XCVMITF.tlk Driver Reference
Circutor CVM-ITF/CVM-R8C Controllers Protocol Driver
This driver requires that you have TAS-HMITalk 8.04 installed.
XCVMITF driver allows you to connect with CIRCUTOR CVM-ITF/BD Series
Supply Network Analyzer and CIRCUTOR CVM-R8C/R8D Programable
Peripherals. This driver complies with Instruction Manual M981
171/96-001 (2/2) from Circutor S.A.
Power Meters
CIRCUTOR CVM-ITF Energy Network Analyzer
CIRCUTOR CVM-R8C Programmable Peripheral
CIRCUTOR CVM-R8D Programmable Peripheral
CIRCUTOR CVM-BD Series Supply Network Analyzer
Read Voltages Phase-Phase INST (V)
Read Voltages Phase-Phase MAX (V)
Read Voltages Phase-Phase MIN (V)
Read Voltages Phase-Neutral INST (V)
Read Voltages Phase-Neutral MAX (V)
Read Voltages Phase-Neutral MIN (V)
Read Inductive Powers INST (var.L)
Read Inductive Powers MAX (var.L)
Read Inductive Powers MIN (var.L)
Read Capacitive Powers INST (var.C)
Read Capacitive Powers MAX (var.C)
Read Capacitive Powers MIN (var.C)
Write Measuring Mode (Type of Set Voltage)
Read Inductive Energy (varh.L)
Read Capacitive Energy (varh.C)
Read Initial Value of Positive Energies (W.h)
Write Initial Positive Energies
Read Initial Value of Negative Energies (W.h)
Write Initial Negative Energies
Read Input and Relay Status in CVM-R8C
Write Input and Relay Status in CVM-R8C
Read Scale Factors of A/D Converter in CVM-R8C
Write Scale Factors of A/D Converter in CVM-R8C
Write Leds Activation in CVM-R8C
Read Integer Type Registers in CVM-R8C
Write Integer Type Registers in CVM-R8C
COMMAND DESCRIPTION:
Reads Voltages Phase-Phase INST in Volts.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-4
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 0
RETURNS:
- HMITalk1.PointValue(0) = Voltage Phase-Phase L12
- HMITalk1.PointValue(1) = Voltage Phase-Phase L23
- HMITalk1.PointValue(2) = Voltage Phase-Phase L31
- HMITalk1.PointValue(3) = Voltage Phase-Phase Av
COMMAND DESCRIPTION:
Reads Voltages Phase-Phase MAX in Volts.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-3
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 1
RETURNS:
- HMITalk1.PointValue(0) = Voltage Phase-Phase L12 Max.
- HMITalk1.PointValue(1) = Voltage Phase-Phase L23 Max.
- HMITalk1.PointValue(2) = Voltage Phase-Phase L31 Max.
COMMAND DESCRIPTION:
Reads Voltages Phase-Phase MIN in Volts.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-3
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 2
RETURNS:
- HMITalk1.PointValue(0) = Voltage Phase-Phase L12 Min.
- HMITalk1.PointValue(1) = Voltage Phase-Phase L23 Min.
- HMITalk1.PointValue(2) = Voltage Phase-Phase L31 Min.
COMMAND DESCRIPTION:
Reads Voltages Phase-Neutral INST in Volts.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-4
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 3
RETURNS:
- HMITalk1.PointValue(0) = Voltage L1
- HMITalk1.PointValue(1) = Voltage L2
- HMITalk1.PointValue(2) = Voltage L3
- HMITalk1.PointValue(3) = Voltage Av
COMMAND DESCRIPTION:
Reads Voltages Phase-Neutral MAX in Volts.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-3
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 4
RETURNS:
- HMITalk1.PointValue(0) = Voltage L1 Max.
- HMITalk1.PointValue(1) = Voltage L2 Max.
- HMITalk1.PointValue(2) = Voltage L3 Max.
COMMAND DESCRIPTION:
Reads Voltages Phase-Neutral MIN in Volts.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-3
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 5
RETURNS:
- HMITalk1.PointValue(0) = Voltage L1 Min.
- HMITalk1.PointValue(1) = Voltage L2 Min.
- HMITalk1.PointValue(2) = Voltage L3 Min.
