CPKSoft Engineering

XMITSUFX.tlk Driver Reference

Mitsubishi PLC FX Series Protocol Driver

This driver requires that you have TAS-HMITalk 8.04 installed.

Driver Overview

XMITSUFX driver allows you to connect to the MITSUBISHI programmable

controllers, series FX, through an RS-422 to RS-232C interface unit.

The recommended interface is the FX-232AW unit, although any standard

232/422 converter can be good to communicate with the PLC through the

base unit programming connector.

 

Protocol specifications:

 

Transfer format: RS232C standard, asynchronous bi-directional (not simultaneously)

Baud rate: 9600 bps

Parity: Even

Verification: Sum check

Characters: ASCII, plus STX, ETX, ENQ, ACK and NAK.

 

IMPORTANT NOTE:

 

If you cannot communicate with your PLC, check after setting the

CommTxHoldRTSWhileTransmitting and CommTxHoldRTSWhileReceiving

properties both to On.

 

Inaccessible Areas:

 

The constant K setting of timer and counter coils in the program

area are not accessable via the interface. Use data registers to store

the setting if this function is desired.

 

File registers D1000 to D1999 are stored in the program memory area.

Thus they are not accessable via this interface. Normally, their data

has to be read to normal data registers before any process can be made

anyway.

Supported Equipment Type

Programmable Logic Controllers

Supported Devices List

MITSUBISHI Programmable Controllers FX Series.

Supported Commands List

Read Words of type T, C or D

Read Bits of type X, Y, M, S, T or C

Write Words of type T, C or D

Write Bits of type X, Y, M, S, T or C

Force Individual Bit of type X, Y, M, S, T or C

Read Words of type T, C or D

COMMAND DESCRIPTION:

Reads multiple current values of consecutive words of type

T (Timers), C (Counters) or D (Data registers).

The PLC can be in STOP or in RUN mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-32

HMITalk1.DriverP0 = 0

HMITalk1.DriverP6 = Determines the address of the first timer,

counter or data register to be read.

Valid addresses are:

- T0 to T255 for timers.

- C0 to C199 for counters.

- D0 to D511 for data registers.

- D8000 to D8255 for special data registers.

 

NOTE:

Parameters P1 to P5 and P7 to P9 are not used.

 

RETURNS:

- HMITalk1.PointValue(0) = First word value (0-65535)

- HMITalk1.PointValue(1) = Second word value (0-65535)

.

- HMITalk1.PointValue(DriverNumPoints-1) = Last word value (0-65535)

Read Bits of type X, Y, M, S, T or C

COMMAND DESCRIPTION:

Reads multiple current status of consecutive bits of type

X, Y, M, S, T, C (Contacts and coils). Bits are read in

groups of 8. The PLC can be in STOP or in RUN mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Input

HMITalk1.DriverNumPoints = 1-256

HMITalk1.DriverP0 = 0

HMITalk1.DriverP6 = Determines the address of the first group

of 8 bits to be read (contact or coil).

Valid addresses are:

- X0 to X170 (in multiples of 10)

- Y0 to Y170 (in multiples of 10)

- M0 to M1016 (in multiples of 8)

- M8000 to M8248 (in multiples of 8)

- S0 to S992 (in multiples of 8)

- T0 to T248 (in multiples of 8)

- C0 to C248 (in multiples of 8)

- Z0 to Z170 (in multiples of 10, for PLS Y, PLF Y COIL, status of prev scan)

- U0 to U248 (in multiples of 8, for OUT T COIL)

- N0 to N1016 (in multiples of 8, for PLS M, PLF M COIL, status of prev scan)

- D0 to D248 (in multiples of 8, for OUT C COIL)

- V0 to V248 (in multiples of 8, for RST T COIL)

- E0 to E248 (in multiples of 8, for RST C COIL)

 

NOTE:

Parameters P1 to P5 and P7 to P9 are not used.

 

RETURNS:

- HMITalk1.PointValue(0) = First bit status (0 or 1)

- HMITalk1.PointValue(1) = Second bit status (0 or 1)

.

- HMITalk1.PointValue(DriverNumPoints-1) = Last bit status (0 or 1)

Write Words of type T, C or D

COMMAND DESCRIPTION:

Writes multiple values of consecutive words of type

T (Timers), C (Counters) or D (Data registers).

