PointValue(28) = Jam Trip Setpoint.

- HMITalk1.PointValue(29) = Jam Start Delay Setpoint.

- HMITalk1.PointValue(30) = Jam Run Delay Setpoint.

- HMITalk1.PointValue(31) = Under Load Alarm Setpoint.

- HMITalk1.PointValue(32) = Under Load Trip Setpoint.

- HMITalk1.PointValue(33) = Under Load Start Delay Setpoint.

- HMITalk1.PointValue(34) = Under Load Run Delay Setpoint.

- HMITalk1.PointValue(35) = Phase Unbalance Alarm Setpoint.

- HMITalk1.PointValue(36) = Phase Unbalance Delay Setpoint.

- HMITalk1.PointValue(37) = Starts per minute Setpoint.

- HMITalk1.PointValue(38) = Starts time limit Setpoint.

- HMITalk1.PointValue(39) = Transition Current Level Setpoint.

- HMITalk1.PointValue(40) = Transition Time Setpoint.

- HMITalk1.PointValue(41) = Incomplete Sequence Time Setpoint.

- HMITalk1.PointValue(42) = Anti-backspin delay Setpoint.

- HMITalk1.PointValue(43) = Full Load Amps Setpoint.

- HMITalk1.PointValue(44) = Current Transformer Ratio.

- HMITalk1.PointValue(45) = Aux. Trip Delay:

0 = Normal Trip

1 = Unstantaneous Over Current Only

2 = Squared T Only

3 = Ground Fault Only

4 = Jam Only

5 = Under Load Only

6 = Motor Bearing Temperature Only

7 = Load Bearing Temperature Only

8 = Winding Temperature Only

9 = Reversing Only

IQ 1000 II Commands : Read Time-Stamped Trip Data Buffer

COMMAND DESCRIPTION:

This request is for use with products that provide "time stamping" or

trip data. When the product receives a Fast-Status request, it resets

an on-board Trip Time Offset clock. Should the product perform a

protective trip, the product records the value of the Trip Time Offset

clock at the instant of the trip. The value of the Trip Time

Offset clock then represents the elapsed time between the las time

mark (Fast-Status) received from the master and the time at

which the product tripped. The resolution of the product Trip

Time Offset clock is assumed to be 1/256 of a second.

When a protective trip ocurrs, the product records the following

data into a TIME STAMPED TRIP DATA buffer:

- Trip Time Offset clock

- Metered values

- Flags

- Setpoints

The Trip Time Offset clock continues to run. If a product has more

than one TIME STAMPED TRIP DATA buffer, it will over-write the oldest

buffer. If a product has only one TIME STAMPED TRIP DATA buffer, it

will be over-written.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-111

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 5

HMITalk1.DriverP2 = 971 (3CBh)

 

RETURNS:

- HMITalk1.PointValue(0) = TRIP DATA Buffer number.

- HMITalk1.PointValue(1) = Number of unread TRIP DATA Buffers.

- HMITalk1.PointValue(2) = TRIP TIME OFFSET.

- HMITalk1.PointValue(3) = Phase A Current.

- HMITalk1.PointValue(4) = Phase B Current.

- HMITalk1.PointValue(5) = Phase C Current.

- HMITalk1.PointValue(6) = Groung Fault Current.

- HMITalk1.PointValue(7) = Windind Temperature 1.

- HMITalk1.PointValue(8) = Windind Temperature 2.

- HMITalk1.PointValue(9) = Windind Temperature 3.

- HMITalk1.PointValue(10) = Windind Temperature 4.

- HMITalk1.PointValue(11) = Windind Temperature 5.

- HMITalk1.PointValue(12) = Windind Temperature 6.

- HMITalk1.PointValue(13) = Motor Bearing Temperature 1.

- HMITalk1.PointValue(14) = Motor Bearing Temperature 2.

- HMITalk1.PointValue(15) = Load Bearing Temperature 1.

- HMITalk1.PointValue(16) = Load Bearing Temperature 2.

- HMITalk1.PointValue(17) = Ambient Temperature.

- HMITalk1.PointValue(18) = Temperature Validity 1.

- HMITalk1.PointValue(19) = Temperature Validity 2.

Flags Buffer (same as Read Flags Buffer command):

- HMITalk1.PointValue(20) = If 1, Instantaneous Over Current Trip.

- HMITalk1.PointValue(21) = If 1, I-Squared T Trip.

- HMITalk1.PointValue(22) = If 1, Phase Unbalance Trip.

- HMITalk1.PointValue(23) = If 1, Ground Fault Trip.

- HMITalk1.PointValue(24) = If 1, Jam Trip.

- HMITalk1.PointValue(25) = If 1, Under Load Trip.

- HMITalk1.PointValue(26) = If 1, Trip Bypass.

- HMITalk1.PointValue(27) = If 1, Remote Trip (via hardware input).

- HMITalk1.PointValue(28) = If 1, Motor Bearing Temperature Trip.

- HMITalk1.PointValue(29) = If 1, Load Bearing Temperature Trip.

- HMITalk1.PointValue(30) = If 1, Winding Temperature Trip.

- HMITalk1.PointValue(31) = If 1, Reverse Sequence Trip.

- HMITalk1.PointValue(32) = If 1, Incomplete Sequence Trip.

- HMITalk1.PointValue(33) = If 1, A/D Converter Error.

- HMITalk1.PointValue(34) = If 1, RAM Error.

- HMITalk1.PointValue(35) = If 1, ROM Error.

- HMITalk1.PointValue(36) = If 1, Opto-coupler Failure.

- HMITalk1.PointValue(37) = If 1, Transition Not Completed.

- HMITalk1.PointValue(38) = If 1, Full Load Amps/CT Value Error.

- HMITalk1.PointValue(39) = If 1, Battery Low.

- HMITalk1.PointValue(40) = If 1, External Trip (via INCOM).

- HMITalk1.PointValue(41) = If 1, Differential Trip on AC Input.

- HMITalk1.PointValue(42) = If 1, Ambient Temperature Trip.

- HMITalk1.PointValue(43) = If 1, Phase Unbalance Alarm

- HMITalk1.PointValue(44) = If 1, Winding Temperature Alarm.

- HMITalk1.PointValue(45) = If 1, Motor Bearing Temperature Alarm.

- HMITalk1.PointValue(46) = If 1, Load Bearing Temperature Alarm.

- HMITalk1.PointValue(47) = If 1, Jam Alarm.

- HMITalk1.PointValue(48) = If 1, Under Load Alarm.

- HMITalk1.PointValue(49) = If 1, Ambient Temperature Alarm.

- HMITalk1.PointValue(50) = If 1, I Squared T Alarm/Trip.

- HMITalk1.PointValue(51) = If 1, Starts per Hour Alarm/Trip.

- HMITalk1.PointValue(52) = Operations Count.

- HMITalk1.PointValue(53) = Run Time.

- HMITalk1.PointValue(54) = Remaining Starts.

- HMITalk1.PointValue(55) = Oldest Start Time.

- HMITalk1.PointValue(56) = Percent I2T.

- HMITalk1.PointValue(57) = Highest Phase Current.

- HMITalk1.PointValue(58) = Highest RTD Temperature.

- HMITalk1.PointValue(59) = Number of I2T Trips.

- HMITalk1.PointValue(60) = Number of Instantaneous Over Current Trips.

- HMITalk1.PointValue(61) = Number of Under Load Trips.

- HMITalk1.PointValue(62) = Number of Jam Trips.

- HMITalk1.PointValue(63) = Number of Ground Fault Trips.

- HMITalk1.PointValue(64) = Number of RTD Trips.

Setpoints Buffer (same as Read Setpoints Buffer command):

- HMITalk1.PointValue(65) = If 1, auto reset for I2T. If 0, manual reset for I2T.

- HMITalk1.PointValue(66) = If 1, 2 second trip delay on Phase Unbalance.

- HMITalk1.PointValue(67) = If 1, transition on time out. Else trip on time out.

- HMITalk1.PointValue(68) = If 1, unit is 50 Hz. If 0, unit is 60 Hz.

- HMITalk1.PointValue(69) = If 1, Trip Mode 2. If 0, Trip Mode 1.

- HMITalk1.PointValue(70) = If 1, reversing is allowed. If 0, non reversing mode.