COMMAND DESCRIPTION:
Reads Currents INST in mA.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-4
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 6
RETURNS:
- HMITalk1.PointValue(0) = Current L1
- HMITalk1.PointValue(1) = Current L2
- HMITalk1.PointValue(2) = Current L3
- HMITalk1.PointValue(3) = Current Av
COMMAND DESCRIPTION:
Reads Currents MAX in mA.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-3
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 7
RETURNS:
- HMITalk1.PointValue(0) = Current L1 Max.
- HMITalk1.PointValue(1) = Current L2 Max.
- HMITalk1.PointValue(2) = Current L3 Max.
COMMAND DESCRIPTION:
Reads Currents MIN in mA.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-3
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 8
RETURNS:
- HMITalk1.PointValue(0) = Current L1 Min.
- HMITalk1.PointValue(1) = Current L2 Min.
- HMITalk1.PointValue(2) = Current L3 Min.
COMMAND DESCRIPTION:
Reads Active Powers INST in Watts.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-4
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 9
RETURNS:
- HMITalk1.PointValue(0) = Power L1
- HMITalk1.PointValue(1) = Power L2
- HMITalk1.PointValue(2) = Power L3
- HMITalk1.PointValue(3) = Power III
COMMAND DESCRIPTION:
Reads Active Powers MAX in Watts.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-4
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 10
RETURNS:
- HMITalk1.PointValue(0) = Power L1 Max.
- HMITalk1.PointValue(1) = Power L2 Max.
- HMITalk1.PointValue(2) = Power L3 Max.
- HMITalk1.PointValue(3) = Power III Max.
COMMAND DESCRIPTION:
Reads Active Powers MIN in Watts.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-4
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 11
RETURNS:
- HMITalk1.PointValue(0) = Power L1 Min.
- HMITalk1.PointValue(1) = Power L2 Min.
- HMITalk1.PointValue(2) = Power L3 Min.
- HMITalk1.PointValue(3) = Power III Min.
COMMAND DESCRIPTION:
Reads Inductive Powers INST in var.L.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-4
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 12
RETURNS:
- HMITalk1.PointValue(0) = Inductive Power L1
- HMITalk1.PointValue(1) = Inductive Power L2
- HMITalk1.PointValue(2) = Inductive Power L3
- HMITalk1.PointValue(3) = Inductive Power III
COMMAND DESCRIPTION:
Reads Inductive Powers MAX in var.L.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-4
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 13
RETURNS:
- HMITalk1.PointValue(0) = Inductive Power L1 Max.
- HMITalk1.PointValue(1) = Inductive Power L2 Max.
- HMITalk1.PointValue(2) = Inductive Power L3 Max.
- HMITalk1.PointValue(3) = Inductive Power III Max.
COMMAND DESCRIPTION:
Reads Inductive Powers MIN in var.L.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-4
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 14
RETURNS:
- HMITalk1.PointValue(0) = Inductive Power L1 Min.
- HMITalk1.PointValue(1) = Inductive Power L2 Min.
- HMITalk1.PointValue(2) = Inductive Power L3 Min.
- HMITalk1.PointValue(3) = Inductive Power III Min.
COMMAND DESCRIPTION:
Reads Capacitive Powers INST in var.C.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-4
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 15
RETURNS:
- HMITalk1.PointValue(0) = Capacitive Power L1
- HMITalk1.PointValue(1) = Capacitive Power L2
- HMITalk1.PointValue(2) = Capacitive Power L3
- HMITalk1.PointValue(3) = Capacitive Power III
COMMAND DESCRIPTION:
Reads Capacitive Powers MAX in var.C.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-4
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 16
RETURNS:
- HMITalk1.PointValue(0) = Capacitive Power L1 Max.
- HMITalk1.PointValue(1) = Capacitive Power L2 Max.
- HMITalk1.PointValue(2) = Capacitive Power L3 Max.
- HMITalk1.PointValue(3) = Capacitive Power III Max.
COMMAND DESCRIPTION:
Reads Capacitive Powers MIN in var.C.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-3
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 17
RETURNS:
- HMITalk1.PointValue(0) = Capacitive Power L1 Min.
- HMITalk1.PointValue(1) = Capacitive Power L2 Min.
- HMITalk1.PointValue(2) = Capacitive Power L3 Min.
COMMAND DESCRIPTION:
Reads Power Factors INST.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-4
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 18
RETURNS:
- HMITalk1.PointValue(0) = Power Factor L1
- HMITalk1.PointValue(1) = Power Factor L2
- HMITalk1.PointValue(2) = Power Factor L3
- HMITalk1.PointValue(3) = Power Factor Av
COMMAND DESCRIPTION:
Reads Power Factors MAX.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-3
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 19
RETURNS:
- HMITalk1.PointValue(0) = Power Factor L1 Max.
