XABSLC5.tlk Driver Reference
Allen Bradley SLC-500 Full Duplex DF1 Protocol Driver
This driver requires that you have TAS-HMITalk 8.04 installed.
XABSLC5 allows you to use full-duplex DF1 protocol (System point-to-point)
to communicate with ALLEN-BRADLEY SLC-500 PLCs using any of the following
adapters connected to the PC's RS-232 port:
- Channel 0 located in the processor
- 1747-KE (DH-485)
- 1785-KE (Data Highway Plus)
- 1770-KF2 (Data Highway Plus)
- 1770-KF3 (DH-485)
- 1771-KE/KF (Data Highway)
- 1770-KF2 (Data Highway)
No additional boards are required in the PC bus.
To minimize the number of messages needed to poll all the required
information, it is a good idea to concentrate all data to be transmitted
in groups of consecutive integers within the PLC memory. Up to 16 ON/OFF
status, 1 16-bit value, 2 8-bit values or even floating-point values
(scaled to a range of 0 to 65535) can be encoded in each integer
value sent or received.
This convention for accessing to the SLC-500 controllers' data
is used by the following SLC-500 commands:
- Generic Read
- Generic Write
The general format of item names for data from SLC-500 controllers
matches the naming convention used by the programming software.
The format is shown below. (The parts of the name shown in square
brackets ([ ]) are optional.)
X [FILE] : ELEMENT [.FIELD] [/BIT]
X:
Identifies the file type. The list below summarizes the valid file
types and the default file number for each type:
X File Type Default File
O *Output 0
I *Input 1
S Status 2
B Binary 3
T Timer 4
C Counter 5
R Control 6
N Integer 7
F **Floating P. 8
* Output and Input file types may be Read Only depending on the SLC-500 model.
** Available only on certain SLC500 models. Check the Processor
Manual for the model being used. If the Floating Point file type is
not supported, file 8 is reserved and unusable.
FILE:
File number must be 0-255 decimal. File 0 must be Output, file 1
must be Input, file 2 must be Status and so on for all the default
file types. If this number is not specified, the default file number
will be used.
ELEMENT:
Element number within the file. For Input and Output files it must
be between 0 and 30 decimal. All other file types, it must be between
0 and 255 decimal.
FIELD:
Referes to the subelement number. If the file type is Timer, Counter
or Control, then the subelement field must be replaced by its
corresponing number. In some cases there is no reference needed
for a subelement number, and if a subelement is included in the
command, it will be ignored.
BIT:
Valid for all file types except Floating Point.
Must be 0-15 decimal.
DESCRIPTION OF THE AVAILABLE FILE ITEMS:
----------------------------------------
OUTPUT FILE ITEMS:
O[n]:e.s[/b]
- "n" represents the file number and is optional. If not
specified, it is assumed to be zero.
- "e" indicates the element number in the file.
- "s" indicates the sub-element number (0 - 255).
- "b" specifies the bit (0 - 15 decimal.) "/b" may be
omitted if necessary to treat the I/O group as a numeric value.
Examples:
- O0:0/0
- O:2/15
- O:3
INPUT FILE ITEMS:
I[n]:e.s[/b]
- "n" represents the file number and is optional. If not
specified, it is assumed to be one.
- "e" indicates the element number in the file.
- "s" indicates the sub-element number (0 - 255).
- "b" specifies the bit (0 - 15 decimal.) "/b" may be
omitted if necessary to treat the I/O group as a numeric value.
Examples:
- I1:0/0
- I:2/15
- I:3
ADDRESSING I/O MODULES:
The elements (words) in I/O modules are mapped into a memory table.
If the Analog I/O modules are being used, then the point naming will
differ from the point naming in the programming software. The Item
Name must be computed from the sum total of words used by the
previous input or output blocks regardless their relative position in
the module rack. The operator can use the programming software
Data Monitor to look at the memory map of the I file or O file to
verify your address. If the address is unsure, or if the PLC
configuration is likely to change, copy the points in question to
the N table or B table and access the data from there.
LABEL I/O MODULES WITH "WORD COUNTS":
The address of any point within the I/O datatable space, in an
SLC processor, is the sum of the words occupied by previous modules
(to the left in the rack) of the same type. Therefore, to determine
the correct address for any particular point in the I/O datatable,
one must know the number of words each module will consume.
Refer to the list below:
N. of Words Module
0 1747-L524 SLC 5/02 Module Processor
1 1746-IA8 8 point 120VAC input module
1 1746-OA16 16 Point 120VAC output module
1 1746-IA16 16 point 120VAC input module
4 1746-NI4 4 point 20mA analog input module
4 1746-NO4I 4 point 20mA analog output module
1 1746-0A8 8 point 120VAC input module
2 1746-IB32 32 point DC input module
NOTE:
In the table above, the minimum amount of words which can
be consumed by a module is 1 (16 bits). This is due to the
memory scheme of all Allen-Bradley processors.
STATUS FILE ITEMS:
S[n]:e[/b]
- "n" represents the file number and is optional. If not
specified, it is assumed to be two.