- HMITalk1.PointValue(71) = If 1, Single Phase Operation. If 0, 3 Phase.

- HMITalk1.PointValue(72) = If 1, IOC Protection Disabled. If 0, IOC Enabled.

- HMITalk1.PointValue(73) = Current Loop Out Prop.:

0 = Current Loop Out Prop. to 100% Full Load

1 = Current Loop Out Prop. to 125% Full Load

2 = Current Loop Out Prop. to Max Winding RTD

3 = Current Loop Out Prop. to I2T Trip Level

- HMITalk1.PointValue(74) = Mode:

0 = Remote Reset

1 = Remote Trip

2 = Remote Differential Trip

3 = Motor Stop

4 = Reset Disabled

- HMITalk1.PointValue(75) = Winding Temperature Trip Setpoint.

- HMITalk1.PointValue(76) = Motor Bearing Temp Trip Setpoint.

- HMITalk1.PointValue(77) = Load Bearing Temp Trip Setpoint.

- HMITalk1.PointValue(78) = Ambient Temp Trip Setpoint.

- HMITalk1.PointValue(79) = Winding Temperature Alarm Setpoint.

- HMITalk1.PointValue(80) = Motor Bearing Temp Alarm Setpoint.

- HMITalk1.PointValue(81) = Load Bearing Temp Alarm Setpoint.

- HMITalk1.PointValue(82) = Ambient Temp Alarm Setpoint.

- HMITalk1.PointValue(83) = Ground Fault Trip Setpoint.

- HMITalk1.PointValue(84) = Ground Fault Start Delay Setpoint.

- HMITalk1.PointValue(85) = Ground Fault Run Delay Setpoint.

- HMITalk1.PointValue(86) = Inst Over Current Trip Setpoint.

- HMITalk1.PointValue(87) = Inst Over Current Start Delay Setpoint.

- HMITalk1.PointValue(88) = Locked Rotor Current Setpoint.

- HMITalk1.PointValue(89) = Locked Rotor Stall Time Setpoint.

- HMITalk1.PointValue(90) = Ultimate Trip Current Setpoint.

- HMITalk1.PointValue(91) = I Squared T Alarm Setpoint.

- HMITalk1.PointValue(92) = Jam Alarm Setpoint.

- HMITalk1.PointValue(93) = Jam Trip Setpoint.

- HMITalk1.PointValue(94) = Jam Start Delay Setpoint.

- HMITalk1.PointValue(95) = Jam Run Delay Setpoint.

- HMITalk1.PointValue(96) = Under Load Alarm Setpoint.

- HMITalk1.PointValue(97) = Under Load Trip Setpoint.

- HMITalk1.PointValue(98) = Under Load Start Delay Setpoint.

- HMITalk1.PointValue(99) = Under Load Run Delay Setpoint.

- HMITalk1.PointValue(100) = Phase Unbalance Alarm Setpoint.

- HMITalk1.PointValue(101) = Phase Unbalance Delay Setpoint.

- HMITalk1.PointValue(102) = Starts per minute Setpoint.

- HMITalk1.PointValue(103) = Starts time limit Setpoint.

- HMITalk1.PointValue(104) = Transition Current Level Setpoint.

- HMITalk1.PointValue(105) = Transition Time Setpoint.

- HMITalk1.PointValue(106) = Incomplete Sequence Time Setpoint.

- HMITalk1.PointValue(107) = Anti-backspin delay Setpoint.

- HMITalk1.PointValue(108) = Full Load Amps Setpoint.

- HMITalk1.PointValue(109) = Current Transformer Ratio.

- HMITalk1.PointValue(110) = Aux. Trip Delay:

0 = Normal Trip

1 = Unstantaneous Over Current Only

2 = Squared T Only

3 = Ground Fault Only

4 = Jam Only

5 = Under Load Only

6 = Motor Bearing Temperature Only

7 = Load Bearing Temperature Only

8 = Winding Temperature Only

9 = Reversing Only

IQ 1000 II Commands : Write Slave Action

COMMAND DESCRIPTION:

This command results in the device performing an action as

detailed below. The value sent will be the current value

contained in the HMITalk1.PointValue(0) property.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 5

HMITalk1.DriverP2 = 976 (3D0h)

 

VALUE TO SEND:

0 = Reset Trip/Alarm.

1 = Reset TRIP DATA Buffer.

2 = Reset (peak) demand current.

3 = Trip (Stop).

 

IQ 500 Commands : Read Fast Status

COMMAND DESCRIPTION:

This command retrieves information about the current

status.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-6

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 6

HMITalk1.DriverP2 = 768 (300h)

 

RETURNS:

- HMITalk1.PointValue(0) = Division Code.

- HMITalk1.PointValue(1) = Communications Software Version.

- HMITalk1.PointValue(2) = Product ID.

16 = Size 1/2 (IQ 502).

18 = Size 3/4 (IQ 504).

- HMITalk1.PointValue(3) = Status.

0 = Opened, Off or Ready (Normal Inactive)

1 = Closed, On or Running (Normal Active)

2 = Tripped (Abnormal Inactive)

3 = Alarmed (Abnormal Active)

- HMITalk1.PointValue(4) = If 1, opened by remote communications.

- HMITalk1.PointValue(5) = If 1, powered on since last status read request.

IQ 500 Commands : Read Current Buffer

COMMAND DESCRIPTION:

This command retrieves information about the current phases

and current IX. Currents are expressed in amperes.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-4

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 6

HMITalk1.DriverP2 = 773 (305h)

 

RETURNS:

- HMITalk1.PointValue(0) = Phase current IA (Amperes).

- HMITalk1.PointValue(1) = Phase current IB (Amperes).

- HMITalk1.PointValue(2) = Phase current IC (Amperes).

- HMITalk1.PointValue(3) = Current IX (Amperes).

Note:

Current IX will usually be ground current. For some products, this

current may be either fourth pole current or neutral current. These

latter cases will not have ground current.

IQ 500 Commands : Read Flags Buffer

COMMAND DESCRIPTION:

This command retrieves extended information about the current

operating conditions.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-8

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 6

HMITalk1.DriverP2 = 968 (3C8h)

 

RETURNS:

- HMITalk1.PointValue(0) = If 1, Overload Trip.

- HMITalk1.PointValue(1) = If 1, Phase Unbalance Trip.

- HMITalk1.PointValue(2) = If 1, Ground Fault Trip.

- HMITalk1.PointValue(3) = If 1, Jam Trip.

- HMITalk1.PointValue(4) = If 1, ULM Trip.

- HMITalk1.PointValue(5) = If 1, Remote Trip.

- HMITalk1.PointValue(6) = If 1, Remote Reset.

- HMITalk1.PointValue(7) = If 1, O/L Alarm.

IQ 500 Commands : Read Setpoints Buffer

COMMAND DESCRIPTION:

This request gives a Setpoints Buffer description.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-6

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 6

HMITalk1.DriverP2 = 969 (3C9h)

 

RETURNS:

- HMITalk1.PointValue(0) = Dip Switch 1.

- HMITalk1.PointValue(1) = Dip Switch 2.

- HMITalk1.PointValue(2) = Dip Switch 3.

- HMITalk1.PointValue(3) = Dip Switch 4.

- HMITalk1.PointValue(4) = Dip Switch 5.

- HMITalk1.PointValue(5) = Dip Switch 6.

NOTE:

Plese refer to the IQ 500 User's Manual for

information on the meaning of the Dip switches.

IQ 500 Commands : Read Time-Stamped Trip Data Buffer

COMMAND DESCRIPTION:

This request is for use with products that provide "time stamping" or

trip data. When the product receives a Fast-Status request, it resets

an on-board Trip Time Offset clock. Should the product perform a

protective trip, the product records the value of the Trip Time Offset

clock at the instant of the trip. The value of the Trip Time

Offset clock then represents the elapsed time between the las time

mark (Fast-Status) received from the master and the time at

which the product tripped. The resolution of the product Trip

Time Offset clock is assumed to be 1/256 of a second.

When a protective trip ocurrs, the product records the following

data into a TIME STAMPED TRIP DATA buffer:

- Trip Time Offset clock

- Metered values

- Flags

- Setpoints

The Trip Time Offset clock continues to run. If a product has more

than one TIME STAMPED TRIP DATA buffer, it will over-write the oldest

buffer. If a product has only one TIME STAMPED TRIP DATA buffer, it

will be over-written.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-21

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 6

HMITalk1.DriverP2 = 971 (3CBh)

 

RETURNS:

- HMITalk1.PointValue(0) = TRIP DATA Buffer number.

