XMODBTCP.tlk Driver Reference
Modbus TCP Protocol Driver
This driver requires that you have TAS-HMITalk 8.04 installed.
XMODBTCP driver supports the Modbus TCP protocol according to the
Modbus Messaging TCP/IP Implementation Guide from Modbus.org
Rev 1.0, 8 May 02
This driver implements Modbus commands 1, 2, 3, 4, 5, 6, 15 and 16.
It also implements some special commands that are not part of the original
Modbus specification that bring support for special data formats
used by certain devices.
This driver expects that you connect to your device through its tcp/ip
port. The device should behave as a slave in your RS-232/485 network.
TCP/IP communication must be set in TCP mode using port 502.
TESTING WITH MODSIM:
If you are using MODSIM Modbus slave emulation software to test this driver,
then use command 'Read Input Registers as Unsigned 16-bit Integers' (P1=4)
to read 'Inputs Register' from ModSim. Also, set the register address to 0 (P2=0)
if you want to read Input Register 1 from ModSim.
DAQ Modules
Flow Computers
Loop Controllers
Power Meters
Remote Terminal Units
Programmable Logic Controllers
ABB Totalflow µFLO 6213
ABB Totalflow XRC 6490 RTU
ABB Totalflow XRC 6790 RTU
ABB Totalflow XRC 6890 RTU
ABB Totalflow 8000/8100 Btu/CV Transmitter
ABB Totalflow XFC 6410 EFM
ABB Totalflow XFC 6413 EFM
ABB Totalflow XFC 6713 EFM
ABB S4C+ Robot Controller Controller
ACKSYS Communications & Systems COMETH Network Gateway
ACKSYS Communications & Systems WL-ABOARD/N Network Gateway
ACKSYS Communications & Systems WL-ABOARD/S Network Gateway
ACKSYS Communications & Systems WL-COMETH Network Gateway
ACROMAG 901MB-0900 Discrete Input Module
ACROMAG 902MB-0900 Discrete Output Module
ACROMAG 903MB-0900 Discrete I/O Modules
ACROMAG 904MB Discrete Input Module
ACROMAG 905MB Discrete Output Module
ACROMAG 906MB Discrete I/O Module
ACROMAG 913MB Analog Input Module
ACROMAG 914MB Analog Input Module
ACROMAG 917MB Analog Output Module
ACROMAG 918MB Analog Output Module
ACROMAG 924MB Analog Input Module
ACROMAG 932MB Analog Input Module
ACROMAG 934MB Analog Input Module
ACROMAG 942MB Frequency/Pulse Counter Module
ACROMAG BusWorks 900EN Ethernet I/O Modules
ACTL eWON2001 Network Gateway
ADFWEB.COM SRL Datalogger Modbus RTU
ADVANTAGE ENGINEERING Sentra 300 Controller
ADVANTECH ADAM-5510EKW/TP Controller
ALERTON FLG-Modbus BACtalk Gateway
AMASS Data Technologies Inc Analog to Digital Conversion Module
AMASS Data Technologies Inc Embedded Control Digital I/O Module
AMASS Data Technologies Inc PSE/RTU Shaft Encoder Sensor
ANTX Inc Elite Gas Controller
APEX Automation Technologies GmbH PDnetIP-Controller
AQUASENSORS LLC
AQUASENSORS LLC DataStick System Sensor
ARCOM HtMux Network Gateway
ARCOM HtNode Network Gateway
AREVA T&D BiTRONICS M871
AUMA Riester GmbH & Co KG AUMATIC AC/DC Drive Control
BACHMANN ELECTRONIC M1 (M200 series) Controller
BARIX AG Barix IO12 I/O Module
BARIX AG Barix R6 I/O Interface
BARIX AG Barix X8 I/O Interface
BARNETT ENGINEERIING Ltd ProTalk SPX Monitoring Hardware
BECKHOFF Modbus Bus Terminal Controller BC7300 Controller
