CPKSoft Engineering

XAFEISA.tlk Driver Reference

Afeisa Industrial Microcomputers Protocol Driver

This driver requires that you have TAS-HMITalk 8.04 installed.

Driver Overview

XAFEISA driver allows you to connect with Afeisa Industrial

Microcomputers.

Supported Equipment Type

Power Meters

Programmable Logic Controllers

Supported Devices List

AFEISA MIDA 20D Industrial Microcomputer

Supported Commands List

Read Voltage Phase-Phase INST

Read Voltage Phase-Phase MAX

Read Voltage Phase-Phase MIN

Read Voltage INST

Read Voltage MAX

Read Voltage MIN

Read Current INST

Read Current MAX

Read Current MIN

Read Power INST

Read Power MAX

Read Power MIN

Read Inductive Power INST

Read Inductive Power MAX

Read Inductive Power MIN

Read Capacitive Power INST

Read Capacitive Power MAX

Read Capacitive Power MIN

Read Power Factor INST

Read Power Factor MAX

Read Power Factor MIN

Read Frequency INST

Read Frequency MAX

Read Frequency MIN

Read Apparent Power INST

Read Apparent Power MAX

Read Apparent Power MIN

Read Transformers Ratio

Read Type of Voltage

Read Total Information

Read Active Energy

Read Inductive Energy

Read Capacitive Energy

Read Initial Energies

Write Transformers Ratio

Write Type of Voltage

Write Initial Energies

Read Input and Relay Status in MIDA 20D

Write Input and Relay Status in MIDA 20D

Read A/D Channels in MIDA 20D

Read Scale Factors of A/D Converter in MIDA 20D

Write Scale Factors of A/D Converter in MIDA 20D

Write Leds Activation in MIDA 20D

Read Integer Type Registers in MIDA 20D

Write Integer Type Registers in MIDA 20D

Read Voltage Phase-Phase INST

COMMAND DESCRIPTION:

Reads Voltage Phase-Phase INST.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-4

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 0

 

RETURNS:

- HMITalk1.PointValue(0) = Voltage Phase-Phase L12

- HMITalk1.PointValue(1) = Voltage Phase-Phase L23

- HMITalk1.PointValue(2) = Voltage Phase-Phase L31

- HMITalk1.PointValue(3) = Voltage Three-Phase Network

Read Voltage Phase-Phase MAX

COMMAND DESCRIPTION:

Reads Voltage Phase-Phase MAX.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 1

 

RETURNS:

- HMITalk1.PointValue(0) = Voltage Phase-Phase L12 Max.

- HMITalk1.PointValue(1) = Voltage Phase-Phase L23 Max.

- HMITalk1.PointValue(2) = Voltage Phase-Phase L31 Max.

Read Voltage Phase-Phase MIN

COMMAND DESCRIPTION:

Reads Voltage Phase-Phase MIN.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 2

 

RETURNS:

- HMITalk1.PointValue(0) = Voltage Phase-Phase L12 Min.

- HMITalk1.PointValue(1) = Voltage Phase-Phase L23 Min.

- HMITalk1.PointValue(2) = Voltage Phase-Phase L31 Min.

Read Voltage INST

COMMAND DESCRIPTION:

Reads Voltage INST.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-4

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 3

 

RETURNS:

- HMITalk1.PointValue(0) = Voltage L12

- HMITalk1.PointValue(1) = Voltage L23

- HMITalk1.PointValue(2) = Voltage L31

- HMITalk1.PointValue(3) = Voltage Network

Read Voltage MAX

COMMAND DESCRIPTION:

Reads Voltage MAX.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 4

 

RETURNS:

- HMITalk1.PointValue(0) = Voltage L12 Max.

- HMITalk1.PointValue(1) = Voltage L23 Max.

- HMITalk1.PointValue(2) = Voltage L31 Max.

Read Voltage MIN

COMMAND DESCRIPTION:

Reads Voltage MIN.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 5

 

RETURNS:

- HMITalk1.PointValue(0) = Voltage L12 Min.

- HMITalk1.PointValue(1) = Voltage L23 Min.

- HMITalk1.PointValue(2) = Voltage L31 Min.

Read Current INST

COMMAND DESCRIPTION:

Reads Current INST.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-4

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 6

 

RETURNS:

- HMITalk1.PointValue(0) = Current L12

- HMITalk1.PointValue(1) = Current L23

- HMITalk1.PointValue(2) = Current L31

- HMITalk1.PointValue(3) = Current Network

Read Current MAX

COMMAND DESCRIPTION:

Reads Current MAX.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 7

 

RETURNS:

- HMITalk1.PointValue(0) = Current L12 Max.