- HMITalk1.PointValue(1) = Number of unread TRIP DATA Buffers.

- HMITalk1.PointValue(2) = TRIP TIME OFFSET.

- HMITalk1.PointValue(3) = Phase A Current.

- HMITalk1.PointValue(4) = Phase B Current.

- HMITalk1.PointValue(5) = Phase C Current.

- HMITalk1.PointValue(6) = Groung Fault Current.

Flags Buffer (same as Read Flags Buffer command):

- HMITalk1.PointValue(7) = If 1, Overload Trip.

- HMITalk1.PointValue(8) = If 1, Phase Unbalance Trip.

- HMITalk1.PointValue(9) = If 1, Ground Fault Trip.

- HMITalk1.PointValue(10) = If 1, Jam Trip.

- HMITalk1.PointValue(11) = If 1, ULM Trip.

- HMITalk1.PointValue(12) = If 1, Remote Trip.

- HMITalk1.PointValue(13) = If 1, Remote Reset.

- HMITalk1.PointValue(14) = If 1, O/L Alarm.

Setpoints Buffer (same as Read Setpoints Buffer command):

- HMITalk1.PointValue(15) = Dip Switch 1.

- HMITalk1.PointValue(16) = Dip Switch 2.

- HMITalk1.PointValue(17) = Dip Switch 3.

- HMITalk1.PointValue(18) = Dip Switch 4.

- HMITalk1.PointValue(19) = Dip Switch 5.

- HMITalk1.PointValue(20) = Dip Switch 6.

IQ 500 Commands : Write Slave Action

COMMAND DESCRIPTION:

This command results in the device performing an action as

detailed below. The value sent will be the current value

contained in the HMITalk1.PointValue(0) property.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 6

HMITalk1.DriverP2 = 976 (3D0h)

 

VALUE TO SEND:

0 = Reset Trip/Unit.

1 = Reset TRIP DATA Buffer.

2 = Trip (open).

 

IQ Data & IQ Generator Commands : Read Fast Status

COMMAND DESCRIPTION:

This command retrieves information about the current

status.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-6

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 7

HMITalk1.DriverP2 = 768 (300h)

 

RETURNS:

- HMITalk1.PointValue(0) = Division Code.

- HMITalk1.PointValue(1) = Communications Software Version.

- HMITalk1.PointValue(2) = Product ID (= 20).

- HMITalk1.PointValue(3) = Status.

0 = Opened, Off or Ready (Normal Inactive)

1 = Closed, On or Running (Normal Active)

2 = Tripped (Abnormal Inactive)

3 = Alarmed (Abnormal Active)

- HMITalk1.PointValue(4) = If 1, opened by remote communications.

- HMITalk1.PointValue(5) = If 1, powered on since last status read request.

IQ Data & IQ Generator Commands : Read Current Buffer

COMMAND DESCRIPTION:

This command retrieves information about the current phases.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 7

HMITalk1.DriverP2 = 773 (305h)

 

RETURNS:

- HMITalk1.PointValue(0) = Phase current IA (Amperes).

- HMITalk1.PointValue(1) = Phase current IB (Amperes).

- HMITalk1.PointValue(2) = Phase current IC (Amperes).

IQ Data & IQ Generator Commands : Read Line-to-Line Voltage Buffer

COMMAND DESCRIPTION:

This command retrieves information about the current line-to-line

voltages. Voltages are expressed in volts.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 7

HMITalk1.DriverP2 = 774 (306h)

 

RETURNS:

- HMITalk1.PointValue(0) = Line-to-line Voltage VAB (Volts).

- HMITalk1.PointValue(1) = Line-to-line Voltage VBC (Volts).

- HMITalk1.PointValue(2) = Line-to-line Voltage VCA (Volts).

IQ Data & IQ Generator Commands : Read Line-to-Neutral Voltage Buffer

COMMAND DESCRIPTION:

This command retrieves information about the current line-to-neutral

voltages. Voltages are expressed in volts.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 7

HMITalk1.DriverP2 = 775 (307h)

 

RETURNS:

- HMITalk1.PointValue(0) = Line-to-neutral Voltage VAN (Volts).

- HMITalk1.PointValue(1) = Line-to-neutral Voltage VBN (Volts).

- HMITalk1.PointValue(2) = Line-to-neutral Voltage VCN (Volts).

IQ Data & IQ Generator Commands : Read Power Buffer

COMMAND DESCRIPTION:

This command retrieves information about the system's present

frequency. Frequency is expressed in hertz.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 7

HMITalk1.DriverP2 = 777 (309h)

 

RETURNS:

- HMITalk1.PointValue(0) = System Frequency (Hertz).

IQ Data & IQ Generator Commands : Read Flags Buffer

COMMAND DESCRIPTION:

This command retrieves extended information about the current

operating conditions.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-2

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 7

HMITalk1.DriverP2 = 968 (3C8h)

 

RETURNS:

- HMITalk1.PointValue(0) = If 1, RAM Failure.

- HMITalk1.PointValue(1) = If 1, EE o CAL erro.

IQ Data & IQ Generator Commands : Read Setpoints Buffer

COMMAND DESCRIPTION:

This request gives a Setpoints Buffer description.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-16

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 7

HMITalk1.DriverP2 = 969 (3C9h)

 

RETURNS:

- HMITalk1.PointValue(0) = JUMP1 (SW1), Switch 1.

- HMITalk1.PointValue(1) = JUMP1 (SW1), Switch 2.

- HMITalk1.PointValue(2) = JUMP1 (SW1), Switch 3.

- HMITalk1.PointValue(3) = JUMP1 (SW1), Switch 4.

- HMITalk1.PointValue(4) = JUMP1 (SW1), Switch 5.

- HMITalk1.PointValue(5) = JUMP1 (SW1), Switch 6.

- HMITalk1.PointValue(6) = JUMP1 (SW1), Switch 7.

- HMITalk1.PointValue(7) = JUMP1 (SW1), Switch 8.

- HMITalk1.PointValue(8) = JUMP2 (SW2), Switch 1.

- HMITalk1.PointValue(9) = JUMP2 (SW2), Switch 2.

- HMITalk1.PointValue(10) = JUMP2 (SW2), Switch 3.

- HMITalk1.PointValue(11) = JUMP2 (SW2), Switch 4.

- HMITalk1.PointValue(12) = JUMP2 (SW2), Switch 5.

- HMITalk1.PointValue(13) = JUMP2 (SW2), Switch 6.

- HMITalk1.PointValue(14) = JUMP2 (SW2), Switch 7.

- HMITalk1.PointValue(15) = JUMP2 (SW2), Switch 8.

NOTE:

JUMPx refers to SWITCHx in IQ DATA/GENERATOR User's Manual.

Refer to the IQ Data/IQ Generator User's Manual for

information on the meaning of the Dip switches.

 

IQ Data Plus II Commands : Read Trip Data Buffer

COMMAND DESCRIPTION:

This request retrieves Trip Data Buffer information.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-24

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 8

HMITalk1.DriverP2 = 970 (3CAh)

 

RETURNS:

- HMITalk1.PointValue(0) = If 1, Trip.

- HMITalk1.PointValue(1) = If 1, Alarm.

- HMITalk1.PointValue(2) = If 1, External.

- HMITalk1.PointValue(3) = If 1, Overvoltage.

- HMITalk1.PointValue(4) = If 1, Undervoltage.

- HMITalk1.PointValue(5) = If 1, Phase Unbalance.

- HMITalk1.PointValue(6) = If 1, Phase Loss.

- HMITalk1.PointValue(7) = If 1, Phase Reversal.

- HMITalk1.PointValue(8) = If 1, RAM or ROM Failure.

- HMITalk1.PointValue(9) = Phase A Current.

- HMITalk1.PointValue(10) = Phase B Current.

- HMITalk1.PointValue(11) = Phase C Current.

- HMITalk1.PointValue(12) = Voltage A-B.

- HMITalk1.PointValue(13) = Voltage B-C.

- HMITalk1.PointValue(14) = Voltage C-A.