BELUK Capacitor-Protecting Relay KSR Sensor
BELUK EMM Power Analyzer Monitoring Hardware
BELUK Power Factor Control Relay BLR-CM
BENTEK SYSTEMS SMX-900 Modem
BIHL WIEDEMANN AS-i/Modbus Gateway
COMET SYSTEM SRO Ethernet Sensor
CONTROL MYCROSYSTEMS SCADAPack Controller
CONTROL TECHNIQUES Commander SE AC Vector Drive Control
CONTROL TECHNIQUES Commander SK AC/DC Drive Control
CONTROL TECHNIQUES Commander SX AC/DC Drive Control
CONTROL TECHNIQUES Epsilon Digital Servo AC/DC Drive Control
CONTROL TECHNIQUES MDS Modular Servo AC/DC Drive ControlControl Techniques Inc EN Servo Drive AC/DC Drive Control
CONTROL TECHNIQUES Unidrive SP AC/DC Drive Control
CONTROL TECHNIQUES. Mentor II DC AC/DC Drive Control
CONTROL TECHNIQUES. Quantum III DC AC/DC Drive Control
DAE Instrument SIO270 I/O Module
DANIEL Measurement and Control Model 3804 Liquid Ultrasonic Flow Meter Sensor
DATAFORTH Corporation isoLynx SLX200 Data Acquisition System
DATANAB LLC BarioNet Controller
DATAQ Instruments Inc DI-900MB Modules
DELTA COMPUTER SYSTEMS RMC70 Series One- and Two-Axis Mothion Controllers
DGH CORPORATION D1000M single-channel data acquisition modules
DGH CORPORATION D5000M Four Analog Input Modules
DGH CORPORATION DIN-100 Series I/O
ENDRESS HAUSER Flowtec AG Promag 53 Electromagnetic Flowmeter
ENDRESS HAUSER Flowtec AG Promass 83 Coriolis Flowmeter
EPRODUCTION SOLUTIONS Axess 2.4 GHz Gateway Sensor Receiver
EQUUSTEK SOLUTIONS DL2000-CMX Network Gateway
EQUUSTEK SOLUTIONS DL3500 Network Gateway
EQUUSTEK SOLUTIONS DL4000-DMX DF1 Network Gateway
EQUUSTEK SOLUTIONS DL4000-MMX Network Gateway
EQUUSTEK SOLUTIONS DL4500-MEDH+ Network Gateway
EQUUSTEK SOLUTIONS DL4500-MEDH-485 Network Gateway
EUROTHERM 2500 Intelligent Data Acqusition and Precision Multi-Loop PID Control
EXEMYS LLC MODBUS Serial Server Network Gateway
FLOWSERVE CORPORATION Valtek Logix 2000 Digital Positioner Controller
FLUENTA FGM
FRABA POSITAL Absolute Rotary Encoder Series OCD-EM
GALIL Motion Control IOC-7007 I/O Controller
GSE Scale Systems Indicator 460 Series
GSE Scale Systems Indicator 560 Series
GSE Scale Systems Indicator 660 Series
HACH COMPANY MOD I/O Modbus Interface
HACH COMPANY sc1000 Multi-parameter Universal Controller
HONEYWELL INTERNATIONAL Herculine Smart Actuators
ICP DAS USA M-7000 Series Controllers
INDUSTRIAL SCIENTIFIC CORPORATION 4800 Controller
INSTROMET
PRECISION DIGITAL CORPORATION Model PD865 Snooper RTU
PRECISION DIGITAL CORPORATION PD500 Series Controller
PROSOFT TECHNOLOGY MV156-MCM I/O Interface
PROSOFT TECHNOLOGY MVI56-MCMR Network Gateway
PROSOFT TECHNOLOGY MVI56-MNET Network Gateway
ROXAR RFM
SCHNEIDER ELECTRIC Advantys OTB Network Interface Module OTB 1E0 DM9LP
SCHNEIDER ELECTRIC Advantys STB Network Interface Module
SCHNEIDER ELECTRIC Altistart 48 Soft Starters Controller
SCHNEIDER ELECTRIC Altivar Speed Drives ATV 58
SCHNEIDER ELECTRIC Altivar Speed Drives ATV31
SCHNEIDER ELECTRIC Altivar Speed Drives ATV38
SCHNEIDER ELECTRIC Altivar Speed Drives ATV68
SCHNEIDER ELECTRIC Altivar Speed Drives ATV71H
