XALGODUE.tlk Driver Reference
Algodue UPM Series Universal Power Meters Driver
This driver requires that you have TAS-HMITalk 8.04 installed.
XALGODUE driver allows you to connect with UPM320 Universal Power
Meter from Algodue Elettronica. Communication with the UPM320
takes place by means of an asynchronous serial transmission,
half duplex RS-485. The RS485 standard enables a multi-drop
connection, which is the connection of several instruments to
a host with only one cable. Use isolated converters to connect
the instruments to the PC.
Power Meters
ALGODUE UPM300 Universal Power Meter
ALGODUE UPM320 Universal Power Meter
COMMAND DESCRIPTION:
This command reads all the available measured values.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-32
HMITalk1.DriverP0 = Instrument Identification (0-255)
HMITalk1.DriverP1 = 62
RETURNS:
- HMITalk1.PointValue(0) = THREE-PHASE SYSTEM VOLTAGE (rms)
- HMITalk1.PointValue(1) = PHASE L1 VOLTAGE (rms)
- HMITalk1.PointValue(2) = PHASE L2 VOLTAGE (rms)
- HMITalk1.PointValue(3) = PHASE L3 VOLTAGE (rms)
- HMITalk1.PointValue(4) = LINE L1-L2 VOLTAGE (rms)
- HMITalk1.PointValue(5) = LINE L2-L3 VOLTAGE (rms)
- HMITalk1.PointValue(6) = LINE L3-L1 VOLTAGE (rms)
- HMITalk1.PointValue(7) = THREE-PHASE SYSTEM CURRENT (rms)
- HMITalk1.PointValue(8) = LINE L1 CURRENT (rms)
- HMITalk1.PointValue(9) = LINE L2 CURRENT (rms)
- HMITalk1.PointValue(10) = LINE L3 CURRENT (rms)
- HMITalk1.PointValue(11) = THREE-PHASE SYSTEM POWER FACTOR
- HMITalk1.PointValue(12) = PHASE L1 POWER FACTOR
- HMITalk1.PointValue(13) = PHASE L2 POWER FACTOR
- HMITalk1.PointValue(14) = PHASE L3 POWER FACTOR
- HMITalk1.PointValue(15) = THREE-PHASE SYSTEM APPARENT POWER
- HMITalk1.PointValue(16) = PHASE L1 APPARENT POWER
- HMITalk1.PointValue(17) = PHASE L2 APPARENT POWER
- HMITalk1.PointValue(18) = PHASE L3 APPARENT POWER
- HMITalk1.PointValue(19) = THREE-PHASE SYSTEM ACTIVE POWER
- HMITalk1.PointValue(20) = PHASE L1 ACTIVE POWER
- HMITalk1.PointValue(21) = PHASE L2 ACTIVE POWER
- HMITalk1.PointValue(22) = PHASE L3 ACTIVE POWER
- HMITalk1.PointValue(23) = THREE-PHASE SYSTEM REACTIVE POWER
- HMITalk1.PointValue(24) = PHASE L1 REACTIVE POWER
- HMITalk1.PointValue(25) = PHASE L2 REACTIVE POWER
- HMITalk1.PointValue(26) = PHASE L3 REACTIVE POWER
- HMITalk1.PointValue(27) = 3-PHASE SYSTEM ACTIVE ENERGY
- HMITalk1.PointValue(28) = 3-PHASE SYSTEM REACTIVE ENERGY
- HMITalk1.PointValue(39) = FREQUENCY
- HMITalk1.PointValue(30) = AVERAGE POWER
- HMITalk1.PointValue(31) = AVERAGE CURRENT
COMMAND DESCRIPTION:
This command reads all the maximum values.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-5
HMITalk1.DriverP0 = Instrument Identification (0-255)
HMITalk1.DriverP1 = 97
RETURNS:
- HMITalk1.PointValue(0) = MAXIMUM I1
- HMITalk1.PointValue(1) = MAXIMUM I2
- HMITalk1.PointValue(2) = MAXIMUM I3
- HMITalk1.PointValue(3) = MAXIMUM Pav
- HMITalk1.PointValue(4) = MAXIMUM Iav
[1005] DRIVER (Internal): Invalid driver stage
[1300] PROTOCOL (Timeout): No answer
[1433] PROTOCOL (Format): Validation error in device response
[2001] CONFIG (DataType): Analog outputs are not supported by this driver
[2002] CONFIG (DataType): Digital inputs are not supported by this driver
[2003] CONFIG (DataType): Digital outputs are not supported by this driver
[2258] CONFIG (NumValues): Too many values requested (max=32)
[2262] CONFIG (NumValues): Too many values requested (max=5)
[3014] CONFIG (P0): Invalid device address (0-255)
[3508] CONFIG (P1): Invalid command