- HMITalk1.PointValue(1) = Current L23 Max.

- HMITalk1.PointValue(2) = Current L31 Max.

Read Current MIN

COMMAND DESCRIPTION:

Reads Current MIN.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 8

 

RETURNS:

- HMITalk1.PointValue(0) = Current L12 Min.

- HMITalk1.PointValue(1) = Current L23 Min.

- HMITalk1.PointValue(2) = Current L31 Min.

Read Power INST

COMMAND DESCRIPTION:

Reads Power INST.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-4

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 9

 

RETURNS:

- HMITalk1.PointValue(0) = Power L12

- HMITalk1.PointValue(1) = Power L23

- HMITalk1.PointValue(2) = Power L31

- HMITalk1.PointValue(3) = Power Network

Read Power MAX

COMMAND DESCRIPTION:

Reads Power MAX.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 10

 

RETURNS:

- HMITalk1.PointValue(0) = Power L12 Max.

- HMITalk1.PointValue(1) = Power L23 Max.

- HMITalk1.PointValue(2) = Power L31 Max.

Read Power MIN

COMMAND DESCRIPTION:

Reads Power MIN.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 11

 

RETURNS:

- HMITalk1.PointValue(0) = Power L12 Min.

- HMITalk1.PointValue(1) = Power L23 Min.

- HMITalk1.PointValue(2) = Power L31 Min.

Read Inductive Power INST

COMMAND DESCRIPTION:

Reads Inductive Power INST.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-4

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 12

 

RETURNS:

- HMITalk1.PointValue(0) = Inductive Power L12

- HMITalk1.PointValue(1) = Inductive Power L23

- HMITalk1.PointValue(2) = Inductive Power L31

- HMITalk1.PointValue(3) = Inductive Power Network

Read Inductive Power MAX

COMMAND DESCRIPTION:

Reads Inductive Power MAX.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 13

 

RETURNS:

- HMITalk1.PointValue(0) = Inductive Power L12 Max.

- HMITalk1.PointValue(1) = Inductive Power L23 Max.

- HMITalk1.PointValue(2) = Inductive Power L31 Max.

Read Inductive Power MIN

COMMAND DESCRIPTION:

Reads Inductive Power MIN.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 14

 

RETURNS:

- HMITalk1.PointValue(0) = Inductive Power L12 Min.

- HMITalk1.PointValue(1) = Inductive Power L23 Min.

- HMITalk1.PointValue(2) = Inductive Power L31 Min.

Read Capacitive Power INST

COMMAND DESCRIPTION:

Reads Capacitive Power INST.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-4

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 15

 

RETURNS:

- HMITalk1.PointValue(0) = Capacitive Power L12

- HMITalk1.PointValue(1) = Capacitive Power L23

- HMITalk1.PointValue(2) = Capacitive Power L31

- HMITalk1.PointValue(3) = Capacitive Power Network

Read Capacitive Power MAX

COMMAND DESCRIPTION:

Reads Capacitive Power MAX.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 16

 

RETURNS:

- HMITalk1.PointValue(0) = Capacitive Power L12 Max.

- HMITalk1.PointValue(1) = Capacitive Power L23 Max.

- HMITalk1.PointValue(2) = Capacitive Power L31 Max.

Read Capacitive Power MIN

DESCR2PTION:

Reads Capacitive Power MIN.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 17

 

RETURNS:

- HMITalk1.PointValue(0) = Capacitive Power L12 Min.

- HMITalk1.PointValue(1) = Capacitive Power L23 Min.

- HMITalk1.PointValue(2) = Capacitive Power L31 Min.

Read Power Factor INST

COMMAND DESCRIPTION:

Reads Power Factor INST.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-4

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 18

 

RETURNS:

- HMITalk1.PointValue(0) = Power Factor L12

- HMITalk1.PointValue(1) = Power Factor L23

- HMITalk1.PointValue(2) = Power Factor L31

- HMITalk1.PointValue(3) = Power Factor Network

Read Power Factor MAX

COMMAND DESCRIPTION:

Reads Power Factor MAX.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 19

 

RETURNS:

- HMITalk1.PointValue(0) = Power Factor L12 Max.

- HMITalk1.PointValue(1) = Power Factor L23 Max.

- HMITalk1.PointValue(2) = Power Factor L31 Max.

