CPKSoft Engineering

XINTERGY.tlk Driver Reference

Swichtec SM20/Sm50 Intergy Mini Power Driver

This driver requires that you have TAS-HMITalk 8.04 installed.

Driver Overview

XINTERGY driver allows you to connect to the Swichtec SM20/SM50

Intergy Mini Power Systems using the S3P protocol.

Communication is performed using a RS-232 port in the PC.

Packets are sent at 19200 baud with one start bit, 8 data bits,

one stop bit and no parity.

Supported Equipment Type

Power Meters

Supported Devices List

POWERWARE SWICHTEC Intergy SM20/SM50 Mini Power Systems

Supported Commands List

Connect to Slave

Disconnect from Slave

Read System Voltage

Read Load Current

Read Battery Current

Read Battery Temperature

Read Manual Equalise

Read Periodic Equalise

Read Battery Test

Read Alarm State

Read Rectifier Urgent Alarm

Read Rectifier Non Urgent Alarm

Connect to Slave

COMMAND DESCRIPTION:

Establishes a communication channel between the master PC

and the slave.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1.

HMITalk1.DriverP0 = Slave address (1-124).

Use 0 for a stand-alone device.

HMITalk1.DriverP1 = 1

Disconnect from Slave

COMMAND DESCRIPTION:

Reverts a slave to the disconnected state.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1.

HMITalk1.DriverP0 = Slave address (1-124).

Use 0 for a stand-alone device.

HMITalk1.DriverP1 = 0

Read System Voltage

COMMAND DESCRIPTION:

Returns the current DC bus voltage.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1.

HMITalk1.DriverP0 = Slave address (1-124).

Use 0 for a stand-alone device.

HMITalk1.DriverP1 = 16393

HMITalk1.DriverP2 = 14

Read Load Current

COMMAND DESCRIPTION:

Returns the load current.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1.

HMITalk1.DriverP0 = Slave address (1-124).

Use 0 for a stand-alone device.

HMITalk1.DriverP1 = 16392

HMITalk1.DriverP2 = 14

Read Battery Current

COMMAND DESCRIPTION:

Returns the battery current. This is positive for

current flowing into the batteries.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1.

HMITalk1.DriverP0 = Slave address (1-124).

Use 0 for a stand-alone device.

HMITalk1.DriverP1 = 16394

HMITalk1.DriverP2 = 14

Read Battery Temperature

COMMAND DESCRIPTION:

Returns the battery temperature.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1.

HMITalk1.DriverP0 = Slave address (1-124).

Use 0 for a stand-alone device.

HMITalk1.DriverP1 = 16395

HMITalk1.DriverP2 = 14

Read Manual Equalise

COMMAND DESCRIPTION:

Indicates present process state of manual equalise.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1.

HMITalk1.DriverP0 = Slave address (1-124).

Use 0 for a stand-alone device.

HMITalk1.DriverP1 = 16420

HMITalk1.DriverP2 = 5

 

RETURNS:

430 = process disabled

431 = process inactive

432 = process active

Read Periodic Equalise

COMMAND DESCRIPTION:

Indicates present process state of periodic equalise.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1.

HMITalk1.DriverP0 = Slave address (1-124).

Use 0 for a stand-alone device.

HMITalk1.DriverP1 = 16425

HMITalk1.DriverP2 = 5

 

RETURNS:

430 = process disabled

431 = process inactive

432 = process active

Read Battery Test

COMMAND DESCRIPTION:

Indicates present process state of battery test.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1.

HMITalk1.DriverP0 = Slave address (1-124).

Use 0 for a stand-alone device.

HMITalk1.DriverP1 = 16439

HMITalk1.DriverP2 = 5

 

RETURNS:

430 = process disabled

431 = process inactive

432 = process active

Read Alarm State

COMMAND DESCRIPTION:

Represents the current state of the system alarm.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1.

HMITalk1.DriverP0 = Slave address (1-124).

Use 0 for a stand-alone device.

HMITalk1.DriverP1 = 16466

HMITalk1.DriverP2 = 20

HMITalk1.DriverP3 = Alarm Index

 

RETURNS:

1 = alarm inactive

2 = alarm active

Read Rectifier Urgent Alarm

COMMAND DESCRIPTION:

Set to alarm active if there is presently an urgent

rectifier alarm.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1.

HMITalk1.DriverP0 = Slave address (1-124).

Use 0 for a stand-alone device.

HMITalk1.DriverP1 = 16467

HMITalk1.DriverP2 = 5

 

RETURNS:

1 = alarm inactive

2 = alarm active

Read Rectifier Non Urgent Alarm

COMMAND DESCRIPTION:

Set to alarm active if there is presently an non-urgent

rectifier alarm.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1.

HMITalk1.DriverP0 = Slave address (1-124).

Use 0 for a stand-alone device.

HMITalk1.DriverP1 = 16468

HMITalk1.DriverP2 = 5

 

RETURNS:

1 = alarm inactive

2 = alarm active

Returned Errors List

[1005] DRIVER (Internal): Invalid driver stage

[1300] PROTOCOL (Timeout): No answer

[1421] PROTOCOL (Format): Negative acknowledge received from device

[1433] PROTOCOL (Format): Validation error in device response

[2001] CONFIG (DataType): Analog outputs are not supported by this driver

[2002] CONFIG (DataType): Digital inputs are not supported by this driver

[3009] CONFIG (P0): Invalid device address (0-124)

[3510] CONFIG (P1): Invalid command (0 or 1 only)

About the XINTERGY.tlk driver

This driver requires that you have TAS-HMITalk 8.04 installed.

Driver Source Code Last Update: 03/08/2004 14:07:58

Driver Reference Last Update: 10/30/2008 17:40:04

© 1990-2008, CPKSoft Engineering. All rights reserved.