CPKSoft Engineering

XGEFAN90.tlk Driver Reference

GE Fanuc Series 90 SNP-X Protocol Driver

This driver requires that you have TAS-HMITalk 8.04 installed.

Driver Overview

XGEFAN90 driver allows connecting to the General Electric

model GE FANUC series 90 PLC using the SNP-X communication protocol.

Communication is made through an RS-232 or RS-485 port.

Supported Equipment Type

Programmable Logic Controllers

Supported Devices List

GENERAL ELECTRIC Model GE FANUC Series 90 PLC

Supported Commands List

Read Registers

Read Analog Inputs

Read Analog Outputs

Read Discrete Inputs in Bit Mode

Read Discrete Inputs in Byte Mode

Read Discrete Outputs in Bit Mode

Read Discrete Outputs in Byte Mode

Read Discrete Temporaries in Bit Mode

Read Discrete Temporaries in Byte Mode

Read Discrete Internals in Bit Mode

Read Discrete Internals in Byte Mode

Read Discrete SA in Bit Mode

Read Discrete SA in Byte Mode

Read Discrete SB in Bit Mode

Read Discrete SB in Byte Mode

Read Discrete SC in Bit Mode

Read Discrete SC in Byte Mode

Read Discrete S in Bit Mode

Read Discrete S in Byte Mode

Read Discrete Genius Global Data in Bit Mode

Read Discrete Genius Global Data in Byte Mode

Write Registers

Write Analog Inputs

Write Analog Outputs

Write Discrete Inputs in Bit Mode

Write Discrete Inputs in Byte Mode

Write Discrete Outputs in Bit Mode

Write Discrete Outputs in Byte Mode

Write Discrete Temporaries in Bit Mode

Write Discrete Temporaries in Byte Mode

Write Discrete Internals in Bit Mode

Write Discrete Internals in Byte Mode

Write Discrete SA in Bit Mode

Write Discrete SA in Byte Mode

Write Discrete SB in Bit Mode

Write Discrete SB in Byte Mode

Write Discrete SC in Bit Mode

Write Discrete SC in Byte Mode

Read Registers

COMMAND DESCRIPTION:

This command allows you to read the value of the registers.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Given that P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 8

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Read Analog Inputs

COMMAND DESCRIPTION:

This command allows you to read the value of the analog inputs.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 10

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Read Analog Outputs

COMMAND DESCRIPTION:

This command allows you to read the value of the analog outputs.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 12

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Read Discrete Inputs in Bit Mode

COMMAND DESCRIPTION:

This command allows you to read the value of the discrete inputs

in bit mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 70

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Read Discrete Inputs in Byte Mode

COMMAND DESCRIPTION:

This command allows you to read the value of the discrete inputs

in byte mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 16

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Read Discrete Outputs in Bit Mode

COMMAND DESCRIPTION:

This command allows you to read the value of the discrete outputs

in bit mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 72

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Read Discrete Outputs in Byte Mode

COMMAND DESCRIPTION:

This command allows you to read the value of the discrete outputs

in byte mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 18

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Read Discrete Temporaries in Bit Mode

COMMAND DESCRIPTION:

This command allows you to read the value of the discrete

temporaries in bit mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 74

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Read Discrete Temporaries in Byte Mode

COMMAND DESCRIPTION:

This command allows you to read the value of the discrete

temporaries in byte mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 20

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Read Discrete Internals in Bit Mode

COMMAND DESCRIPTION:

This command allows you to read the value of the discrete

internals in bit mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 76

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Read Discrete Internals in Byte Mode

COMMAND DESCRIPTION:

This command allows you to read the value of the discrete

internals in byte mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 22

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Read Discrete SA in Bit Mode

COMMAND DESCRIPTION:

This command allows you to read the value of the discrete SA

in bit mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 78

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Read Discrete SA in Byte Mode

COMMAND DESCRIPTION:

This command allows you to read the value of the discrete SA

in byte mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 24

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Read Discrete SB in Bit Mode

COMMAND DESCRIPTION:

This command allows you to read the value of the discrete SB

in bit mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 80

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Read Discrete SB in Byte Mode

COMMAND DESCRIPTION:

This command allows you to read the value of the discrete SB

in byte mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 26

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Read Discrete SC in Bit Mode