- "e" indicates the element number in the file (0 - 255 decimal).
- "b" is optional. If specified, it indicates the bit
(0 - 15 decimal).
NOTE:
Refer to the SLC-500 Family Processor Manual (Allen-Bradley Publication)
for a complete description of Status file information.
Examples:
- S2:6 (major error fault)
- S2:13 (math register)
- S:1/5 (forces enabled)
BINARY FILE ITEMS:
B[n]:e/b
or
B[n]/m
- "n" represents the file number and is optional. If not
specified, it is assumed to be three. If specified, the file
number must be between 9 and 255 decimal.
- "e" specifies the element (word) number within the Binary
file. It must be between 0 and 255 decimal.
- "b" specifies the bit number within the word. In the first
form (where ":e" is present,) the bit number must be between
0 and 15 decimal.
- "m" also represents the bit number. However, in the second
form, no word number is specified and the bit number may
be between 0 and 4095.
Examples:
- B3/4095 (same bit as B:255/15)
- B:6/4 (same bit as B/100)
- B3
TIMER FILE ITEMS:
T[n]:e[.f][/b]
- "n" represents the file number and is optional. If not
specified, it is assumed to be four. If specified, the file
number must be between 9 and 255 decimal.
- "e" specifies the element number (three words per element)
within the Timer file. It must be between 0 and 255 decimal.
- "f" identifies one of the valid Timer fields. The valid
fields for Timer Files are listed in the table below (use
the numeric order as reference). If "f" is omitted, it is
assumed to be the word 0.
- "b" is optional and is normally not used. All of the fields
of a timer can be accessed by specifying the ".f" fields.
However, it is possible to use "/b" to single out a bit in
the .PRE or .ACC fields (which are words).
Order number Timer Fields
0 .PRE
1 .ACC
2 .EN
3 .TT
4 .DN
Examples:
- T4:0.1 (means: .ACC)
- T4:3.4 (means: .DN)
- T4:1.0 (means: .PRE)
COUNTER FILE ITEMS:
C[n]:e[.f][/b]
- "n" represents the file number and is optional. If not
specified, it is assumed to be five. If specified, the file
number must be between 9 and 255 decimal.
- "e" specifies the element number (three words per element)
within the Counter file. It must be between 0 and 255 decimal.
- "f" identifies one of the valid Counter fields. The valid
fields for the Counter Files are listed in the table below
(use the numeric order as reference). If "f" is omitted,
it is assumed to be the word 0.
- "b" is optional and is normally not used. All of the fields
of a counter can be accessed by specifying the ".f" fields.
However, it is possible to use "/b" to single out a bit in
the .PRE or .ACC fields (which are words).
Order number Counter Fields
0 .PRE
1 .ACC
2 .CU
3 .CD
4 .DN
5 .OV
6 .UN
7 .UA
Examples:
- C5:0.1 (means: .ACC)
- C5:3.5 (means: .OV)
- C5:1.0 (means: .PRE)
CONTROL FILE ITEMS:
R[n]:e[.f][/b]
- "n" represents the file number and is optional. If not
specified, it is assumed to be six. If specified, the file
number must be between 9 and 255 decimal.
- "e" specifies the element number (three words per element)
within the Control file. It must be between 0 and 255 decimal.
- "f" identifies one of the valid Control fields. The valid
fields for the Control files are listed in the table below
(use the numeric order as reference). If "f" is omitted,
it is assumed to be the word 0.
- "b" is optional and is normally not used. All of the fields
of a Control file can be accessed by specifying the ".f"
fields. However, it is possible to use "/b" to single out
a bit in the .LEN or .POS fields (which are words).
Order number Control Fields
0 .LEN
1 .POS
2 .EN
3 .DN
4 .ER
5 .UL
6 .IN
7 .FD
Examples:
- R6:0.0 (means: .LEN)
- R6:3.2 (means: .EN)
- R6:1.1 (means: .POS)
INTEGER FILE ITEMS:
N[n]:e[/b]
- "n" represents the file number and is optional. If not
specified, it is assumed to be seven. If specified, the
file number must be between 9 and 255 decimal.
- "e" specifies the element number within the Integer file.
It must be between 0 and 255 decimal.
- "b" is optional. If specified, it indicates the bit
(0 - 15 decimal).
Examples:
- N7:0
- N7:0/15
- N7:3
FLOATING POINT FILE ITEMS:
F[n]:e
- "n" represents the file number (optional). If not specified,
it is assumed to be eight. If specified, the file number
must be between 9 and 255 decimal.
- "e" specifies the element number within the Floating Point
file. It must be between 0 and 255 decimal.
Examples:
- F8:0
- F8:2
IMPORTANT NOTES:
----------------
Remember to configure the 1747-KE using the following settings:
- Use the DF1 FULL DUPLEX Protocol
- Use the checksum mode (BCC or CRC) as stated in HMITalk1.DriverP5 parameter.
- Use the baud-rate, parity, stop bits and data bits that are
currently used in the driver settings.
