XELVIPD3.tlk Driver Reference
ElControl Energy VIPD3-485 Protocol Driver
This driver requires that you have TAS-HMITalk 8.04 installed.
XELVIPD3 driver allows you to connect with ELCONTROL ENERGY devices
model VIPD3-485.
The most common serial setup is:
9600 | 1200 Bauds, 7 Db, No parity, 1 Sb.
It is strongly recommended that you use The PC-485 Box RS-232/485
converter supplied by ELCONTROL. The device could behave erratically
if you use a different RS-232/485 converter.
Power Meters
ELCONTROL ENERGY VIPD3-485 Energy Monitor
ELCONTROL ENERGY VIPD3-485 HV Energy Monitor
Average and Picks Reset with Date & Time Information
Counter Reset with Date & Time Information
Write K Factor of Current Transformer in VIPD3-485
Write K Factor of Current Transformer in VIPD3-485 HV
Write K Factor of Voltage Transformer in VIPD3-485 HV
COMMAND DESCRIPTION:
Obtains all data measured.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-37
HMITalk1.DriverP0 = Station Number (1-247).
HMITalk1.DriverP1 = 1
RETURNS:
- HMITalk1.PointValue(0) = Voltage 3-Phase
- HMITalk1.PointValue(1) = Current 3-Phase
- HMITalk1.PointValue(2) = Active Power 3-Phase
- HMITalk1.PointValue(3) = Power Factor 3-Phase
- HMITalk1.PointValue(4) = Voltage Phase L1
- HMITalk1.PointValue(5) = Voltage Phase L2
- HMITalk1.PointValue(6) = Voltage Phase L3
- HMITalk1.PointValue(7) = Current Phase L1
- HMITalk1.PointValue(8) = Current Phase L2
- HMITalk1.PointValue(9) = Current Phase L3
- HMITalk1.PointValue(10) = Active Power Phase L1
- HMITalk1.PointValue(11) = Active Power Phase L2
- HMITalk1.PointValue(12) = Active Power Phase L3
- HMITalk1.PointValue(13) = Apparent Power 3-Phase
- HMITalk1.PointValue(14) = Reactive Power 3-Phase
- HMITalk1.PointValue(15) = Frecuency
- HMITalk1.PointValue(16) = Real Energy 3-Phase
- HMITalk1.PointValue(17) = Reactive Energy 3-Phase
- HMITalk1.PointValue(18) = Apparent Power Peaks
- HMITalk1.PointValue(19) = Active Power Peaks
- HMITalk1.PointValue(20) = Apparent Power Average
- HMITalk1.PointValue(21) = Active Power Average
- HMITalk1.PointValue(22) = TDHTF of Phase L1
- HMITalk1.PointValue(23) = TDHTF of Phase L2
- HMITalk1.PointValue(24) = TDHTF of Phase L3
- HMITalk1.PointValue(25) = Connection Type (0 = Single Phase,
1 = 3-Phase)
- HMITalk1.PointValue(26) = Analog Output Full Scale (0 = 750 V,
1 = 250 V) or PQS Output Pulse Value Select
(0 = 1 Pulse = 3 W/h, 1 = 20 Pulses = 3 W/h)
- HMITalk1.PointValue(27) = Select Baudrate (0 = 9600, 1 = 1200)
- HMITalk1.PointValue(28) = Select Instrument Type:
1 = VIP D
2 = VIP 96
3 = VIP D3
4 = VIP DC
5 = OEM1 Module
6 = OEM3 Module
7 = VIP D144
8 = VIP D30 A
9 = VIP DBatt
10 = NanoVip
11 = PFRM
12 = Micro VIP 3
15 = VIPD3-HV
- HMITalk1.PointValue(29) = RS485: Present MODBUS Protocol
- HMITalk1.PointValue(30) = Present Q Analog Output
- HMITalk1.PointValue(31) = Present S Analog Output
- HMITalk1.PointValue(32) = Present P Analog Output
- HMITalk1.PointValue(33) = Present Q Pulse Output
- HMITalk1.PointValue(34) = Present S Pulse Output
- HMITalk1.PointValue(35) = Present P Pulse Output
- HMITalk1.PointValue(36) = RS232: Present ELCONTROL Protocol
COMMAND DESCRIPTION:
Enable/Disable keyboard.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Digital Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Station Number (1-247).
HMITalk1.DriverP1 = 2
COMMAND DESCRIPTION:
Average and picks reset and returns the date & time information
corresponding to the moment the reset was done.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-6
HMITalk1.DriverP0 = Station Number (1-247).