- HMITalk1.PointValue(1) = Power Factor L2 Max.
- HMITalk1.PointValue(2) = Power Factor L3 Max.
COMMAND DESCRIPTION:
Reads Power Factors MIN.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-3
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 20
RETURNS:
- HMITalk1.PointValue(0) = Power Factor L1 Min.
- HMITalk1.PointValue(1) = Power Factor L2 Min.
- HMITalk1.PointValue(2) = Power Factor L3 Min.
COMMAND DESCRIPTION:
Reads Frequency INST in Hz.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 21
RETURNS:
- HMITalk1.PointValue(0) = Frequency
COMMAND DESCRIPTION:
Reads Frequency MAX in Hz.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 22
RETURNS:
- HMITalk1.PointValue(0) = Frequency Max.
COMMAND DESCRIPTION:
Reads Frequency MIN in Hz.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 23
RETURNS:
- HMITalk1.PointValue(0) = Frequency Min.
COMMAND DESCRIPTION:
Reads Apparent Power INST in VA.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 24
RETURNS:
- HMITalk1.PointValue(0) = Apparent Power.
COMMAND DESCRIPTION:
Reads Apparent Power MAX in VA.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 25
RETURNS:
- HMITalk1.PointValue(0) = Apparent Power Max.
COMMAND DESCRIPTION:
Reads Apparent Power MIN in VA.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 26
RETURNS:
- HMITalk1.PointValue(0) = Apparent Power Min.
COMMAND DESCRIPTION:
Reads Transforming Ratios.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-3
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 27
RETURNS:
- HMITalk1.PointValue(0) = Prim V
- HMITalk1.PointValue(1) = Sec V
- HMITalk1.PointValue(2) = Prim A
COMMAND DESCRIPTION:
Writes Transforming Ratios.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 3
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 34
WHERE:
- HMITalk1.PointValue(0) = Prim V
- HMITalk1.PointValue(1) = Sec V
- HMITalk1.PointValue(2) = Prim A
COMMAND DESCRIPTION:
Reads Type of Set Voltage.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 28
RETURNS:
- HMITalk1.PointValue(0) = Type of Set Voltage
WHERE:
- 0 = Phase - Phase (Compound)
- 1 = Phase - Neutral (Single)
COMMAND DESCRIPTION:
Writes Measuring Mode (Type of Set Voltage).
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 35
WHERE:
- HMITalk1.PointValue(0) = New Measuring Mode
- 0 = Phase - Phase (Compound)
- 1 = Phase - Neutral (Single)
COMMAND DESCRIPTION:
Reads Total Information.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-30
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 29
RETURNS:
- HMITalk1.PointValue(0) = Voltage Phase-Phase L12 (V).
- HMITalk1.PointValue(1) = Voltage Phase-Phase L23 (V).
- HMITalk1.PointValue(2) = Voltage Phase-Phase L31 (V).
- HMITalk1.PointValue(3) = Voltage Phase-Phase Av (V).
- HMITalk1.PointValue(4) = Voltage Phase-Neutral L1 (V).
- HMITalk1.PointValue(5) = Voltage Phase-Neutral L2 (V).
- HMITalk1.PointValue(6) = Voltage Phase-Neutral L3 (V).
- HMITalk1.PointValue(7) = Voltage Phase-Neutral Av.
- HMITalk1.PointValue(8) = Current L1 (mA).
- HMITalk1.PointValue(9) = Current L2 (mA).
- HMITalk1.PointValue(10) = Current L3 (mA).
- HMITalk1.PointValue(11) = Current Av (mA).
- HMITalk1.PointValue(12) = Active Power L1 (W).
- HMITalk1.PointValue(13) = Active Power L2 (W).
- HMITalk1.PointValue(14) = Active Power L3 (W).
- HMITalk1.PointValue(15) = Active Power III (W).
- HMITalk1.PointValue(16) = Inductive Power L1 (var.L).
- HMITalk1.PointValue(17) = Inductive Power L2 (var.L).
- HMITalk1.PointValue(18) = Inductive Power L3 (var.L).
- HMITalk1.PointValue(19) = Inductive Power III (var.L).
- HMITalk1.PointValue(20) = Capacitive Power L1 (var.C).