SCHNEIDER ELECTRIC ASi Communications Gateways
SCHNEIDER ELECTRIC Atrium PL7 Processors
SCHNEIDER ELECTRIC Atrium Unity Processors TSX PCI 57
SCHNEIDER ELECTRIC Carriere Digital 600 Retrofit Trip Relay
SCHNEIDER ELECTRIC ConneXium Communications Gateways
SCHNEIDER ELECTRIC DeviceNet Modbus Communication Gateways
SCHNEIDER ELECTRIC Easergy Substation Control Unit Controller
SCHNEIDER ELECTRIC Fipio Modbus Communications Gateways
SCHNEIDER ELECTRIC Inductel Inductive Identification System XGK-S1.0421
SCHNEIDER ELECTRIC Inductel Inductive Identification System XGKS1715503
SCHNEIDER ELECTRIC LT6 Motor Control
SCHNEIDER ELECTRIC MASTERPACT Circuit Breaker
SCHNEIDER ELECTRIC Micro Communications Modules TSX ETZ 410
SCHNEIDER ELECTRIC Micro Communications Modules TSX ETZ 510
SCHNEIDER ELECTRIC Micro PL7 Processors
SCHNEIDER ELECTRIC Momentum M1 PLC Processor Controller
SCHNEIDER ELECTRIC Momentum M1E PLC Processor Controller
SCHNEIDER ELECTRIC PM500 Power Meter
SCHNEIDER ELECTRIC PM800 Power Meter
SCHNEIDER ELECTRIC PM9 Power Meter
SCHNEIDER ELECTRIC Power Logic Circuit Monitor CM3000
SCHNEIDER ELECTRIC Power Logic Circuit Monitor CM4000
SCHNEIDER ELECTRIC Premium Communications Modules TSX ETY 410
SCHNEIDER ELECTRIC Premium Communications Modules TSX ETY 510
SCHNEIDER ELECTRIC Premium family CPU module P571634
SCHNEIDER ELECTRIC Premium family CPU module P573634
SCHNEIDER ELECTRIC Premium family CPU module P574634
SCHNEIDER ELECTRIC Premium family CPU module P575634
SCHNEIDER ELECTRIC Premium PL7 TSX 57
SCHNEIDER ELECTRIC Premium Unity Processors TSX P57
SCHNEIDER ELECTRIC Preventa safety controllers Controller
SCHNEIDER ELECTRIC Profibus DP Modbus Communications Gateways
SCHNEIDER ELECTRIC Quantum Communications Modules 140 NOE 771 0
SCHNEIDER ELECTRIC Quantum Communications Modules 140 NOE 771 1X
SCHNEIDER ELECTRIC Quantum Concept Processors
SCHNEIDER ELECTRIC Quantum family CPU module CPU65160
SCHNEIDER ELECTRIC Quantum Unity Processors
SCHNEIDER ELECTRIC SEPAM 20 Protection Relays
SCHNEIDER ELECTRIC SEPAM 2000 Protection Relays
SCHNEIDER ELECTRIC SEPAM 40 Protection Relays
SCHNEIDER ELECTRIC SEPAM 80 Protection Relays
SCHNEIDER ELECTRIC Tesys U Motor Control and Protection Units Controller
Schneider Electric TSX 37 Controllers
SCHNEIDER ELECTRIC Twido Programmable Controllers
SCHNEIDER ELECTRIC Varlogic Power Factor Controller
SCHNEIDER ELECTRIC Vigilohm Insulation Monitor
SCHNEIDER ELECTRIC Vision System
SCHNEIDER ELECTRIC Zelio Smart Relays
SEALEVEL SYSTEMS SeaI/O-410 I/O Module
SEALEVEL SYSTEMS SeaI/O-420 I/O Module
SEALEVEL SYSTEMS SeaI/O-430 I/O Module
SEALEVEL SYSTEMS SeaI/O-440 I/O Module
SEALEVEL SYSTEMS SeaI/O-450 I/O Module
SEALEVEL SYSTEMS SeaI/O-462 I/O Module
SEALEVEL SYSTEMS SeaI/O-463 I/O Module
SEEKIRK A1700 Annunciator
STANLEY ASSEMBLY TECHNOLOGIES QPM Sigma Controller Q3000
WEED INSTRUMENT (EoTec) Modbus Remote I/O Electrical Interface
Read Holding Registers as Unsigned 16-bit Integers
Read Holding Registers as Signed 16-bit Integers
Read Holding Registers as Unsigned 32-bit Integers