HMITalk1.DriverP1 = 3
RETURNS:
- HMITalk1.PointValue(0) = Month
- HMITalk1.PointValue(1) = Day
- HMITalk1.PointValue(2) = Year
- HMITalk1.PointValue(3) = Hour
- HMITalk1.PointValue(4) = Minutes
- HMITalk1.PointValue(5) = Seconds
COMMAND DESCRIPTION:
Counter reset and returns the date & time information.
corresponding to the moment the reset was done.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-6
HMITalk1.DriverP0 = Station Number (1-247).
HMITalk1.DriverP1 = 4
COMMAND DESCRIPTION:
Writes the K factor of current transformer in VIPD3-485.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Station Number (1-247).
HMITalk1.DriverP1 = 5
WHERE:
- 00 - Reserved
- 01 - Transformer = 10/1 K = 10
- 02 - Transformer = 100/1 K = 100
- 03 - Transformer = 200/1 K = 200
- 04 - Transformer = 500/1 K = 500
- 05 - Transformer = 1000/1 K = 1000
- 06 - Transformer = 3000/1 K = 3000
- 07 - Transformer = 5/5 K = 1
- 08 - Transformer = 20/5 K = 4
- 09 - Transformer = 30/5 K = 6
- 10 - Transformer = 50/5 K = 10
- 11 - Transformer = 60/5 K = 12
- 12 - Transformer = 75/5 K = 15
- 13 - Transformer = 80/5 K = 16
- 14 - Transformer = 100/5 K = 20
- 15 - Transformer = 150/5 K = 30
- 16 - Transformer = 200/5 K = 40
- 17 - Transformer = 250/5 K = 50
- 18 - Transformer = 300/5 K = 60
- 19 - Transformer = 400/5 K = 80
- 20 - Transformer = 500/5 K = 100
- 21 - Transformer = 600/5 K = 120
- 22 - Transformer = 800/5 K = 160
- 23 - Transformer = 1000/5 K = 200
- 24 - Transformer = 1200/5 K = 240
- 25 - Transformer = 1500/5 K = 300
- 26 - Transformer = 2000/5 K = 400
- 27 - Transformer = 2500/5 K = 500
- 28 - Transformer = 3000/5 K = 600
COMMAND DESCRIPTION:
Writes the K factor of current transformer in VIPD3-485 HV.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Station Number (1-247).
HMITalk1.DriverP1 = 6
WHERE:
- 00 - Reserved
- 01 - Transformer = 10/1 K = 10
- 02 - Transformer = 50/1 K = 50
- 03 - Transformer = 100/1 K = 100
- 04 - Transformer = 200/1 K = 200
- 05 - Transformer = 250/1 K = 250
- 06 - Transformer = 300/1 K = 300
- 07 - Transformer = 400/1 K = 400
- 08 - Transformer = 500/1 K = 500
- 09 - Transformer = 600/1 K = 600
- 10 - Transformer = 700/1 K = 700
- 11 - Transformer = 750/1 K = 750
- 12 - Transformer = 800/1 K = 800
- 13 - Transformer = 1000/1 K = 1000
- 14 - Transformer = 1200/1 K = 1200
- 15 - Transformer = 1600/1 K = 1600
- 16 - Transformer = 2000/1 K = 2000
- 17 - Transformer = 2400/1 K = 2400
- 18 - Transformer = 3000/1 K = 3000
- 19 - Transformer = 4000/1 K = 4000
- 20 - Transformer = 5/5 K = 1
- 21 - Transformer = 10/5 K = 2
- 22 - Transformer = 15/5 K = 3
- 23 - Transformer = 20/5 K = 4
- 24 - Transformer = 30/5 K = 6
- 25 - Transformer = 40/5 K = 8
- 26 - Transformer = 50/5 K = 10
- 27 - Transformer = 60/5 K = 12
- 28 - Transformer = 75/5 K = 15
- 29 - Transformer = 80/5 K = 16
- 30 - Transformer = 100/5 K = 20
- 31 - Transformer = 150/5 K = 30
- 32 - Transformer = 200/5 K = 40
- 33 - Transformer = 250/5 K = 50
- 34 - Transformer = 300/5 K = 60
- 35 - Transformer = 400/5 K = 80
- 36 - Transformer = 500/5 K = 100
- 37 - Transformer = 600/5 K = 120
- 38 - Transformer = 800/5 K = 160
- 39 - Transformer = 900/5 K = 180
- 40 - Transformer = 1000/5 K = 200
- 41 - Transformer = 1200/5 K = 240
- 42 - Transformer = 1500/5 K = 300
- 43 - Transformer = 1600/5 K = 320
- 44 - Transformer = 2000/5 K = 400
- 45 - Transformer = 2500/5 K = 500
- 46 - Transformer = 3000/5 K = 600
- 47 - Transformer = 3500/5 K = 700
- 48 - Transformer = 4000/5 K = 800
- 49 - Transformer = 5000/5 K = 1000
- 50 - Transformer = 6000/5 K = 1200
COMMAND DESCRIPTION:
Writes the K factor of voltage transformer in VIPD3-485 HV.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Station Number (1-247).