Read Power Factor MIN

COMMAND DESCRIPTION:

Reads Power Factor MIN.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 20

 

RETURNS:

- HMITalk1.PointValue(0) = Power Factor L12 Min.

- HMITalk1.PointValue(1) = Power Factor L23 Min.

- HMITalk1.PointValue(2) = Power Factor L31 Min.

Read Frequency INST

COMMAND DESCRIPTION:

Reads Frequency INST.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 21

Read Frequency MAX

COMMAND DESCRIPTION:

Reads Frequency MAX.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 22

Read Frequency MIN

COMMAND DESCRIPTION:

Reads Frequency MIN.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 23

Read Apparent Power INST

COMMAND DESCRIPTION:

Reads Apparent Power INST.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 24

Read Apparent Power MAX

COMMAND DESCRIPTION:

Reads Apparent Power MAX.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 25

Read Apparent Power MIN

COMMAND DESCRIPTION:

Reads Apparent Power MIN.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 26

Read Transformers Ratio

COMMAND DESCRIPTION:

Reads Transformers Ratio.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 27

 

RETURNS:

- HMITalk1.PointValue(0) = Prim V

- HMITalk1.PointValue(1) = Sec V

- HMITalk1.PointValue(2) = Prim A

Read Type of Voltage

COMMAND DESCRIPTION:

Reads Type of Voltage.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 28

 

WHERE:

- 0 = Phase - Phase

- 1 = Phase - Neutral

Read Total Information

COMMAND DESCRIPTION:

Reads Total Information.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-30

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 29

 

RETURNS:

- HMITalk1.PointValue(0) = Voltage Phase-Phase L12.

- HMITalk1.PointValue(1) = Voltage Phase-Phase L23.

- HMITalk1.PointValue(2) = Voltage Phase-Phase L31.

- HMITalk1.PointValue(3) = Voltage Phase-Phase Network.

- HMITalk1.PointValue(4) = Voltage Phase-Neutral L1.

- HMITalk1.PointValue(5) = Voltage Phase-Neutral L2.

- HMITalk1.PointValue(6) = Voltage Phase-Neutral L3.

- HMITalk1.PointValue(7) = Voltage Phase-Neutral Network.

- HMITalk1.PointValue(8) = Current L1.

- HMITalk1.PointValue(9) = Current L2.

- HMITalk1.PointValue(10) = Current L3.

- HMITalk1.PointValue(11) = Current Network.

- HMITalk1.PointValue(12) = Active Power L1.

- HMITalk1.PointValue(13) = Active Power L2.

- HMITalk1.PointValue(14) = Active Power L3.

- HMITalk1.PointValue(15) = Active Power Network.

- HMITalk1.PointValue(16) = Inductive Power L1.

- HMITalk1.PointValue(17) = Inductive Power L2.

- HMITalk1.PointValue(18) = Inductive Power L3.

- HMITalk1.PointValue(19) = Inductive Power Network.

- HMITalk1.PointValue(20) = Capacitive Power L1.

- HMITalk1.PointValue(21) = Capacitive Power L2.

- HMITalk1.PointValue(22) = Capacitive Power L3.

- HMITalk1.PointValue(23) = Capacitive Power Network.

- HMITalk1.PointValue(24) = Power Factor L1.

- HMITalk1.PointValue(25) = Power Factor L2.

- HMITalk1.PointValue(26) = Power Factor L3.

- HMITalk1.PointValue(27) = Power Factor Network.

- HMITalk1.PointValue(28) = Frequency.

- HMITalk1.PointValue(29) = Apparent Power.

Read Active Energy

COMMAND DESCRIPTION:

Reads Active Energy.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 30

Read Inductive Energy

COMMAND DESCRIPTION:

Reads Inductive Energy.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 31

Read Capacitive Energy

COMMAND DESCRIPTION:

Reads Capacitive Energy.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 32

Read Initial Energies

COMMAND DESCRIPTION:

Reads Initial Energies.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-3

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 33

 

RETURNS:

- HMITalk1.PointValue(0) = Active Energy

- HMITalk1.PointValue(1) = Inductive Energy

- HMITalk1.PointValue(2) = Capacitive Energy

Write Transformers Ratio

COMMAND DESCRIPTION:

Writes Transformers Ratio.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 3

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 34

 

WHERE:

- HMITalk1.PointValue(0) = Prim V

- HMITalk1.PointValue(1) = Sec V

- HMITalk1.PointValue(2) = Prim A

Write Type of Voltage

COMMAND DESCRIPTION:

Writes Type of Voltage.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 35

 

WHERE:

- 0 = Phase - Phase

- 1 = Phase - Neutral

Write Initial Energies

COMMAND DESCRIPTION:

Writes Initial Energies.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 3

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 36

 

WHERE:

- HMITalk1.PointValue(0) = Active Energy

- HMITalk1.PointValue(1) = Inductive Energy

- HMITalk1.PointValue(2) = Capacitive Energy

Read Input and Relay Status in MIDA 20D

COMMAND DESCRIPTION:

Reads Input and Relay Status in MIDA 20D.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Input

HMITalk1.DriverNumPoints = 1-99

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 37

HMITalk1.DriverP2 = Defines the first register to be read.