- HMITalk1.PointValue(21) = Capacitive Power L2 (var.C).
- HMITalk1.PointValue(22) = Capacitive Power L3 (var.C).
- HMITalk1.PointValue(23) = Capacitive Power III (var.C).
- HMITalk1.PointValue(24) = Power Factor L1.
- HMITalk1.PointValue(25) = Power Factor L2.
- HMITalk1.PointValue(26) = Power Factor L3.
- HMITalk1.PointValue(27) = Power Factor Av.
- HMITalk1.PointValue(28) = Frequency.
- HMITalk1.PointValue(29) = Apparent Power (VA).
COMMAND DESCRIPTION:
Reads Active Energy in W.h.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 30
RETURNS:
- HMITalk1.PointValue(0) = Active Energy
COMMAND DESCRIPTION:
Reads Inductive Energy in varh.L.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 31
RETURNS:
- HMITalk1.PointValue(0) = Inductive Energy
COMMAND DESCRIPTION:
Reads Capacitive Energy in varh.C.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 32
RETURNS:
- HMITalk1.PointValue(0) = Capacitive Energy
COMMAND DESCRIPTION:
Reads Initial Value of the Positive Energies.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-3
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 33
RETURNS:
- HMITalk1.PointValue(0) = Active Energy
- HMITalk1.PointValue(1) = Inductive Energy
- HMITalk1.PointValue(2) = Capacitive Energy
COMMAND DESCRIPTION:
Writes Initial value of the positive Energies.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 3
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 36
WHERE:
- HMITalk1.PointValue(0) = Active Energy
- HMITalk1.PointValue(1) = Inductive Energy
- HMITalk1.PointValue(2) = Capacitive Energy
COMMAND DESCRIPTION:
Reads Initial Value of the Negative Energies.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-3
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 45
RETURNS:
- HMITalk1.PointValue(0) = Active Energy
- HMITalk1.PointValue(1) = Inductive Energy
- HMITalk1.PointValue(2) = Capacitive Energy
COMMAND DESCRIPTION:
Writes Initial absolute value of the negative Energies.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 3
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 46
WHERE:
- HMITalk1.PointValue(0) = Active Energy (absolute value)
- HMITalk1.PointValue(1) = Inductive Energy (absolute value)
- HMITalk1.PointValue(2) = Capacitive Energy (absolute value)
COMMAND DESCRIPTION:
Reads Date and Time.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-6
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 47
RETURNS:
- HMITalk1.PointValue(0) = Day (1-31)
- HMITalk1.PointValue(1) = Month (1-12)
- HMITalk1.PointValue(2) = Year (1990-2089)
- HMITalk1.PointValue(3) = Hour (0-23)
- HMITalk1.PointValue(4) = Minutes (0-59)
- HMITalk1.PointValue(5) = Seconds (0-59)
COMMAND DESCRIPTION:
Writes Date and Time.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 6
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 48
WHERE:
- HMITalk1.PointValue(0) = Day (1-31)
- HMITalk1.PointValue(1) = Month (1-12)
- HMITalk1.PointValue(2) = Year (1990-2089)
- HMITalk1.PointValue(3) = Hour (0-23)
- HMITalk1.PointValue(4) = Minutes (0-59)
- HMITalk1.PointValue(5) = Seconds (0-59)
COMMAND DESCRIPTION:
Reads Power Demand Period + Parameter.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-2
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 49
RETURNS:
- HMITalk1.PointValue(0) = Power Demand Period
- HMITalk1.PointValue(1) = Parameter
- 21 = kW
- 26 = KVA
- 20 = AIII
COMMAND DESCRIPTION:
Writes Power Demand Period + Parameter.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 2
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 50
WHERE:
- HMITalk1.PointValue(0) = Power Demand Period
- HMITalk1.PointValue(1) = Parameter
- 21 = kW
- 26 = KVA
- 20 = AIII
COMMAND DESCRIPTION:
Reads Maximum Demand Value.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-8
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 51
RETURNS:
- HMITalk1.PointValue(0) = Day (1-31)
- HMITalk1.PointValue(1) = Month (1-12)
- HMITalk1.PointValue(2) = Year (1990-2089)
- HMITalk1.PointValue(3) = Hour (0-23)
- HMITalk1.PointValue(4) = Minutes (0-59)
- HMITalk1.PointValue(5) = Seconds (0-59)
- HMITalk1.PointValue(6) = Maximum from the last reset
- HMITalk1.PointValue(7) = Last Period maximum
COMMAND DESCRIPTION:
Deletes Maximum Demand Value (max pd = 0).