- HMITalk1.PointValue(15) = Voltage A-N.

- HMITalk1.PointValue(16) = Voltage B-N.

- HMITalk1.PointValue(17) = Voltage C-N.

- HMITalk1.PointValue(18) = Watts.

- HMITalk1.PointValue(19) = Watts Demand.

- HMITalk1.PointValue(20) = Watt Hours.

- HMITalk1.PointValue(21) = Frequency.

- HMITalk1.PointValue(22) = VARs.

- HMITalk1.PointValue(23) = Power Factor.

IQ Data Plus II Commands : Read Fast Status

COMMAND DESCRIPTION:

This command retrieves information about the current

status.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-6

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 8

HMITalk1.DriverP2 = 768 (300h)

 

RETURNS:

- HMITalk1.PointValue(0) = Division Code.

- HMITalk1.PointValue(1) = Communications Software Version.

- HMITalk1.PointValue(2) = Product ID.

2 = IQ Data Plus II (Communications Version >= 5 only).

22 = IQ Data Plus II HV (High Voltage).

- HMITalk1.PointValue(3) = Status.

0 = Opened, Off or Ready (Normal Inactive)

1 = Closed, On or Running (Normal Active)

2 = Tripped (Abnormal Inactive)

3 = Alarmed (Abnormal Active)

- HMITalk1.PointValue(4) = If 1, opened by remote communications.

- HMITalk1.PointValue(5) = If 1, powered on since last status read request.

IQ Data Plus II Commands : Read Current Buffer

COMMAND DESCRIPTION:

This command retrieves information about the current phases.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 8

HMITalk1.DriverP2 = 773 (305h)

 

RETURNS:

- HMITalk1.PointValue(0) = Phase current IA (Amperes).

- HMITalk1.PointValue(1) = Phase current IB (Amperes).

- HMITalk1.PointValue(2) = Phase current IC (Amperes).

IQ Data Plus II Commands : Read Line-to-Line Voltage Buffer

COMMAND DESCRIPTION:

This command retrieves information about the current line-to-line

voltages. Voltages are expressed in volts.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 8

HMITalk1.DriverP2 = 774 (306h)

 

RETURNS:

- HMITalk1.PointValue(0) = Line-to-line Voltage VAB (Volts).

- HMITalk1.PointValue(1) = Line-to-line Voltage VBC (Volts).

- HMITalk1.PointValue(2) = Line-to-line Voltage VCA (Volts).

IQ Data Plus II Commands : Read Line-to-Neutral Voltage Buffer

COMMAND DESCRIPTION:

This command retrieves information about the current line-to-neutral

voltages. Voltages are expressed in volts.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 8

HMITalk1.DriverP2 = 775 (307h)

 

RETURNS:

- HMITalk1.PointValue(0) = Line-to-neutral Voltage VAN (Volts).

- HMITalk1.PointValue(1) = Line-to-neutral Voltage VBN (Volts).

- HMITalk1.PointValue(2) = Line-to-neutral Voltage VCN (Volts).

IQ Data Plus II Commands : Read Power Buffer 1

COMMAND DESCRIPTION:

This command retrieves information about the system's present

power value (in watts), the power demand and the energy (in

units of watt hours).

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 8

HMITalk1.DriverP2 = 776 (308h)

 

RETURNS:

- HMITalk1.PointValue(0) = Power (watts).

- HMITalk1.PointValue(1) = Power Demand (watts).

- HMITalk1.PointValue(2) = Energy (watt hours).

IQ Data Plus II Commands : Read Power Buffer 2

COMMAND DESCRIPTION:

This command retrieves information about the system's present

frequency, reactive power and power factor.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 8

HMITalk1.DriverP2 = 777 (309h)

 

RETURNS:

- HMITalk1.PointValue(0) = System Frequency (Hertz).

- HMITalk1.PointValue(1) = Reactive Power (vars).

- HMITalk1.PointValue(2) = Power Factor.

IQ Data Plus II Commands : Read Energy Buffer

COMMAND DESCRIPTION:

This command retrieves information about the value of

energy in units of Kilowatt hours.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 8

HMITalk1.DriverP2 = 778 (30Ah)

 

RETURNS:

- HMITalk1.PointValue(0) = Energy (Kilowatt hours).

NOTE:

The maximum range for energy is 0 to 16,777,215 KWH.

IQ Data Plus II Commands : Read Flags Buffer

COMMAND DESCRIPTION:

This command retrieves extended information about the current

operating conditions.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-9

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 8

HMITalk1.DriverP2 = 968 (3C8h)

 

RETURNS:

- HMITalk1.PointValue(0) = If 1, Trip.

- HMITalk1.PointValue(1) = If 1, Alarm.

- HMITalk1.PointValue(2) = If 1, External.

- HMITalk1.PointValue(3) = If 1, Overvoltage.

- HMITalk1.PointValue(4) = If 1, Undervoltage.

- HMITalk1.PointValue(5) = If 1, Phase Unbalance.

- HMITalk1.PointValue(6) = If 1, Phase Loss.

- HMITalk1.PointValue(7) = If 1, Phase Reversal.

- HMITalk1.PointValue(8) = If 1, RAM or ROM failure.

IQ Data Plus II Commands : Read Setpoints Buffer

COMMAND DESCRIPTION:

This request gives a Setpoints Buffer description.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-6

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 8

HMITalk1.DriverP2 = 969 (3C9h)

 

RETURNS:

- HMITalk1.PointValue(0) = Dip Switch SW1.

- HMITalk1.PointValue(1) = Dip Switch SW2.

- HMITalk1.PointValue(2) = Dip Switch SW3.

- HMITalk1.PointValue(3) = Dip Switch SW4.

- HMITalk1.PointValue(4) = Dip Switch SW5.

- HMITalk1.PointValue(5) = Dip Switch SW6.

NOTE:

Plese refer to the IQ Data Plus II User's Manual for

information on the meaning of the Dip switches.

IQ Data Plus II Commands : Write Slave Action

COMMAND DESCRIPTION:

This command results in the device performing an action as

detailed below. The value sent will be the current value

contained in the HMITalk1.PointValue(0) property.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 8

HMITalk1.DriverP2 = 976 (3D0h)

 

VALUE TO SEND:

0 = Reset Trip/Alarm.

1 = Reset TRIP DATA Buffer.

2 = Reset demand.

3 = Reset Energy (KWH).

4 = External Trip.

5 = Reset external Trip

 

AEM II Commands : Read Fast Status

COMMAND DESCRIPTION:

This command retrieves information about the current

status.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-9

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 9

HMITalk1.DriverP2 = 768 (300h)

 

RETURNS:

- HMITalk1.PointValue(0) = Division Code.

- HMITalk1.PointValue(1) = Communications Software Version.

1 = AEMII in AEMI compatibility mode.

3 or greater = AEMII in AEMII mode.

- HMITalk1.PointValue(2) = Product ID (= 1).

- HMITalk1.PointValue(3) = Status.

0 = Normal - Inactive (no devices detected on sub-network).

1 = Normal - Active.

2 = Tripped (a trip has ocurred and has not been acknowledged).

3 = Alarm (Digitrip in high load).

- HMITalk1.PointValue(4) = If 1, opened by remote communications.

- HMITalk1.PointValue(5) = If 1, powered on since last status read request.

- HMITalk1.PointValue(6) = If 1, was in learn mode.

- HMITalk1.PointValue(7) = If 1, in learn mode.

- HMITalk1.PointValue(8) = AEMII malfunction.

AEM II Commands : Read Setpoints Buffer

COMMAND DESCRIPTION:

This request gives a Setpoints Buffer description.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-4

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 9

HMITalk1.DriverP2 = 969 (3C9h)

 

RETURNS:

- HMITalk1.PointValue(0) = If 1, Learn mode. If 0, operational.

- HMITalk1.PointValue(1) = If 1, AEM II mode. If 0, AEM I mode.

- HMITalk1.PointValue(2) = If 1, 9600 baud. If 0, 1200 baud.

- HMITalk1.PointValue(3) = If 1, Test mode. If 0, operational.

AEM II Commands : Write Current Date and Time

COMMAND DESCRIPTION:

This request is used to send the real-time clock data (current date

and time) to a slave. 7 channels are needed to full specify date &

time information. Missing channels will be provided internally by

the driver according to current PC date & time information.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1-7

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 9

HMITalk1.DriverP2 = 984 (3D8h)

 

VALUES TO SEND:

- HMITalk1.PointValue(0) = 1/100 second.

