XGLOBALW.tlk Driver Reference
Global Weighing MP 30 Protocol Driver
This driver requires that you have TAS-HMITalk 8.04 installed.
XGLOBALW driver allows you to connect to the Sartorius Global Weighing
MP 30 digital indicators. The equipment is expected to use
mnemonics in the communication messages.
Scales and Load Cells
SARTORIUS GLOBAL WEIGHING MP 30 Digital Indicator
COMMAND DESCRIPTION:
This command allows you to read the Net Weight value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 0
RETURNS:
HMITalk1.PointValue(0) = Value read
COMMAND DESCRIPTION:
This command allows you to read the Total value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 1
RETURNS:
HMITalk1.PointValue(0) = Value read
COMMAND DESCRIPTION:
This command allows you to read the Max Input value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 2
RETURNS:
HMITalk1.PointValue(0) = Value read
COMMAND DESCRIPTION:
This command allows you to read the Min Input value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 3
RETURNS:
HMITalk1.PointValue(0) = Value read
COMMAND DESCRIPTION:
This command allows you to read the Setpoint 1 value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 4
RETURNS:
HMITalk1.PointValue(0) = Value read
COMMAND DESCRIPTION:
This command allows you to read the Setpoint 2 value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 5
RETURNS:
HMITalk1.PointValue(0) = Value read
COMMAND DESCRIPTION:
This command allows you to read the Setpoint 3 value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 6
RETURNS:
HMITalk1.PointValue(0) = Value read
COMMAND DESCRIPTION:
This command allows you to read the Setpoint 4 value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 7
RETURNS:
HMITalk1.PointValue(0) = Value read
COMMAND DESCRIPTION:
This command allows you to read the Analog Output Register
value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 8
RETURNS:
HMITalk1.PointValue(0) = Value read
COMMAND DESCRIPTION:
This command allows you to read the Control Status Register
value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 9
RETURNS:
HMITalk1.PointValue(0) = Value read
COMMAND DESCRIPTION:
This command allows you to read the Gross Weight value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 10
RETURNS:
HMITalk1.PointValue(0) = Value read
COMMAND DESCRIPTION:
This command allows you to read the Tare Weight value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 11
RETURNS:
HMITalk1.PointValue(0) = Value read
COMMAND DESCRIPTION:
This command allows you to read the Front Key State.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Digital Input
HMITalk1.DriverNumPoints = 1-5
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 12
RETURNS:
HMITalk1.PointValue(0) = F1 Key
HMITalk1.PointValue(1) = F2 Key
HMITalk1.PointValue(2) = RST Key
HMITalk1.PointValue(3) = Second F1 Key
HMITalk1.PointValue(4) = Second F2 Key
COMMAND DESCRIPTION:
This command allows you to read the User Inputs State.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Digital Input
HMITalk1.DriverNumPoints = 1-6
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 13
RETURNS:
HMITalk1.PointValue(0) = User 1 Edge
HMITalk1.PointValue(1) = User 2 Edge
HMITalk1.PointValue(2) = User 3 Edge
HMITalk1.PointValue(3) = User 1 Level
HMITalk1.PointValue(4) = User 2 Level
HMITalk1.PointValue(5) = User 3 Level
COMMAND DESCRIPTION:
This command allows you to read the Setpoint Auto/Manual Modes.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Digital Input
HMITalk1.DriverNumPoints = 1-5
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 14
RETURNS:
HMITalk1.PointValue(0) = SP1 Mode
HMITalk1.PointValue(1) = SP2 Mode
HMITalk1.PointValue(2) = SP3 Mode
HMITalk1.PointValue(3) = SP4 Mode
HMITalk1.PointValue(4) = Analog Output Mode
COMMAND DESCRIPTION:
This command allows you to read the Setpoint Outputs State.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Digital Input
HMITalk1.DriverNumPoints = 1-4
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 15
RETURNS:
HMITalk1.PointValue(0) = SP1 State
HMITalk1.PointValue(1) = SP2 State
HMITalk1.PointValue(2) = SP3 State
HMITalk1.PointValue(3) = SP4 State
COMMAND DESCRIPTION:
This command allows you to reset the Total value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 1
WHERE:
HMITalk1.PointValue(0) = Ignored
COMMAND DESCRIPTION:
This command allows you to reset the Max Input value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 2
WHERE:
HMITalk1.PointValue(0) = Ignored
COMMAND DESCRIPTION:
This command allows you to reset the Min Input value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 3
WHERE:
HMITalk1.PointValue(0) = Ignored
COMMAND DESCRIPTION:
This command allows you to set the Setpoint 1 value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 4
WHERE:
HMITalk1.PointValue(0) = New Setpoint 1 Value
COMMAND DESCRIPTION:
This command allows you to set the Setpoint 2 value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 5
WHERE:
HMITalk1.PointValue(0) = New Setpoint 2 Value
COMMAND DESCRIPTION:
This command allows you to set the Setpoint 3 value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 6
WHERE:
HMITalk1.PointValue(0) = New Setpoint 3 Value
COMMAND DESCRIPTION:
This command allows you to set the Setpoint 4 value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 7
WHERE:
HMITalk1.PointValue(0) = New Setpoint 4 Value
COMMAND DESCRIPTION:
This command allows you to set the Analog Output Register
value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 8
WHERE:
HMITalk1.PointValue(0) = New Analog Output Register Value
COMMAND DESCRIPTION:
This command allows you to set the Control Status Register
value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Indicates the station address (00-99).
If 0 indicates point-to-point connection.
HMITalk1.DriverP1 = 9
WHERE:
HMITalk1.PointValue(0) = New Control Status Register Value
[1005] DRIVER (Internal): Invalid driver stage
[1300] PROTOCOL (Timeout): No answer
[1410] PROTOCOL (Format): Invalid device id in response
[3018] CONFIG (P0): Invalid device address (0-99)
[3508] CONFIG (P1): Invalid command
This driver requires that you have TAS-HMITalk 8.04 installed.
Driver Source Code Last Update: 03/08/2004 14:07:12
Driver Reference Last Update: 10/30/2008 17:38:42
© 1990-2008, CPKSoft Engineering. All rights reserved.