Read Holding Registers as Signed 32-bit Integers
Read Holding Registers as Unsigned 32-bit Integers (words reversed)
Read Holding Registers as Signed 32-bit Integers (words reversed)
Read Holding Registers as IEEE Floats
Read Holding Registers as IEEE Floats (bytes reversed)
Read Holding Registers as IEEE Floats (words reversed)
Read Input Registers as Unsigned 16-bit Integers
Read Input Registers as Signed 16-bit Integers
Read Input Registers as Unsigned 32-bit Integers
Read Input Registers as Signed 32-bit Integers
Read Input Registers as Unsigned 32-bit Integers (words reversed)
Read Input Registers as Signed 32-bit Integers (words reversed)
Read Input Registers as IEEE Floats
Read Input Registers as IEEE Floats (bytes reversed)
Read Input Registers as IEEE Floats (words reversed)
Preset Single Register as Unsigned 16-bit Integer
Preset Multiple Registers as Unsigned 16-bit Integers
Preset Multiple Registers as Unsigned 32-bit Integers
Preset Multiple Registers as Signed 32-bit Integers
Preset Multiple Registers as Unsigned 32-bit Integers (words reversed)
Preset Multiple Registers as Signed 32-bit Integers (words reversed)
Preset Multiple Registers as IEEE Floats
Preset Multiple Registers as IEEE Floats (bytes reversed)
Preset Multiple Registers as IEEE Floats (words reversed)
COMMAND DESCRIPTION:
Obtains current status (ON/OFF) in a group of logic coils.
This command implements Modbus function 1.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Digital Input
HMITalk1.DriverNumPoints = 1-1000
HMITalk1.DriverP0 = Station number (0-255).
HMITalk1.DriverP1 = 1
HMITalk1.DriverP2 = Indicates the starting coil address.
RETURNS:
- HMITalk1.PointValue(0) = First coil status (0=OFF, 1=ON)
- HMITalk1.PointValue(1) = Second coil status (0=OFF, 1=ON)
...
- HMITalk1.PointValue(n-1) = Last coil status (0=OFF, 1=ON)
COMMAND DESCRIPTION:
Obtains current status (ON/OFF) in a group of discrete inputs.
This command implements Modbus function 2.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Digital Input
HMITalk1.DriverNumPoints = 1-1000
HMITalk1.DriverP0 = Station number (0-255).
HMITalk1.DriverP1 = 2
HMITalk1.DriverP2 = Indicates the starting input address.
RETURNS:
- HMITalk1.PointValue(0) = First input status (0=OFF, 1=ON)
- HMITalk1.PointValue(1) = Second input status (0=OFF, 1=ON)
...
- HMITalk1.PointValue(n-1) = Last input status (0=OFF, 1=ON)
COMMAND DESCRIPTION:
Obtains the current values in one or more holding registers
as unsigned 16-bit integers from 0 to 65535.
This command implements Modbus function 3.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-125
HMITalk1.DriverP0 = Station number (0-255).
HMITalk1.DriverP1 = 3
HMITalk1.DriverP2 = Indicates the starting register address.
RETURNS:
- HMITalk1.PointValue(0) = First register value (0-65535)
- HMITalk1.PointValue(1) = Second register value (0-65535)
...
- HMITalk1.PointValue(n-1) = Last register value (0-65535)
COMMAND DESCRIPTION:
Obtains the current values in one or more holding registers
as signed 16-bit integers from -32768 to 32767.