- HMITalk1.PointValue(1) = Hour.

- HMITalk1.PointValue(2) = Minute.

- HMITalk1.PointValue(3) = Second.

- HMITalk1.PointValue(4) = Month.

- HMITalk1.PointValue(5) = Day.

- HMITalk1.PointValue(6) = Year.

AEM II Commands : Write Slave Action

COMMAND DESCRIPTION:

This command results in the device performing an action as

detailed below. The value sent will be the current value

contained in the HMITalk1.PointValue(0) property.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 9

HMITalk1.DriverP2 = 976 (3D0h)

 

VALUE TO SEND:

0 = Reset AEMII trip mode, acknowledge alarm.

1 = Reset device software (hardware reset).

2 = Reset trip buffer, purges all trips buffered.

 

Universal RTD Commands : Read Fast Status

COMMAND DESCRIPTION:

This command retrieves information about the current

status.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-6

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 10

HMITalk1.DriverP2 = 768 (300h)

 

RETURNS:

- HMITalk1.PointValue(0) = Division Code.

- HMITalk1.PointValue(1) = Communications Software Version.

- HMITalk1.PointValue(2) = Product ID (= 19).

- HMITalk1.PointValue(3) = Status.

0 = Failure.

1 = OK.

2 = Not used.

3 = Not used.

- HMITalk1.PointValue(4) = If 1, opened by remote communications.

- HMITalk1.PointValue(5) = If 1, powered on since last status read request.

Universal RTD Commands : Read Temperature Buffer

COMMAND DESCRIPTION:

This command retrieves the temperature in degrees for six motor

windings temperatures, two motor bearing temperatures, two load

bearing temperatures and one ambient temperature.

Temperatures range form 0 to 255 degrees centigrade.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-13

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 5

HMITalk1.DriverP2 = 783 (30Fh)

HMITalk1.DriverP3 = 1

 

RETURNS:

- HMITalk1.PointValue(0) = Windind Temperature 1.

- HMITalk1.PointValue(1) = Windind Temperature 2.

- HMITalk1.PointValue(2) = Windind Temperature 3.

- HMITalk1.PointValue(3) = Windind Temperature 4.

- HMITalk1.PointValue(4) = Windind Temperature 5.

- HMITalk1.PointValue(5) = Windind Temperature 6.

- HMITalk1.PointValue(6) = Motor Bearing Temperature 1.

- HMITalk1.PointValue(7) = Motor Bearing Temperature 2.

- HMITalk1.PointValue(8) = Load Bearing Temperature 1.

- HMITalk1.PointValue(9) = Load Bearing Temperature 2.

- HMITalk1.PointValue(10) = Auxiliary Temperature.

- HMITalk1.PointValue(11) = Temperature Validity 1.

- HMITalk1.PointValue(12) = Temperature Validity 2.

NOTE:

The Temperature Validity values are used to represent the presence

of a selector sensor.

Universal RTD Commands : Read Flags Buffer

COMMAND DESCRIPTION:

This command retrieves extended information about the current

operating conditions.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 10

HMITalk1.DriverP2 = 968 (3C8h)

 

RETURNS:

- HMITalk1.PointValue(0) = If 1, RAM failure.

Universal RTD Commands : Read Setpoints Buffer

COMMAND DESCRIPTION:

This request gives a Setpoints Buffer description.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-8

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 10

HMITalk1.DriverP2 = 969 (3C9h)

 

RETURNS:

- HMITalk1.PointValue(0) = SW1, switch 1.

- HMITalk1.PointValue(1) = SW1, switch 2.

- HMITalk1.PointValue(2) = SW1, switch 3.

- HMITalk1.PointValue(3) = SW1, switch 4.

- HMITalk1.PointValue(4) = SW1, switch 5.

- HMITalk1.PointValue(5) = SW1, switch 6.

- HMITalk1.PointValue(6) = SW1, switch 7.

- HMITalk1.PointValue(7) = SW1, switch 8.

NOTE:

0 = On

1 = Off

 

CMU (Central Monitoring Unit) Commands : Read Fast Status

COMMAND DESCRIPTION:

This command retrieves information about the current

status.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-9

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 11

HMITalk1.DriverP2 = 768 (300h)

 

RETURNS:

- HMITalk1.PointValue(0) = Division Code.

- HMITalk1.PointValue(1) = Communications Software Version.

- HMITalk1.PointValue(2) = Product ID (= 29).

- HMITalk1.PointValue(3) = Status.

0 = Normal - Inactive (no devices detected on sub-network).

1 = Normal - Active.

2 = Tripped (a trip has ocurred and has not been acknowledged).

3 = Alarm (Advantage in overload).

- HMITalk1.PointValue(4) = If 1, opened by remote communications.

- HMITalk1.PointValue(5) = If 1, powered on since last status read request.

- HMITalk1.PointValue(6) = If 1, was in learn mode.

- HMITalk1.PointValue(7) = If 1, in learn mode.

- HMITalk1.PointValue(8) = CMU malfunction.

CMU (Central Monitoring Unit) Commands : Read Setpoints Buffer

COMMAND DESCRIPTION:

This request gives a Setpoints Buffer description.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 11

HMITalk1.DriverP2 = 969 (3C9h)

 

RETURNS:

- HMITalk1.PointValue(0) = If 1, Learn mode. If 0, operational.

- HMITalk1.PointValue(1) = If 1, 9600 baud. If 0, 1200 baud.

- HMITalk1.PointValue(2) = If 1, Test mode. If 0, operational.

CMU (Central Monitoring Unit) Commands : Write Current Date and Time

COMMAND DESCRIPTION:

This request is used to send the real-time clock data (current date

and time) to a slave. 7 channels are needed to full specify date &

time information. Missing channels will be provided internally by

the driver according to current PC date & time information.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1-7

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 11

HMITalk1.DriverP2 = 984 (3D8h)

 

VALUES TO SEND:

- HMITalk1.PointValue(0) = 1/100 second.

- HMITalk1.PointValue(1) = Hour.

- HMITalk1.PointValue(2) = Minute.

- HMITalk1.PointValue(3) = Second.

- HMITalk1.PointValue(4) = Month.

- HMITalk1.PointValue(5) = Day.

- HMITalk1.PointValue(6) = Year.

CMU (Central Monitoring Unit) Commands : Write Slave Action

COMMAND DESCRIPTION:

This command results in the device performing an action as

detailed below. The value sent will be the current value

contained in the HMITalk1.PointValue(0) property.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 11

HMITalk1.DriverP2 = 976 (3D0h)

 

VALUE TO SEND:

0 = Reset CMU trip mode, acknowledge alarm.

1 = Reset device software (hardware reset).

2 = Reset trip buffer, purges all trips buffered.

 

ACM (Advantage Control Module) Commands : Read Fast Status

COMMAND DESCRIPTION:

This command retrieves information about the current

status.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-8

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 12

HMITalk1.DriverP2 = 768 (300h)

 

RETURNS:

- HMITalk1.PointValue(0) = Division Code.

- HMITalk1.PointValue(1) = Communications Software Version.

- HMITalk1.PointValue(2) = Product ID.

35 = Full voltage, non-reversing.

36 = Forward/Reverse.

37 = Fast/Slow - 2 winding.

38 = Fast/Slow - constant horsepower.

39 = Fast/Slow - constant torque.

40 = Reduced voltage - primary resintance.

41 = Reduced voltage - part winding.

42 = Reduced voltage - auto transformer.

43 = Reduced voltage - Wye-Delta open transition.

44 = Reduced voltage - Wye-Delta close transition.

45 = Metering.

- HMITalk1.PointValue(3) = Status.

0 = Open

1 = Closed

2 = Tripped

3 = Alarmed

- HMITalk1.PointValue(4) = If 1, tripped or opened by remote communications.

- HMITalk1.PointValue(5) = If 1, powered on since last status read request.

- HMITalk1.PointValue(6) = Set when trip detected, cleared when the trip buffer is read.

- HMITalk1.PointValue(7) = Set indicates W-PONI - ACM communications is functional.