HMITalk1.DriverP1 = 7
WHERE:
- 00 - Reserved
- 01 - Transformer = 380/100 K = 3.8
- 02 - Transformer = 400/100 K = 4
- 03 - Transformer = 600/100 K = 6
- 04 - Transformer = 1000/100 K = 10
- 05 - Transformer = 2000/100 K = 20
- 06 - Transformer = 3000/100 K = 30
- 07 - Transformer = 6000/100 K = 60
- 08 - Transformer = 10000/100 K = 100
- 09 - Transformer = 12000/100 K = 120
- 10 - Transformer = 15000/100 K = 150
- 11 - Transformer = 20000/100 K = 200
- 12 - Transformer = 30000/100 K = 300
- 13 - Transformer = 150000/100 K = 1500
- 14 - Transformer = 500000/100 K = 5000
- 15 - Transformer = 3300/110 K = 30
- 16 - Transformer = 6600/110 K = 60
- 17 - Transformer = 11000/110 K = 100
- 18 - Transformer = 22000/110 K = 200
- 19 - Transformer = 33000/110 K = 300
- 20 - Transformer = 44000/110 K = 400
- 21 - Transformer = 66000/110 K = 600
- 22 - Transformer = 88000/110 K = 800
- 23 - Transformer = 110000/110 K = 1000
- 24 - Transformer = 132000/110 K = 1200
- 25 - Transformer = 220000/110 K = 2000
- 26 - Transformer = 275000/110 K = 2500
- 27 - Transformer = 330000/110 K = 3000
- 28 - Transformer = 550000/110 K = 5000
- 29 - Transformer = 20125/115 K = 175
- 30 - Transformer = 34500/115 K = 300
- 31 - Transformer = 840/120 K = 7
- 32 - Transformer = 1200/120 K = 10
- 33 - Transformer = 2400/120 K = 20
- 34 - Transformer = 4200/120 K = 35
- 35 - Transformer = 4800/120 K = 40
- 36 - Transformer = 7200/120 K = 60
- 37 - Transformer = 8400/120 K = 70
- 38 - Transformer = 12000/120 K = 100
- 39 - Transformer = 14400/120 K = 120
- 40 - Transformer = 24000/120 K = 200
COMMAND DESCRIPTION:
Writes integration period.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Station Number (1-247).
HMITalk1.DriverP1 = 8
HMITalk1.DriverP2 = Indicates the equipment to be used.
- 0 = VIPD3-485
- 1 = VIPD3-485-HV
WHERE:
- 0 = 10 Minutes
- 1 = 15 Minutes
- 2 = 20 Minutes
- 3 = 30 Minutes
[1005] DRIVER (Internal): Invalid driver stage
[1300] PROTOCOL (Timeout): No answer
[1408] PROTOCOL (Format): Invalid amount of data bytes received
[1410] PROTOCOL (Format): Invalid device id in response
[1433] PROTOCOL (Format): Validation error in device response
[2002] CONFIG (DataType): Digital inputs are not supported by this driver
[2147] CONFIG (NumValues): Only one value can be read or written
[2214] CONFIG (NumValues): Too many values (max=37)
[2226] CONFIG (NumValues): Too many values (max=6)
[3007] CONFIG (P0): Invalid device address
[3508] CONFIG (P1): Invalid command
[8013] CONFIG (Remote): Acknowledge
[8036] CONFIG (Remote): Busy, rejected message
[8138] CONFIG (Remote): Failure in associated device
[8168] CONFIG (Remote): Illegal data address
[8170] CONFIG (Remote): Illegal data value
[8172] CONFIG (Remote): Illegal function
[8217] CONFIG (Remote): NAK-negative acknowledgment
[8347] CONFIG (Remote): Unknown error
This driver requires that you have TAS-HMITalk 8.04 installed.
Driver Source Code Last Update: 03/08/2004 14:07:46
Driver Reference Last Update: 10/30/2008 17:37:12
© 1990-2008, CPKSoft Engineering. All rights reserved.