This command implements Modbus function 3.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-125
HMITalk1.DriverP0 = Station number (0-255).
HMITalk1.DriverP1 = 74
HMITalk1.DriverP2 = Indicates the starting register address.
RETURNS:
- HMITalk1.PointValue(0) = First register value (-32768 to 32767)
- HMITalk1.PointValue(1) = Second register value (-32768 to 32767)
...
- HMITalk1.PointValue(n-1) = Last register value (-32768 to 32767)
COMMAND DESCRIPTION:
Obtains the current values in one or more holding registers
as unsigned 32-bit integer numbers.
This command uses Modbus function 3.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station number (0-255).
HMITalk1.DriverP1 = 76
HMITalk1.DriverP2 = Indicates the starting register address.
RETURNS:
- HMITalk1.PointValue(0) = First register value
- HMITalk1.PointValue(1) = Second register value
...
- HMITalk1.PointValue(n-1) = Last register value
COMMAND DESCRIPTION:
Obtains the current values in one or more holding registers
as signed 32-bit integer numbers.
This command uses Modbus function 3.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station number (0-255).
HMITalk1.DriverP1 = 75
HMITalk1.DriverP2 = Indicates the starting register address.
RETURNS:
- HMITalk1.PointValue(0) = First register value
- HMITalk1.PointValue(1) = Second register value
...
- HMITalk1.PointValue(n-1) = Last register value
COMMAND DESCRIPTION:
Obtains current values in one or more holding registers
as unsigned 32-bit integer numbers with words in reverse
order.
This command uses Modbus function 3.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station number (0-255).
HMITalk1.DriverP1 = 86
HMITalk1.DriverP2 = Indicates the starting register address.
RETURNS:
- HMITalk1.PointValue(0) = First register value
- HMITalk1.PointValue(1) = Second register value
...
- HMITalk1.PointValue(n-1) = Last register value
COMMAND DESCRIPTION:
Obtains current values in one or more holding registers
as signed 32-bit integer numbers with words in reverse
order.
This command uses Modbus function 3.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station number (0-255).
HMITalk1.DriverP1 = 85
HMITalk1.DriverP2 = Indicates the starting register address.
RETURNS:
- HMITalk1.PointValue(0) = First register value
- HMITalk1.PointValue(1) = Second register value
...
- HMITalk1.PointValue(n-1) = Last register value
COMMAND DESCRIPTION:
Obtains the current values in one or more holding registers
as 32-bit IEEE floating-point values.
This command uses Modbus function 3.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station number (0-255).
HMITalk1.DriverP1 = 66
HMITalk1.DriverP2 = Indicates the starting register address.
RETURNS:
- HMITalk1.PointValue(0) = First register value
- HMITalk1.PointValue(1) = Second register value
...
- HMITalk1.PointValue(n-1) = Last register value
COMMAND DESCRIPTION:
Obtains the current values in one or more holding registers
as 32-bit IEEE floating-point values assuming that bytes are
received in reverse order.
This command uses Modbus function 3.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station number (0-255).
HMITalk1.DriverP1 = 68
HMITalk1.DriverP2 = Indicates the starting register address.
RETURNS:
- HMITalk1.PointValue(0) = First register value
- HMITalk1.PointValue(1) = Second register value
...
- HMITalk1.PointValue(n-1) = Last register value
COMMAND DESCRIPTION:
Obtains current values in one or more holding registers
as 32-bit IEEE floating point values assuming that the words
order is received in reversed order.
This command uses Modbus function 3.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station number (0-255).
HMITalk1.DriverP1 = 80
HMITalk1.DriverP2 = Indicates the starting memory address.
RETURNS:
- HMITalk1.PointValue(0) = First register value
- HMITalk1.PointValue(1) = Second register value
...
- HMITalk1.PointValue(n-1) = Last register value
NOTE:
This command was added to support the floating-point format
used by the TSX-3722 PLC from Telemecanique.
COMMAND DESCRIPTION:
Obtains the current values in one or more input registers
as unsigned 16-bit integers from 0 to 65535.