ACM (Advantage Control Module) Commands : Read Current Buffer

COMMAND DESCRIPTION:

This command retrieves information about the current phases

and current IX. Currents are expressed in amperes.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-4

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 12

HMITalk1.DriverP2 = 773 (305h)

 

RETURNS:

- HMITalk1.PointValue(0) = Phase current IA (Amperes).

- HMITalk1.PointValue(1) = Phase current IB (Amperes).

- HMITalk1.PointValue(2) = Phase current IC (Amperes).

- HMITalk1.PointValue(3) = Current IX (Amperes).

Note:

Current IX will usually be ground current. For some products, this

current may be either fourth pole current or neutral current. These

latter cases will not have ground current.

ACM (Advantage Control Module) Commands : Read Flags Buffer

COMMAND DESCRIPTION:

This command retrieves extended information about the current

operating conditions.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-13

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 12

HMITalk1.DriverP2 = 968 (3C8h)

 

RETURNS:

- HMITalk1.PointValue(0) = Run/Closed Indication.

- HMITalk1.PointValue(1) = Ready/Open Indication.

- HMITalk1.PointValue(2) = Trip Indication.

- HMITalk1.PointValue(3) = If 1, Overload.

- HMITalk1.PointValue(4) = If 1, Run Permit Signal Present.

- HMITalk1.PointValue(5) = If 1, Start Signal Present.

- HMITalk1.PointValue(6) = If 0, Remote Reset Present.

- HMITalk1.PointValue(7) = If 0, Local Reset Present.

- HMITalk1.PointValue(8) = Trip Type:

1 = Overload Trip

2 = Ground Current Trip

3 = Phase Loss Trip

4 = Phase Unbalance Trip

16 = Ground. Current exceeds interrupt capacity.

32 = Control Voltage too low. Unit will open.

48 = Control Voltage too low to pick up.

64 = Control Voltage too high to pick up.

80 = Current to low to close.

112 = External Trip (via remote communications).

- HMITalk1.PointValue(9) = Coil Voltage (units of volts).

- HMITalk1.PointValue(10) = Maximum Coil Current on closing.

- HMITalk1.PointValue(11) = Time equivalent of the delay from the middle

of each half-cycle, to the beginning of

holding pulse.

- HMITalk1.PointValue(12) = The recorded holding current.

ACM (Advantage Control Module) Commands : Read Setpoints Buffer

COMMAND DESCRIPTION:

This request gives a Setpoints Buffer description.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-22

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 12

HMITalk1.DriverP2 = 969 (3C9h)

 

RETURNS:

Dipheater:

- HMITalk1.PointValue(0) = Heater number (0-31).

- HMITalk1.PointValue(1) = Overload type:

0 = Class 10 Overload.

1 = Class 20 Overload.

2 = Class 30 Overload.

3 = No protection.

- HMITalk1.PointValue(2) = If 1, Automatic Reset.

Econfig:

- HMITalk1.PointValue(3) = If 1, Ground Fault enabled.

- HMITalk1.PointValue(4) = If 1, Phase Protection enabled.

- HMITalk1.PointValue(5) = If 1, Thermal Overload enabled.

- HMITalk1.PointValue(6) = If 1, unit is 50 Hz. If 0, unit is 60 Hz.

- HMITalk1.PointValue(7) = If 1, Unit is an Overload. If 0, Unit is

a Contactor/Starter.

- HMITalk1.PointValue(8) = If 1, Ultrasonic holding enabled.

- HMITalk1.PointValue(9) = If 1, Local Reset is disabled.

- HMITalk1.PointValue(10) = If 1, Unit will not reset thermal trip on

power up, even if reset conditions met.

Surever:

- HMITalk1.PointValue(11) = Rom Version of the sure chip.

- HMITalk1.PointValue(12) = Product ID of starter #1 (at address 1).

- HMITalk1.PointValue(13) = Product ID of starter #1 (at address 4).

If the version is full voltage, forward/reverse or fast/slow.

ACM Status:

- HMITalk1.PointValue(14) = If 1, IMPACC Auto mode.

- HMITalk1.PointValue(15) = Reserved

- HMITalk1.PointValue(16) = Reserved

- HMITalk1.PointValue(17) = If 1, Starter #4. If 0, Starter #0.

- HMITalk1.PointValue(18) = If 1, Remote Auto mode.

- HMITalk1.PointValue(19) = If 1, ACM sub-network comm OK. If 0, comm failure.

- HMITalk1.PointValue(20) = Reserved

If the version is reduced voltage.

ACM Status:

- HMITalk1.PointValue(14) = If 1, IMPACC Auto mode.

- HMITalk1.PointValue(15) = If 1, Incomplete Sequence Trip.

- HMITalk1.PointValue(16) = If 1, Start transition in progress.

- HMITalk1.PointValue(17) = If 1, Anti-recycle lockout.

- HMITalk1.PointValue(18) = If 1, Remote Auto mode.

- HMITalk1.PointValue(19) = If 1, ACM sub-network comm OK. If 0, comm failure.

- HMITalk1.PointValue(20) = If 1, Transition time out trip.

ACM (Advantage Control Module) Commands : Read Time-Stamped Trip Data Buffer

COMMAND DESCRIPTION:

This request is for use with products that provide "time stamping" or

trip data. When the product receives a Fast-Status request, it resets

an on-board Trip Time Offset clock. Should the product perform a

protective trip, the product records the value of the Trip Time Offset

clock at the instant of the trip. The value of the Trip Time

Offset clock then represents the elapsed time between the las time

mark (Fast-Status) received from the master and the time at

which the product tripped. The resolution of the product Trip

Time Offset clock is assumed to be 1/256 of a second.

When a protective trip ocurrs, the product records the following

data into a TIME STAMPED TRIP DATA buffer:

- Trip Time Offset clock

- Metered values

- Flags

- Setpoints

The Trip Time Offset clock continues to run. If a product has more

than one TIME STAMPED TRIP DATA buffer, it will over-write the oldest

buffer. If a product has only one TIME STAMPED TRIP DATA buffer, it

will be over-written.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-44

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 12

HMITalk1.DriverP2 = 971 (3CBh)

 

RETURNS:

- HMITalk1.PointValue(0) = TRIP DATA Buffer number.

- HMITalk1.PointValue(1) = Number of unread TRIP DATA Buffers.

- HMITalk1.PointValue(2) = TRIP TIME OFFSET.

- HMITalk1.PointValue(3) = Phase A Current.

- HMITalk1.PointValue(4) = Phase B Current.

- HMITalk1.PointValue(5) = Phase C Current.

Flags Buffer (same as Read Flags Buffer command):

- HMITalk1.PointValue(6) = Run/Closed Indication.

- HMITalk1.PointValue(7) = Ready/Open Indication.

- HMITalk1.PointValue(8) = Trip Indication.

- HMITalk1.PointValue(9) = If 1, Overload.

- HMITalk1.PointValue(10) = If 1, Run Permit Signal Present.

- HMITalk1.PointValue(11) = If 1, Start Signal Present.

- HMITalk1.PointValue(12) = If 0, Remote Reset Present.

- HMITalk1.PointValue(13) = If 0, Local Reset Present.

- HMITalk1.PointValue(14) = Trip Type:

1 = Overload Trip

2 = Ground Current Trip

3 = Phase Loss Trip

4 = Phase Unbalance Trip

16 = Ground. Current exceeds interrupt capacity.

32 = Control Voltage too low. Unit will open.

48 = Control Voltage too low to pick up.

64 = Control Voltage too high to pick up.

80 = Current to low to close.

112 = External Trip (via remote communications).

- HMITalk1.PointValue(15) = Coil Voltage (units of volts).

- HMITalk1.PointValue(16) = Maximum Coil Current on closing.

- HMITalk1.PointValue(17) = Time equivalent of the delay from the middle

of each half-cycle, to the beginning of

holding pulse.

- HMITalk1.PointValue(18) = The recorded holding current.

Setpoints Buffer (same as Read Setpoints Buffer command):

Dipheater:

- HMITalk1.PointValue(19) = Heater number (0-31).

- HMITalk1.PointValue(20) = Overload type:

0 = Class 10 Overload.

1 = Class 20 Overload.

2 = Class 30 Overload.

3 = No protection.

- HMITalk1.PointValue(21) = If 1, Automatic Reset.

Econfig:

- HMITalk1.PointValue(22) = If 1, Ground Fault enabled.