COMMAND DESCRIPTION:

This command allows you to read the value of the discrete SC

in bit mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 82

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Read Discrete SC in Byte Mode

COMMAND DESCRIPTION:

This command allows you to read the value of the discrete SC

in byte mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 28

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Read Discrete S in Bit Mode

COMMAND DESCRIPTION:

This command allows you to read the value of the discrete S

in bit mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 84

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Read Discrete S in Byte Mode

COMMAND DESCRIPTION:

This command allows you to read the value of the discrete S

in byte mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 30

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Read Discrete Genius Global Data in Bit Mode

COMMAND DESCRIPTION:

This command allows you to read the value of the discrete

genius global data in bit mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 86

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Read Discrete Genius Global Data in Byte Mode

COMMAND DESCRIPTION:

This command allows you to read the value of the discrete

genius global data in byte mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-200

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 56

HMITalk1.DriverP2 = Defines the address of the element to be read (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before reading.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Write Registers

COMMAND DESCRIPTION:

This command allows you to write the value of the registers.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 8

HMITalk1.DriverP2 = Defines the address of the element to be write (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before writing.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Write Analog Inputs

COMMAND DESCRIPTION:

This command allows you to write the value of the analog inputs.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 10

HMITalk1.DriverP2 = Defines the address of the element to be write (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before writing.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Write Analog Outputs

COMMAND DESCRIPTION:

This command allows you to write the value of the analog outputs.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 12

HMITalk1.DriverP2 = Defines the address of the element to be write (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before writing.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Write Discrete Inputs in Bit Mode

COMMAND DESCRIPTION:

This command allows you to write the value of the discrete inputs

in bit mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 70

HMITalk1.DriverP2 = Defines the address of the element to be write (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before writing.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Write Discrete Inputs in Byte Mode

COMMAND DESCRIPTION:

This command allows you to write the value of the discrete inputs

in byte mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1-8

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 16

HMITalk1.DriverP2 = Defines the address of the element to be write (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before writing.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Write Discrete Outputs in Bit Mode

COMMAND DESCRIPTION:

This command allows you to write the value of the discrete outputs

in bit mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 72

HMITalk1.DriverP2 = Defines the address of the element to be write (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before writing.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Write Discrete Outputs in Byte Mode

COMMAND DESCRIPTION:

This command allows you to write the value of the discrete outputs

in byte mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1-8

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 18

HMITalk1.DriverP2 = Defines the address of the element to be write (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before writing.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Write Discrete Temporaries in Bit Mode

COMMAND DESCRIPTION:

This command allows you to write the value of the discrete

temporaries in bit mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 74

HMITalk1.DriverP2 = Defines the address of the element to be write (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before writing.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Write Discrete Temporaries in Byte Mode

COMMAND DESCRIPTION:

This command allows you to write the value of the discrete

temporaries in byte mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1-8

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 20

HMITalk1.DriverP2 = Defines the address of the element to be write (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before writing.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Write Discrete Internals in Bit Mode

COMMAND DESCRIPTION:

This command allows you to write the value of the discrete

internals in bit mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 76

HMITalk1.DriverP2 = Defines the address of the element to be write (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before writing.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Write Discrete Internals in Byte Mode

COMMAND DESCRIPTION:

This command allows you to write the value of the discrete

internals in byte mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1-8

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 22

HMITalk1.DriverP2 = Defines the address of the element to be write (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before writing.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Write Discrete SA in Bit Mode

COMMAND DESCRIPTION:

This command allows you to write the value of the discrete SA

in bit mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 78

HMITalk1.DriverP2 = Defines the address of the element to be write (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before writing.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Write Discrete SA in Byte Mode

COMMAND DESCRIPTION:

This command allows you to write the value of the discrete SA

in byte mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1-8

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 24

HMITalk1.DriverP2 = Defines the address of the element to be write (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before writing.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Write Discrete SB in Bit Mode

COMMAND DESCRIPTION:

This command allows you to write the value of the discrete SB

in bit mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 80

HMITalk1.DriverP2 = Defines the address of the element to be write (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before writing.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Write Discrete SB in Byte Mode

COMMAND DESCRIPTION:

This command allows you to write the value of the discrete SB

in byte mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1-8

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 26

HMITalk1.DriverP2 = Defines the address of the element to be write (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before writing.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Write Discrete SC in Bit Mode

COMMAND DESCRIPTION:

This command allows you to write the value of the discrete SC

in bit mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 82

HMITalk1.DriverP2 = Defines the address of the element to be write (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before writing.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Write Discrete SC in Byte Mode

COMMAND DESCRIPTION:

This command allows you to write the value of the discrete SC

in byte mode.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1-8

HMITalk1.DriverP0 = Indentifies the station address number (001-999).