This command implements Modbus function 4.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-125
HMITalk1.DriverP0 = Station number (0-255).
HMITalk1.DriverP1 = 4
HMITalk1.DriverP2 = Indicates the starting register address.
RETURNS:
- HMITalk1.PointValue(0) = First register value (0-65535)
- HMITalk1.PointValue(1) = Second register value (0-65535)
...
- HMITalk1.PointValue(n-1) = Last register value (0-65535)
COMMAND DESCRIPTION:
Obtains the current values in one or more input registers
as signed 16-bit integers from -32768 to 32767.
This command implements Modbus function 4.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-125
HMITalk1.DriverP0 = Station number (0-255).
HMITalk1.DriverP1 = 179
HMITalk1.DriverP2 = Indicates the starting register address.
RETURNS:
- HMITalk1.PointValue(0) = First register value (-32768 to 32767)
- HMITalk1.PointValue(1) = Second register value (-32768 to 32767)
...
- HMITalk1.PointValue(n-1) = Last register value (-32768 to 32767)
COMMAND DESCRIPTION:
Obtains the current values in one or more input registers
as unsigned 32-bit integer numbers.
This command uses Modbus function 4.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station number (0-255).
HMITalk1.DriverP1 = 176
HMITalk1.DriverP2 = Indicates the starting register address.
RETURNS:
- HMITalk1.PointValue(0) = First register value
- HMITalk1.PointValue(1) = Second register value
...
- HMITalk1.PointValue(n-1) = Last register value
COMMAND DESCRIPTION:
Obtains the current values in one or more input registers
as signed 32-bit integer numbers.
This command uses Modbus function 4.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station number (0-255).
HMITalk1.DriverP1 = 175
HMITalk1.DriverP2 = Indicates the starting register address.
RETURNS:
- HMITalk1.PointValue(0) = First register value
- HMITalk1.PointValue(1) = Second register value
...
- HMITalk1.PointValue(n-1) = Last register value
COMMAND DESCRIPTION:
Obtains current values in one or more input registers
as unsigned 32-bit integer numbers with words in reverse
order.
This command uses Modbus function 4.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station number (0-255).
HMITalk1.DriverP1 = 186
HMITalk1.DriverP2 = Indicates the starting register address.
RETURNS:
- HMITalk1.PointValue(0) = First register value
- HMITalk1.PointValue(1) = Second register value
...
- HMITalk1.PointValue(n-1) = Last register value
COMMAND DESCRIPTION:
Obtains current values in one or more input registers
as signed 32-bit integer numbers with words in reverse
order.
This command uses Modbus function 4.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station number (0-255).
HMITalk1.DriverP1 = 185
HMITalk1.DriverP2 = Indicates the starting register address.
RETURNS:
- HMITalk1.PointValue(0) = First register value
- HMITalk1.PointValue(1) = Second register value
...
- HMITalk1.PointValue(n-1) = Last register value
COMMAND DESCRIPTION:
Obtains the current values in one or more input registers
as 32-bit IEEE floating-point values.
This command uses Modbus function 4.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station number (0-255).
HMITalk1.DriverP1 = 166
HMITalk1.DriverP2 = Indicates the starting register address.
RETURNS:
- HMITalk1.PointValue(0) = First register value
- HMITalk1.PointValue(1) = Second register value
...
- HMITalk1.PointValue(n-1) = Last register value
COMMAND DESCRIPTION:
Obtains the current values in one or more input registers
as 32-bit IEEE floating-point values assuming that bytes are
received in reverse order.
This command uses Modbus function 4.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station number (0-255).
HMITalk1.DriverP1 = 168
HMITalk1.DriverP2 = Indicates the starting register address.
RETURNS:
- HMITalk1.PointValue(0) = First register value
- HMITalk1.PointValue(1) = Second register value
...
- HMITalk1.PointValue(n-1) = Last register value
COMMAND DESCRIPTION:
Obtains current values in one or more input registers
as 32-bit IEEE floating point values assuming that the words
order is received in reversed order.