- HMITalk1.PointValue(23) = If 1, Phase Protection enabled.

- HMITalk1.PointValue(24) = If 1, Thermal Overload enabled.

- HMITalk1.PointValue(25) = If 1, unit is 50 Hz. If 0, unit is 60 Hz.

- HMITalk1.PointValue(26) = If 1, Unit is an Overload. If 0, Unit is

a Contactor/Starter.

- HMITalk1.PointValue(27) = If 1, Ultrasonic holding enabled.

- HMITalk1.PointValue(28) = If 1, Local Reset is disabled.

- HMITalk1.PointValue(29) = If 1, Unit will not reset thermal trip on

power up, even if reset conditions met.

Surever:

- HMITalk1.PointValue(30) = Rom Version of the sure chip.

- HMITalk1.PointValue(31) = Product ID of starter #1 (at address 1).

- HMITalk1.PointValue(32) = Product ID of starter #1 (at address 4).

If the version is full voltage, forward/reverse or fast/slow.

ACM Status:

- HMITalk1.PointValue(33) = If 1, IMPACC Auto mode.

- HMITalk1.PointValue(34) = Reserved

- HMITalk1.PointValue(35) = Reserved

- HMITalk1.PointValue(36) = If 1, Starter #4. If 0, Starter #0.

- HMITalk1.PointValue(37) = If 1, Remote Auto mode.

- HMITalk1.PointValue(38) = If 1, ACM sub-network comm OK. If 0, comm failure.

- HMITalk1.PointValue(39) = Reserved

If the version is reduced voltage.

ACM Status:

- HMITalk1.PointValue(33) = If 1, IMPACC Auto mode.

- HMITalk1.PointValue(34) = If 1, Incomplete Sequence Trip.

- HMITalk1.PointValue(35) = If 1, Start transition in progress.

- HMITalk1.PointValue(36) = If 1, Anti-recycle lockout.

- HMITalk1.PointValue(37) = If 1, Remote Auto mode.

- HMITalk1.PointValue(38) = If 1, ACM sub-network comm OK. If 0, comm failure.

- HMITalk1.PointValue(39) = If 1, Transition time out trip.

ACM (Advantage Control Module) Commands : Read ACM Status

COMMAND DESCRIPTION:

This request gives current ACM status information.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-26

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 12

HMITalk1.DriverP2 = 972 (3CCh)

HMITalk1.DriverP3 = Indicates the version of ACM.

- 0 = Forward/Reverse or Fast/Slow Version.

- 1 = Reduced Voltage Version.

 

RETURNS:

If the version is full voltage, forward/reverse or fast/slow.

ACM Status:

- HMITalk1.PointValue(0) = If 1, Trip.

- HMITalk1.PointValue(1) = If 1, Alarm.

- HMITalk1.PointValue(2) = If 1, Stop.

- HMITalk1.PointValue(3) = If 1, Forward/Fast Run.

- HMITalk1.PointValue(4) = If 1, Reverse/Slow Run.

- HMITalk1.PointValue(5) = If 1, Off Mode.

- HMITalk1.PointValue(6) = If 1, Auto mode.

- HMITalk1.PointValue(7) = If 1, Hand Mode.

- HMITalk1.PointValue(8) = If 1, IMPACC Auto mode.

- HMITalk1.PointValue(9) = Reserved

- HMITalk1.PointValue(10) = Reserved

- HMITalk1.PointValue(11) = If 1, Starter #4. If 0, Starter #1.

- HMITalk1. HMITalk1.PointValue(12) = If 1, Remote Auto mode.

- HMITalk1.PointValue(13) = If 1, ACM sub-network comm OK. If 0, comm failure.

- HMITalk1.PointValue(14) = Reserved

If the version is reduced voltage.

ACM Status:

- HMITalk1.PointValue(0) = If 1, Trip.

- HMITalk1.PointValue(1) = If 1, Alarm.

- HMITalk1.PointValue(2) = If 1, Hand Mode.

- HMITalk1.PointValue(3) = Reserved

- HMITalk1.PointValue(4) = If 1, Run. If 0, Stop.

- HMITalk1.PointValue(5) = If 1, Off Mode.

- HMITalk1.PointValue(6) = If 1, Auto mode.

- HMITalk1.PointValue(7) = Reserved

- HMITalk1.PointValue(8) = If 1, IMPACC Auto mode.

- HMITalk1.PointValue(9) = If 1, Incomplete Sequence Trip.

- HMITalk1.PointValue(10) = If 1, Start transition in progress.

- HMITalk1.PointValue(11) = If 1, Anti-recycle lockout.

- HMITalk1.PointValue(12) = If 1, Remote Auto mode.

- HMITalk1.PointValue(13) = If 1, ACM sub-network comm OK. If 0, comm failure.

- HMITalk1.PointValue(14) = If 1, Transition time out trip.

Definition for reduced voltage:

- HMITalk1.PointValue(15) = If 1, Metering module connected.

If the version is full voltage, forward/reverse or fast/slow.

ACM Status:

- HMITalk1.PointValue(16) = If 1, Three contactor fast/slow.

- HMITalk1.PointValue(17) = If 1, Mandatory Time Stop.

- HMITalk1.PointValue(18) = If 1, Compel Accel Enabled.

- HMITalk1.PointValue(19) = If 1, Compel Decel Enabled.

- HMITalk1.PointValue(20) = Timer Setting in Seconds.

If the version is reduced voltage.

ACM Status:

- HMITalk1.PointValue(16) = Configuration Type.

0 = Primary Resistance - Setup #1.

1 = Part Winding.

2 = Auto Transformer - Setup #1.

3 = Whe-delta Open transition.

4 = Whe-delta Closed transition.

5 = Primary Resistance - Setup #2.

6 = Auto Transformer - Setup #2.

- HMITalk1.PointValue(17) = If 1, Transition on Current.

- HMITalk1.PointValue(18) = If 1, Transition on Time Out.

- HMITalk1.PointValue(19) = Reserved

- HMITalk1.PointValue(20) = Timer Setting in Seconds.

ACM (Advantage Control Module) Commands : Write Slave Action

COMMAND DESCRIPTION:

This command results in the device performing an action as

detailed below. The value sent will be the current value

contained in the HMITalk1.PointValue(0) property.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 12

HMITalk1.DriverP2 = 976 (3D0h)

 

VALUE TO SEND:

0 = Reset trip/unit.

1 = Reset trip buffer.

2 = Start fast forward.

3 = Start reverse.

4 = Stop.

5 = Start slow forward.

 

IQ DP-4000 Commands : Read Current Buffer

COMMAND DESCRIPTION:

This request retrieves Current Buffer information.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-4

HMITalk1.DriverP0 = Unist Address (0-4095)

HMITalk1.DriverP1 = 14

HMITalk1.DriverP2 = 773 (305h)

 

RETURNS:

- HMITalk1.PointValue(0) = Phase A Current.

- HMITalk1.PointValue(1) = Phase B Current.

- HMITalk1.PointValue(2) = Phase C Current.

- HMITalk1.PointValue(3) = Ground Current.

IQ DP-4000 Commands : Read Line-to-Line Voltage Buffer

COMMAND DESCRIPTION:

This request retrieves Line-to-Line Voltage Buffer

information.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 14

HMITalk1.DriverP2 = 774 (306h)

 

RETURNS:

- HMITalk1.PointValue(0) = Voltage A-B.

- HMITalk1.PointValue(1) = Voltage B-C.

- HMITalk1.PointValue(2) = Voltage C-A.

IQ DP-4000 Commands : Read Line-to-Neutral Voltage Buffer

COMMAND DESCRIPTION:

This request retrieves Line-to-Neutral Voltage Buffer

information.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 14

HMITalk1.DriverP2 = 775 (307h)

 

RETURNS:

- HMITalk1.PointValue(0) = Voltage A-N.

- HMITalk1.PointValue(1) = Voltage B-N.

- HMITalk1.PointValue(2) = Voltage C-N.

IQ DP-4000 Commands : Read Power Buffer

COMMAND DESCRIPTION:

This request retrieves Power Buffer information.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 14

HMITalk1.DriverP2 = 776 (308h)

 

RETURNS:

- HMITalk1.PointValue(0) = Frequency (Hz).

- HMITalk1.PointValue(1) = Reactive Power (VARs).