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 52
WHERE:
- HMITalk1.PointValue(0) = Not relevant.
COMMAND DESCRIPTION:
Reads Input and Relay Status in CVM-R8C.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Digital Input
HMITalk1.DriverNumPoints = 1-99
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 37
HMITalk1.DriverP2 = Defines the first register to be read.
- 1 .. 18 = Inputs
- 100 .. 117 = External Relays
COMMAND DESCRIPTION:
Writes Input and Relay Status in CVM-R8C.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Digital Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 38
HMITalk1.DriverP2 = Defines the register to be written (0-9999).
COMMAND DESCRIPTION:
Reads A/D Channels in CVM-R8C.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-2
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 39
WHERE:
- HMITalk1.PointValue(0) = DC1 Channel.
- HMITalk1.PointValue(1) = DC2 Channel.
COMMAND DESCRIPTION:
Reads Scale Factors of A/D Converter in CVM-R8C.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-2
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 40
WHERE:
- HMITalk1.PointValue(0) = Channel Factor 1.
- HMITalk1.PointValue(1) = Channel Factor 2.
COMMAND DESCRIPTION:
Writes Scale Factors of A/D Converter in CVM-R8C.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 2
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 41
WHERE:
- HMITalk1.PointValue(0) = Channel Factor 1.
- HMITalk1.PointValue(1) = Channel Factor 2.
COMMAND DESCRIPTION:
Writes Leds Activation in CVM-R8C.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Digital Output
HMITalk1.DriverNumPoints = 3
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 42
WHERE:
- HMITalk1.PointValue(0) = Test (0 = Desactivate / 1 = Activate).
- HMITalk1.PointValue(1) = Led 1 (Comm).
- HMITalk1.PointValue(2) = Led 2 (CPU).
COMMAND DESCRIPTION:
Reads Integer Type Registers in CVM-R8C.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-99
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 43
HMITalk1.DriverP2 = First register to be read (0-499).
COMMAND DESCRIPTION:
Writes Integer Type Registers in CVM-R8C.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1
HMITalk1.DriverP0 = Unit Address (0-99).
HMITalk1.DriverP1 = 44
HMITalk1.DriverP2 = First register to be written (0-499).
[1005] DRIVER (Internal): Invalid driver stage
[1300] PROTOCOL (Timeout): No answer
[1433] PROTOCOL (Format): Validation error in device response
[2117] CONFIG (NumValues): Invalid number of values (must be 2)
[2122] CONFIG (NumValues): Invalid number of values (must be 3)
[2129] CONFIG (NumValues): Invalid number of values (must be 6)
[2147] CONFIG (NumValues): Only one value can be read or written
[2193] CONFIG (NumValues): Too many values (max=19)
[2194] CONFIG (NumValues): Too many values (max=2)
[2206] CONFIG (NumValues): Too many values (max=3)
[2207] CONFIG (NumValues): Too many values (max=30)
[2216] CONFIG (NumValues): Too many values (max=4)
[2226] CONFIG (NumValues): Too many values (max=6)
[2235] CONFIG (NumValues): Too many values (max=8)
[2243] CONFIG (NumValues): Too many values (max=99)
[3018] CONFIG (P0): Invalid device address (0-99)
[3508] CONFIG (P1): Invalid command
[4063] CONFIG (P2): Invalid first register (0-499)
[4064] CONFIG (P2): Invalid first register (0-999)
[4065] CONFIG (P2): Invalid first register (0-9999)
[8130] CONFIG (Remote): Error Response
[9500] CONFIG (Value): Invalid day in Value[0] (1-31)
[9501] CONFIG (Value): Invalid hour in Value[3] (0-23)
[9502] CONFIG (Value): Invalid minutes in Value[4] (0-59)
[9503] CONFIG (Value): Invalid month in Value[1] (1-12)
[9504] CONFIG (Value): Invalid parameter in Value[1] (20/21/26 only)
[9505] CONFIG (Value): Invalid seconds in Value[5] (0-59)
[9506] CONFIG (Value): Invalid year in Value[2] (1990-2089)
This driver requires that you have TAS-HMITalk 8.04 installed.
Driver Source Code Last Update: 03/22/2004 18:25:26
Driver Reference Last Update: 10/30/2008 17:35:54
© 1990-2008, CPKSoft Engineering. All rights reserved.