This command uses Modbus function 4.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station number (0-255).
HMITalk1.DriverP1 = 180
HMITalk1.DriverP2 = Indicates the starting memory address.
RETURNS:
- HMITalk1.PointValue(0) = First register value
- HMITalk1.PointValue(1) = Second register value
...
- HMITalk1.PointValue(n-1) = Last register value
COMMAND DESCRIPTION:
Forces a single logic coil to a state ON or OFF.
This command implements Modbus function 5.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Digital Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Station Number (0-255).
If the station number is 0, the command is sent as a broadcast
message and no response is expected.
HMITalk1.DriverP1 = 5
HMITalk1.DriverP2 = Indicates the coil address.
WHERE:
- HMITalk1.PointValue(0) = New coil status (0=OFF, 1=ON)
COMMAND DESCRIPTION:
Forces a series of consecutive logic coils to selected ON or OFF states.
This command implements Modbus function 15.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Digital Output
HMITalk1.DriverNumPoints = 1-1000 (It is convenient for the groups to be a multiple of 8 elements)
HMITalk1.DriverP0 = Station Number (0-255).
If the station number is 0, the command is sent as a broadcast
message and no response is expected.
HMITalk1.DriverP1 = 15
HMITalk1.DriverP2 = Indicates the starting coil address.
WHERE:
- HMITalk1.PointValue(0) = New status for first coil (0=OFF, 1=ON)
- HMITalk1.PointValue(1) = New status for second coil (0=OFF, 1=ON)
...
- HMITalk1.PointValue(n-1) = New status for last coil (0=OFF, 1=ON)
COMMAND DESCRIPTION:
Places a specified value into a holding register as
an unsigned 16-bit integer value from 0 to 65535.
This command implements Modbus function 6.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Station Number (0-255).
If the station number is 0, the command is sent as a broadcast
message and no response is expected.
HMITalk1.DriverP1 = 6
HMITalk1.DriverP2 = Indicates the register address.
WHERE:
- HMITalk1.PointValue(0) = New register value (0-65535)
COMMAND DESCRIPTION:
Places specified values into a series of consecutive
holding registers, as unsigned 16-bit integer values from 0 to 65535.
This command implements Modbus function 16.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1-125
HMITalk1.DriverP0 = Station Number (0-255).
If the station number is 0, the command is sent as a broadcast
message and no response is expected.
HMITalk1.DriverP1 = 16
HMITalk1.DriverP2 = Indicates the starting register address.
WHERE:
- HMITalk1.PointValue(0) = New value for first register (0-65535)
- HMITalk1.PointValue(1) = New value for second register (0-65535)
...
- HMITalk1.PointValue(n-1) = New value for last register (0-65535)
COMMAND DESCRIPTION:
Places specified values into a series of consecutive
holding registers, as unsigned 32-bit integer values.
This command uses Modbus function 16.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station Number (0-255).
If the station number is 0, the command is sent as a broadcast
message and no response is expected.
HMITalk1.DriverP1 = 78
HMITalk1.DriverP2 = Indicates the starting register address.
WHERE:
- HMITalk1.PointValue(0) = New value for first register
- HMITalk1.PointValue(1) = New value for second register
...
- HMITalk1.PointValue(n-1) = New value for last register
COMMAND DESCRIPTION:
Places specified values into a series of consecutive
holding registers, as signed 32-bit integer values.
This command uses Modbus function 16.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station Number (0-255).
If the station number is 0, the command is sent as a broadcast
message and no response is expected.
HMITalk1.DriverP1 = 77
HMITalk1.DriverP2 = Indicates the starting register address.
WHERE:
- HMITalk1.PointValue(0) = New value for first register
- HMITalk1.PointValue(1) = New value for second register
...
- HMITalk1.PointValue(n-1) = New value for last register
COMMAND DESCRIPTION:
Places specified values into a series of consecutive
holding registers, as unsigned 32-bit integer values
with words in reverse order.
This command uses Modbus function 16.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station Number (0-255).
If the station number is 0, the command is sent as a broadcast
message and no response is expected.