- HMITalk1.PointValue(2) = Power Factor Apparent.

IQ DP-4000 Commands : Read Expanded Power Buffer

COMMAND DESCRIPTION:

This request retrieves Expanded Power Buffer information.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-6

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 14

HMITalk1.DriverP2 = 783 (30F)

HMITalk1.DriverP3 = 6

 

RETURNS:

- HMITalk1.PointValue(0) = Real Power (watts).

- HMITalk1.PointValue(1) = Reactive Power (VARs).

- HMITalk1.PointValue(2) = Volt-Amps 3 phase (VA).

- HMITalk1.PointValue(3) = Power Factor Displacement.

- HMITalk1.PointValue(4) = Power Factor Apparent.

- HMITalk1.PointValue(5) = Frequency (Hz).

IQ DP-4000 Commands : Read THD Buffer

COMMAND DESCRIPTION:

This request retrieves THD Buffer information.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-9

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 14

HMITalk1.DriverP2 = 783 (30F)

HMITalk1.DriverP3 = 9

 

RETURNS:

- HMITalk1.PointValue(0) = % THD - Phase A Current (%).

- HMITalk1.PointValue(1) = % THD - Phase B Current (%).

- HMITalk1.PointValue(2) = % THD - Phase C Current (%).

- HMITalk1.PointValue(3) = % THD - Voltage A-B (%).

- HMITalk1.PointValue(4) = % THD - Voltage B-C (%).

- HMITalk1.PointValue(5) = % THD - Voltage C-A (%).

- HMITalk1.PointValue(6) = % THD - Voltage A-N (%).

- HMITalk1.PointValue(7) = % THD - Voltage B-N (%).

- HMITalk1.PointValue(8) = % THD - Voltage C-N (%).

IQ DP-4000 Commands : Read Trip Data Buffer

COMMAND DESCRIPTION:

This request retrieves Trip Data Buffer information.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-27

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 14

HMITalk1.DriverP2 = 971 (3CBh)

 

RETURNS:

- HMITalk1.PointValue(0) = Phase A Current.

- HMITalk1.PointValue(1) = Phase B Current.

- HMITalk1.PointValue(2) = Phase C Current.

- HMITalk1.PointValue(3) = Ground Current.

- HMITalk1.PointValue(4) = Voltage A-B.

- HMITalk1.PointValue(5) = Voltage B-C.

- HMITalk1.PointValue(6) = Voltage C-A.

- HMITalk1.PointValue(7) = Voltage A-N.

- HMITalk1.PointValue(8) = Voltage B-N.

- HMITalk1.PointValue(9) = Voltage C-N.

- HMITalk1.PointValue(10) = Real Power (watts).

- HMITalk1.PointValue(11) = Power Demand (watts).

- HMITalk1.PointValue(12) = Energy (wh).

- HMITalk1.PointValue(13) = Frequency (Hz).

- HMITalk1.PointValue(14) = Reactive Power (VARs).

- HMITalk1.PointValue(15) = Power Factor Apparent.

- HMITalk1.PointValue(16) = % THD - Phase A Current (%).

- HMITalk1.PointValue(17) = % THD - Phase B Current (%).

- HMITalk1.PointValue(18) = % THD - Phase C Current (%).

- HMITalk1.PointValue(19) = % THD - Voltage A-B (%).

- HMITalk1.PointValue(20) = % THD - Voltage B-C (%).

- HMITalk1.PointValue(21) = % THD - Voltage C-A (%).

- HMITalk1.PointValue(22) = % THD - Voltage A-N (%).

- HMITalk1.PointValue(23) = % THD - Voltage B-N (%).

- HMITalk1.PointValue(24) = % THD - Voltage C-N (%).

- HMITalk1.PointValue(25) = Volt-Amps 3 phase (VA).

- HMITalk1.PointValue(26) = Power Factor Displacement.

IQ DP-4000 Commands : Read Flags Buffer

COMMAND DESCRIPTION:

This command retrieves extended information about the current

operating conditions.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-25

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 14

HMITalk1.DriverP2 = 968 (3C8h)

 

RETURNS:

- HMITalk1.PointValue(0) = Relay 1 Activated

- HMITalk1.PointValue(1) = Relay 1 IMPACC External Trip

- HMITalk1.PointValue(2) = Relay 1 Overvoltage Trip

- HMITalk1.PointValue(3) = Relay 1 Undervoltage Trip

- HMITalk1.PointValue(4) = Relay 1 Voltage Phase Loss Trip

- HMITalk1.PointValue(5) = Relay 1 Voltage Phase Unbalance Trip

- HMITalk1.PointValue(6) = Relay 1 Voltage Phase Reversal Trip

- HMITalk1.PointValue(7) = Relay 1 Current Phase Loss Trip

- HMITalk1.PointValue(8) = Relay 2 Activated

- HMITalk1.PointValue(9) = Relay 2 IMPACC External Trip

- HMITalk1.PointValue(10) = Relay 2 Overvoltage Trip

- HMITalk1.PointValue(11) = Relay 2 Undervoltage Trip

- HMITalk1.PointValue(12) = Relay 2 Voltage Phase Loss Trip

- HMITalk1.PointValue(13) = Relay 2 Voltage Phase Unbalance Trip

- HMITalk1.PointValue(14) = Relay 2 Voltage Phase Reversal Trip

- HMITalk1.PointValue(15) = Relay 2 Current Phase Loss Trip

- HMITalk1.PointValue(16) = TRIP RELAY STATE

- HMITalk1.PointValue(17) = ALARM RELAY STATE

- HMITalk1.PointValue(18) = PULSE INITIATOR RELAY STATE

- HMITalk1.PointValue(19) = RAM Failure

- HMITalk1.PointValue(20) = ROM Failure

- HMITalk1.PointValue(21) = A/D Offset Error

- HMITalk1.PointValue(22) = EEPROM Failure

- HMITalk1.PointValue(23) = Deadman Timer Error

- HMITalk1.PointValue(24) = Factory Calibration Mode

IQ DP-4000 Commands : Read System Energy Buffer

COMMAND DESCRIPTION:

This request retrieves System Energy Buffer information.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-7

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 14

HMITalk1.DriverP2 = 783 (30F)

HMITalk1.DriverP3 = 8

 

RETURNS:

- HMITalk1.PointValue(0) = Energy Forward

- HMITalk1.PointValue(1) = Energy Reverse

- HMITalk1.PointValue(2) = Energy Net

- HMITalk1.PointValue(3) = VAR-h Forward

- HMITalk1.PointValue(4) = VAR-h Reverse

- HMITalk1.PointValue(5) = VAR-h Net

- HMITalk1.PointValue(6) = VAR-h

IQ DP-4000 Commands : Read Fast Status

COMMAND DESCRIPTION:

This command retrieves information about the current

device status.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-4095)

HMITalk1.DriverP1 = 14

HMITalk1.DriverP2 = 768 (300h)

 

RETURNS:

- HMITalk1.PointValue(0) = Status.

0 = Inactive

1 = Normal

2 = Tripped (Alarm 1)

3 = Alarmed (Alarm 2)

Returned Errors List

[1005] DRIVER (Internal): Invalid driver stage

[1300] PROTOCOL (Timeout): No answer

[1400] PROTOCOL (Format): Acknowledge not received

[1433] PROTOCOL (Format): Validation error in device response

[2174] CONFIG (NumValues): Too many values (max=%u)

[3007] CONFIG (P0): Invalid device address

[3500] CONFIG (P1): Analog inputs are not supported for this device

[3501] CONFIG (P1): Analog outputs are not supported for this device

[3503] CONFIG (P1): Digital inputs are not supported for this device

[3504] CONFIG (P1): Digital outputs are not supported for this device

[3551] CONFIG (P1): Invalid device code

[4030] CONFIG (P2): Invalid command

[4570] CONFIG (P3): Invalid sub-command

About the XWIMPACC.tlk driver

This driver requires that you have TAS-HMITalk 8.04 installed.

Driver Source Code Last Update: 03/08/2004 14:07:58

Driver Reference Last Update: 10/30/2008 17:52:27

© 1990-2008, CPKSoft Engineering. All rights reserved.

http://www.cpksoft.com - support@cpksoft.com

http://www.cpksoft.com.ar - soporte@cpksoft.com.ar>