The PLC can be in STOP or in RUN mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1-32

HMITalk1.DriverP0 = 0

HMITalk1.DriverP6 = Determines the address of the first timer,

counter or data register to be over-written.

Valid addresses are:

- T0 to T255 for timers.

- C0 to C199 for counters.

- D0 to D511 for data registers.

- D8000 to D8255 for special data registers.

 

NOTE:

Parameters P1 to P5 and P7 to P9 are not used.

 

WHERE:

- HMITalk1.PointValue(0) = Value for first word (0-65535)

- HMITalk1.PointValue(1) = Value for second word (0-65535)

.

- HMITalk1.PointValue(DriverNumPoints-1) = Value for last word (0-65535)

Write Bits of type X, Y, M, S, T or C

COMMAND DESCRIPTION:

Writes multiple status of consecutive bits of type

X, Y, M, S, T, C (Contacts and coils). Bits are written in

groups of 8. Address values must be a multiple of 8.

The PLC can be in STOP or in RUN mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1-256

HMITalk1.DriverP0 = 0

HMITalk1.DriverP6 = Determines the address of the first group

of 8 bits to be over-written.

Valid addresses are:

- X0 to X170 (in multiples of 10)

- Y0 to Y170 (in multiples of 10)

- M0 to M1016 (in multiples of 8)

- M8000 to M8248 (in multiples of 8)

- S0 to S992 (in multiples of 8)

- T0 to T248 (in multiples of 8)

- C0 to C248 (in multiples of 8)

- Z0 to Z170 (in multiples of 10, for PLS Y, PLF Y COIL, status of prev scan)

- U0 to U248 (in multiples of 8, for OUT T COIL)

- N0 to N1016 (in multiples of 8, for PLS M, PLF M COIL, status of prev scan)

- D0 to D248 (in multiples of 8, for OUT C COIL)

- V0 to V248 (in multiples of 8, for RST T COIL)

- E0 to E248 (in multiples of 8, for RST C COIL)

 

NOTE:

Parameters P1 to P5 and P7 to P9 are not used.

 

WHERE:

- HMITalk1.PointValue(0) = Status for first bit (0 or 1)

- HMITalk1.PointValue(1) = Status for second bit (0 or 1)

.

- HMITalk1.PointValue(DriverNumPoints-1) = Status for last bit (0 or 1)

Force Individual Bit of type X, Y, M, S, T or C

COMMAND DESCRIPTION:

Forces one single bit of type X, Y, M, S, T or C to an

ON of OFF state. The PLC can be in STOP or in RUN mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = 1

HMITalk1.DriverP6 = Determines the address of the bit

to be over-written.

Valid addresses are:

- X0 to X7, X10 to X17, ..., X170 to X177

- Y0 to Y7, Y10 to Y17, ..., Y170 to Y177

- M0 to M1023

- M8000 to M8255

- S0 to S999

- T0 to T255

- C0 to C255

 

NOTE:

Parameters P1 to P5 and P7 to P9 are not used.

 

WHERE:

- HMITalk1.PointValue(0) = Status for bit (0 or 1)

Returned Errors List

[1005] DRIVER (Internal): Invalid driver stage

[1300] PROTOCOL (Timeout): No answer

[1433] PROTOCOL (Format): Validation error in device response

[2139] CONFIG (NumValues): Only one bit can be written with this command

[2147] CONFIG (NumValues): Only one value can be read or written

[2186] CONFIG (NumValues): Too many values (max=128)

[2204] CONFIG (NumValues): Too many values (max=256)

[2209] CONFIG (NumValues): Too many values (max=32)

[2230] CONFIG (NumValues): Too many values (max=64)

[3001] CONFIG (P0): Invalid command

[3004] CONFIG (P0): Invalid command (2/3/4)

[4017] CONFIG (P2): Invalid bit number

[4018] CONFIG (P2): Invalid bit number (0-7)

[4089] CONFIG (P2): Invalid read mode

[4125] CONFIG (P2): Invalid write mode

[6008] CONFIG (P6): Invalid Address

About the XMITSUFX.tlk driver

This driver requires that you have TAS-HMITalk 8.04 installed.

Driver Source Code Last Update: 08/26/2004 17:37:30

Driver Reference Last Update: 10/30/2008 17:41:41

© 1990-2008, CPKSoft Engineering. All rights reserved.