XINTERGY.tlk Driver Reference
Swichtec SM20/Sm50 Intergy Mini Power Driver
This driver requires that you have TAS-HMITalk 8.04 installed.
XINTERGY driver allows you to connect to the Swichtec SM20/SM50
Intergy Mini Power Systems using the S3P protocol.
Communication is performed using a RS-232 port in the PC.
Packets are sent at 19200 baud with one start bit, 8 data bits,
one stop bit and no parity.
Power Meters
POWERWARE SWICHTEC Intergy SM20/SM50 Mini Power Systems
Read Rectifier Non Urgent Alarm
COMMAND DESCRIPTION:
Establishes a communication channel between the master PC
and the slave.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Digital Output
HMITalk1.DriverNumPoints = 1.
HMITalk1.DriverP0 = Slave address (1-124).
Use 0 for a stand-alone device.
HMITalk1.DriverP1 = 1
COMMAND DESCRIPTION:
Reverts a slave to the disconnected state.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Digital Output
HMITalk1.DriverNumPoints = 1.
HMITalk1.DriverP0 = Slave address (1-124).
Use 0 for a stand-alone device.
HMITalk1.DriverP1 = 0
COMMAND DESCRIPTION:
Returns the current DC bus voltage.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1.
HMITalk1.DriverP0 = Slave address (1-124).
Use 0 for a stand-alone device.
HMITalk1.DriverP1 = 16393
HMITalk1.DriverP2 = 14
COMMAND DESCRIPTION:
Returns the load current.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1.
HMITalk1.DriverP0 = Slave address (1-124).
Use 0 for a stand-alone device.
HMITalk1.DriverP1 = 16392
HMITalk1.DriverP2 = 14
COMMAND DESCRIPTION:
Returns the battery current. This is positive for
current flowing into the batteries.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1.
HMITalk1.DriverP0 = Slave address (1-124).
Use 0 for a stand-alone device.
HMITalk1.DriverP1 = 16394
HMITalk1.DriverP2 = 14
COMMAND DESCRIPTION:
Returns the battery temperature.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1.
HMITalk1.DriverP0 = Slave address (1-124).
Use 0 for a stand-alone device.
HMITalk1.DriverP1 = 16395
HMITalk1.DriverP2 = 14
COMMAND DESCRIPTION:
Indicates present process state of manual equalise.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1.
HMITalk1.DriverP0 = Slave address (1-124).
Use 0 for a stand-alone device.
HMITalk1.DriverP1 = 16420
HMITalk1.DriverP2 = 5
RETURNS:
430 = process disabled
431 = process inactive
432 = process active
COMMAND DESCRIPTION:
Indicates present process state of periodic equalise.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1.
HMITalk1.DriverP0 = Slave address (1-124).
Use 0 for a stand-alone device.
HMITalk1.DriverP1 = 16425
HMITalk1.DriverP2 = 5
RETURNS:
430 = process disabled
431 = process inactive
432 = process active
COMMAND DESCRIPTION:
Indicates present process state of battery test.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1.
HMITalk1.DriverP0 = Slave address (1-124).
Use 0 for a stand-alone device.
HMITalk1.DriverP1 = 16439
HMITalk1.DriverP2 = 5
RETURNS:
430 = process disabled
431 = process inactive
432 = process active
COMMAND DESCRIPTION:
Represents the current state of the system alarm.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1.
HMITalk1.DriverP0 = Slave address (1-124).
Use 0 for a stand-alone device.
HMITalk1.DriverP1 = 16466
HMITalk1.DriverP2 = 20
HMITalk1.DriverP3 = Alarm Index
RETURNS:
1 = alarm inactive
2 = alarm active
COMMAND DESCRIPTION:
Set to alarm active if there is presently an urgent
rectifier alarm.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1.
HMITalk1.DriverP0 = Slave address (1-124).
Use 0 for a stand-alone device.
HMITalk1.DriverP1 = 16467
HMITalk1.DriverP2 = 5
RETURNS:
1 = alarm inactive
2 = alarm active
COMMAND DESCRIPTION:
Set to alarm active if there is presently an non-urgent
rectifier alarm.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1.
HMITalk1.DriverP0 = Slave address (1-124).
Use 0 for a stand-alone device.
HMITalk1.DriverP1 = 16468
HMITalk1.DriverP2 = 5
RETURNS:
1 = alarm inactive
2 = alarm active
[1005] DRIVER (Internal): Invalid driver stage
[1300] PROTOCOL (Timeout): No answer
[1421] PROTOCOL (Format): Negative acknowledge received from device
[1433] PROTOCOL (Format): Validation error in device response
[2001] CONFIG (DataType): Analog outputs are not supported by this driver
[2002] CONFIG (DataType): Digital inputs are not supported by this driver
[3009] CONFIG (P0): Invalid device address (0-124)
[3510] CONFIG (P1): Invalid command (0 or 1 only)
This driver requires that you have TAS-HMITalk 8.04 installed.