HMITalk1.DriverP1 = 88
HMITalk1.DriverP2 = Indicates the starting register address.
WHERE:
- HMITalk1.PointValue(0) = New value for first register
- HMITalk1.PointValue(1) = New value for second register
...
- HMITalk1.PointValue(n-1) = New value for last register
COMMAND DESCRIPTION:
Places specified values into a series of consecutive
holding registers, as signed 32-bit integer values
with words in reverse order.
This command uses Modbus function 16.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station Number (0-255).
If the station number is 0, the command is sent as a broadcast
message and no response is expected.
HMITalk1.DriverP1 = 87
HMITalk1.DriverP2 = Indicates the starting register address.
WHERE:
- HMITalk1.PointValue(0) = New value for first register
- HMITalk1.PointValue(1) = New value for second register
...
- HMITalk1.PointValue(n-1) = New value for last register
COMMAND DESCRIPTION:
Places specified values into a series of consecutive
holding registers as 32-bit IEEE floating point values.
This command uses Modbus function 16.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station Number (0-255).
If the station number is 0, the command is sent as a broadcast
message and no response is expected.
HMITalk1.DriverP1 = 70
HMITalk1.DriverP2 = Indicates the starting register address.
WHERE:
- HMITalk1.PointValue(0) = New value for first register
- HMITalk1.PointValue(1) = New value for second register
...
- HMITalk1.PointValue(n-1) = New value for last register
COMMAND DESCRIPTION:
Places specified values into a series of consecutive
holding registers as 32-bit IEEE floating point values
where the bytes order is reversed.
This command uses Modbus function 16.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station Number (0-255).
If the station number is 0, the command is sent as a broadcast
message and no response is expected.
HMITalk1.DriverP1 = 72
HMITalk1.DriverP2 = Indicates the starting register address.
WHERE:
- HMITalk1.PointValue(0) = New value for first register
- HMITalk1.PointValue(1) = New value for second register
...
- HMITalk1.PointValue(n-1) = New value for last register
COMMAND DESCRIPTION:
Places specified values into a series of consecutive
holding registers as 32-bit IEEE floating point values
where the required words order must be reversed.
This command uses Modbus function 16.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1-62
HMITalk1.DriverP0 = Station Number (0-255).
If the station number is 0, the command is sent as a broadcast
message and no response is expected.
HMITalk1.DriverP1 = 81
HMITalk1.DriverP2 = Indicates the starting register address.
WHERE:
- HMITalk1.PointValue(0) = New value for first register
- HMITalk1.PointValue(1) = New value for second register
...
- HMITalk1.PointValue(n-1) = New value for last register
NOTE:
This command was added to support the format
used by the TSX-3722 PLC from Telemecanique.
[1005] DRIVER (Internal): Invalid driver stage
[1300] PROTOCOL (Timeout): No answer
[1421] PROTOCOL (Format): Negative acknowledge received from device
[1433] PROTOCOL (Format): Validation error in device response
[1435] PROTOCOL (Format): Invalid transaction identifier received
[2147] CONFIG (NumValues): Only one value can be read or written
[2185] CONFIG (NumValues): Too many values (max=125)
[2229] CONFIG (NumValues): Too many values (max=62)
[3014] CONFIG (P0): Invalid device address (0-255)
[3022] CONFIG (P0): Invalid device address (1-255)
[3508] CONFIG (P1): Invalid command
[4001] CONFIG (P2): Invalid address
[8013] CONFIG (Remote): Acknowledge
[8034] CONFIG (Remote): Busy (rejected message)
[8138] CONFIG (Remote): Failure in associated device
[8168] CONFIG (Remote): Illegal data address
[8170] CONFIG (Remote): Illegal data value
[8172] CONFIG (Remote): Illegal function
[8347] CONFIG (Remote): Unknown error
This driver requires that you have TAS-HMITalk 8.04 installed.
Driver Source Code Last Update: 02/12/2007 15:59:42
Driver Reference Last Update: 10/30/2008 17:42:06
© 1990-2008, CPKSoft Engineering. All rights reserved.