XGAVAZZI.tlk Driver Reference
Carlo GAVAZZI Instruments Protocol Driver
This driver requires that you have TAS-HMITalk 8.04 installed.
XGAVAZZI driver allows you to connect with Carlo GAVAZZI Instruments,
WM1-DIN Power Meter Series.
RS-232 and RS-485 communications are both supported by these meters.
Up to 32 meters can be connected when using RS-485.
Power Meters
GAVAZZI WM1-DIN Power Meter Series
Request for Power Factor / CosFi
COMMAND DESCRIPTION:
This command reads the Voltage value of the Power Meter.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Address (0-255)
HMITalk1.DriverP1 = 3
COMMAND DESCRIPTION:
This command reads the Current (amps.) value of the Power Meter.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Address (0-255)
HMITalk1.DriverP1 = 4
COMMAND DESCRIPTION:
This command reads the Power Factor value of the Power Meter.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Address (0-255)
HMITalk1.DriverP1 = 5
COMMAND DESCRIPTION:
This command reads the Active Power value of the Power Meter.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Address (0-255)
HMITalk1.DriverP1 = 6
COMMAND DESCRIPTION:
This command reads the Aparent Power value of the Power Meter.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Address (0-255)
HMITalk1.DriverP1 = 7
COMMAND DESCRIPTION:
This command reads the Reactive Power value of the Power Meter.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Address (0-255)
HMITalk1.DriverP1 = 8
COMMAND DESCRIPTION:
This command reads the Energy value of the Power Meter.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Address (0-255)
HMITalk1.DriverP1 = 9
COMMAND DESCRIPTION:
This command reads Status of the Power Meter's Output. This
command is considered as an Analog Input holding digital information.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Address (0-255)
HMITalk1.DriverP1 = 10
COMMAND DESCRIPTION:
This command activates an output of the Power Meter.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Digital Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Address (0-255)
HMITalk1.DriverP1 = 0
COMMAND DESCRIPTION:
This command deactivates an output of the Power Meter.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Digital Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Address (0-255)
HMITalk1.DriverP1 = 1
COMMAND DESCRIPTION:
This command resets total values of the Power Meter.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Digital Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Address (0-255)
HMITalk1.DriverP1 = 2
[1005] DRIVER (Internal): Invalid driver stage
[1300] PROTOCOL (Timeout): No answer
[1421] PROTOCOL (Format): Negative acknowledge received from device
[2001] CONFIG (DataType): Analog outputs are not supported by this driver
[2002] CONFIG (DataType): Digital inputs are not supported by this driver
[2147] CONFIG (NumValues): Only one value can be read or written
[3515] CONFIG (P1): Invalid command (0/1/2)
[3529] CONFIG (P1): Invalid command (3/4/5/6/7/8/9/10)
[8255] CONFIG (Remote): Overflow error present on requested data
[8349] CONFIG (Remote): Unknown error present on requested data
This driver requires that you have TAS-HMITalk 8.04 installed.
Driver Source Code Last Update: 03/08/2004 14:07:20
Driver Reference Last Update: 10/30/2008 17:38:02