- 1 .. 18 = Inputs

- 100 .. 117 = External Relays

Write Input and Relay Status in MIDA 20D

COMMAND DESCRIPTION:

Writes Input and Relay Status in MIDA 20D.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 38

HMITalk1.DriverP2 = Defines the register to be written (0-9999).

Read A/D Channels in MIDA 20D

COMMAND DESCRIPTION:

Reads A/D Channels in MIDA 20D.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-4

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 39

 

WHERE:

- HMITalk1.PointValue(0) = DC1 Channel.

- HMITalk1.PointValue(1) = DC2 Channel.

Read Scale Factors of A/D Converter in MIDA 20D

COMMAND DESCRIPTION:

Reads Scale Factors of A/D Converter in MIDA 20D.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-4

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 40

 

WHERE:

- HMITalk1.PointValue(0) = Channel Factor 1.

- HMITalk1.PointValue(1) = Channel Factor 2.

Write Scale Factors of A/D Converter in MIDA 20D

COMMAND DESCRIPTION:

Writes Scale Factors of A/D Converter in MIDA 20D.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1-4

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 41

 

WHERE:

- HMITalk1.PointValue(0) = Channel Factor 1.

- HMITalk1.PointValue(1) = Channel Factor 2.

Write Leds Activation in MIDA 20D

COMMAND DESCRIPTION:

Writes Leds Activation in MIDA 20D.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Digital Output

HMITalk1.DriverNumPoints = 3

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 42

 

WHERE:

- HMITalk1.PointValue(0) = Test (0 = Desactivate / 1 = Activate).

- HMITalk1.PointValue(1) = Led 1 (Comm).

- HMITalk1.PointValue(2) = Led 2 (CPU).

Read Integer Type Registers in MIDA 20D

COMMAND DESCRIPTION:

Reads Integer Type Registers in MIDA 20D.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Input

HMITalk1.DriverNumPoints = 1-99

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 43

HMITalk1.DriverP2 = First register to be read (0-499).

Write Integer Type Registers in MIDA 20D

COMMAND DESCRIPTION:

Writes Integer Type Registers in MIDA 20D.

 

PROPERTY SETTINGS REQUIRED:

HMITalk1.DriverDataType = Analog Output

HMITalk1.DriverNumPoints = 1

HMITalk1.DriverP0 = Unit Address (0-99).

HMITalk1.DriverP1 = 44

HMITalk1.DriverP2 = First register to be written (0-499).

Returned Errors List

[1005] DRIVER (Internal): Invalid driver stage

[1300] PROTOCOL (Timeout): No answer

[1433] PROTOCOL (Format): Validation error in device response

[2109] CONFIG (NumValues): Invalid number of channels (must be 3)

[2113] CONFIG (NumValues): Invalid number of values (max=4)

[2147] CONFIG (NumValues): Only one value can be read or written

[2193] CONFIG (NumValues): Too many values (max=19)

[2194] CONFIG (NumValues): Too many values (max=2)

[2206] CONFIG (NumValues): Too many values (max=3)

[2207] CONFIG (NumValues): Too many values (max=30)

[2216] CONFIG (NumValues): Too many values (max=4)

[2243] CONFIG (NumValues): Too many values (max=99)

[3018] CONFIG (P0): Invalid device address (0-99)

[3508] CONFIG (P1): Invalid command

[4063] CONFIG (P2): Invalid first register (0-499)

[4064] CONFIG (P2): Invalid first register (0-999)

[4065] CONFIG (P2): Invalid first register (0-9999)

[8130] CONFIG (Remote): Error Response

About the XAFEISA.tlk driver

This driver requires that you have TAS-HMITalk 8.04 installed.

Driver Source Code Last Update: 03/08/2004 14:07:28

Driver Reference Last Update: 10/30/2008 17:32:13

© 1990-2008, CPKSoft Engineering. All rights reserved.

http://www.cpksoft.com - support@cpksoft.com