The SNP ID expected by the PLC is in fact a string of 8 ASCII characters.

Becasue P0 is a numeric parameter, the string used is always "GEFxxx\0\0"

where xxx is the part specified in P0 as the station number (3 digits).

For example, if the station number indicated in P0 is 1, the SNP ID

will be sent as GEF001\0\0, or what is the same, "GEF001" followed

by two NULL characters.

NOTE: If DriverP0=-1, the driver will send the string given in DriverP6.

HMITalk1.DriverP1 = 28

HMITalk1.DriverP2 = Defines the address of the element to be write (1..65535).

HMITalk1.DriverP3 = Indicates if the ATTACH command is sent before writing.

- 0 = Send the ATTACH command.

- 1 = Do not send the ATTACH command.

(Its use is necesary when the first request to the PLC is

done, because up to that moment the PLC has not yet been

initialized for communications.)

HMITalk1.DriverP4 = Defines the duration in msec. of the initial break signal

(standard: 400 msec.).

HMITalk1.DriverP5 = Defines the time delay in msec., to wait before sending the

attach command (standard: 50 msec. in a point to point

connection, 600 msec. in a modem connection).

HMITalk1.DriverP6 = Station name used when DriverP0=-1. Must be a 8-character string.

Returned Errors List

[1005] DRIVER (Internal): Invalid driver stage

[1300] PROTOCOL (Timeout): No answer

[1410] PROTOCOL (Format): Invalid device id in response

[1415] PROTOCOL (Format): Invalid response format

[1433] PROTOCOL (Format): Validation error in device response

[2147] CONFIG (NumValues): Only one value can be read or written

[2196] CONFIG (NumValues): Too many values (max=200)

[3019] CONFIG (P0): Invalid device address (0-999)

[3030] CONFIG (P0): Invalid device address (1-999)

[3508] CONFIG (P1): Invalid command

[4007] CONFIG (P2): Invalid address (0-65535)

[4508] CONFIG (P3): Invalid attach mode (0-1)

[6036] CONFIG (P6): Station number must have 1 to 8 characters

[8029] CONFIG (Remote): Autodial Error

[8173] CONFIG (Remote): Illegal mailbox type

[8175] CONFIG (Remote): Illegal service request

[8187] CONFIG (Remote): Insufficient privilege

[8193] CONFIG (Remote): Invalid command returned

[8209] CONFIG (Remote): Local SNP/SNP-X error

[8271] CONFIG (Remote): Problem with getting mail to slave service request task

[8272] CONFIG (Remote): Problem with sending mail to slave service request task

[8285] CONFIG (Remote): Protocol sequence error

[8300] CONFIG (Remote): Remote SNP error

[8317] CONFIG (Remote): Service request error

[8318] CONFIG (Remote): Slave SNP task could not find the requested datagram connection

[8319] CONFIG (Remote): Slave SNP task encountered an error in trying to update the datagram

[8320] CONFIG (Remote): Slave SNP task encountered an error in trying to write the datagram

[8321] CONFIG (Remote): Slave SNP task time out before receiving an response

[8322] CONFIG (Remote): SNP DOS driver error

[8323] CONFIG (Remote): SNP-X slave error

[8332] CONFIG (Remote): The PLC CPU's service request queue is full

[8347] CONFIG (Remote): Unknown error

About the XGEFAN90.tlk driver

This driver requires that you have TAS-HMITalk 8.04 installed.

Driver Source Code Last Update: 11/17/2004 11:46:17

Driver Reference Last Update: 10/30/2008 17:38:28

© 1990-2008, CPKSoft Engineering. All rights reserved.

http://www.cpksoft.com - support@cpksoft.com

http://www.cpksoft.com.ar - soporte@cpksoft.com.ar>