You should verify these settings by connecting your PC to
the 1747-KE CONFIG port using an ASCII terminal (i.e. PROCOMM
or XTALK) and then follow the steps described in the 1747-KE
User Manual.
Be careful to include the 1747-KE node address as the source
node in your HMITalk1.DriverP0 parameter if it is other than 0.
Programmable Logic Controllers
ALLEN BRADLEY SLC-500 Family using Full Duplex DF1 Protocol
ALLEN BRADLEY SLC-500 5/03
ALLEN BRADLEY SLC-500 5/04
ALLEN BRADLEY Micrologix 1000
Generic Write as Analog Values
Generic Write as Binary Values
COMMAND DESCRIPTION:
Reads information from any area of the PLC data table memory
interpreting the values as analog inputs.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Input
HMITalk1.DriverNumPoints = 1-30
HMITalk1.DriverP0 = Identifies the destination address of the PLC with which
you want to communicate (0-255).
HMITalk1.DriverP1 = Indicates a source address of Ch0, KE or KF adapters
other than 0. Use this parameter only if neccesary (0-255).
HMITalk1.DriverP2 = Reserved.
HMITalk1.DriverP3 = Reserved.
HMITalk1.DriverP4 = Reserved.
HMITalk1.DriverP5 = Defines if BCC (0) or CRC (1) must be used.
HMITalk1.DriverP6 = Indicates the address information (ASCII Symbol) of the
first element to be read. Example: N7:0
COMMAND DESCRIPTION:
Reads information from any area of the PLC data table memory
interpreting the values as digital inputs.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Digital Input
HMITalk1.DriverNumPoints = 1-240
HMITalk1.DriverP0 = Identifies the destination address of the PLC with which
you want to communicate (0-255).
HMITalk1.DriverP1 = Indicates a source address of Ch0, KE or KF adapters
other than 0. Use this parameter only if neccesary (0-255).
HMITalk1.DriverP2 = Reserved.
HMITalk1.DriverP3 = Reserved.
HMITalk1.DriverP4 = Reserved.
HMITalk1.DriverP5 = Defines if BCC (0) or CRC (1) must be used.
HMITalk1.DriverP6 = Indicates the address information (ASCII Symbol) of the
first element to be read. Example: I1:0/0
COMMAND DESCRIPTION:
Writes analog information to any area of the PLC data table memory.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Analog Output
HMITalk1.DriverNumPoints = 1-30
HMITalk1.DriverP0 = Identifies the destination address of the PLC with which
you want to communicate (0-255).
HMITalk1.DriverP1 = Indicates a source address of Ch0, KE or KF adapters
other than 0. Use this parameter only if neccesary (0-255).
HMITalk1.DriverP2 = Reserved.
HMITalk1.DriverP3 = Reserved.
HMITalk1.DriverP4 = Reserved.
HMITalk1.DriverP5 = Defines if BCC (0) or CRC (1) must be used.
HMITalk1.DriverP6 = Indicates the address information (ASCII Symbol) of the
first element to be written. Example: N7:0
COMMAND DESCRIPTION:
Writes digital information to any area of the PLC data table memory,
in groups of 16 bits.
PROPERTY SETTINGS REQUIRED:
HMITalk1.DriverDataType = Digital Output
HMITalk1.DriverNumPoints = 16,32,48,...,240 (must be a multiple of 16)
HMITalk1.DriverP0 = Identifies the destination address of the PLC with which
you want to communicate (0-255).
HMITalk1.DriverP1 = Indicates a source address of Ch0, KE or KF adapters
other than 0. Use this parameter only if neccesary (0-255).
HMITalk1.DriverP2 = Reserved.
HMITalk1.DriverP3 = Reserved.
HMITalk1.DriverP4 = Reserved.
HMITalk1.DriverP5 = Defines if BCC (0) or CRC (1) must be used.
HMITalk1.DriverP6 = Indicates the address information (ASCII Symbol) of the
first element to be written. Example: O0:0/0
(note: any bit number you specify will be ignored and assumed as 0).
[1005] DRIVER (Internal): Invalid driver stage
[1300] PROTOCOL (Timeout): No answer
[2200] CONFIG (NumValues): Too many values (max=240)
[2207] CONFIG (NumValues): Too many values (max=30)
[3014] CONFIG (P0): Invalid device address (0-255)
[3571] CONFIG (P1): Invalid source address (0-255)
[5513] CONFIG (P5): Invalid validation mode (0=BCC/1=CRC)
[6010] CONFIG (P6): Invalid address (valid format: N[7]:0[.0][/0])
[6017] CONFIG (P6): Invalid element number (0-999)
[6018] CONFIG (P6): Invalid file number (0-999)
[6019] CONFIG (P6): Invalid file type (must be I/O/S/B/T/C/R/N or F)
[6026] CONFIG (P6): Invalid start bit (0-15)
[6028] CONFIG (P6): Invalid sub-element number (0-999)
[8000] CONFIG (Remote): 1771 module response was not valid
[8001] CONFIG (Remote): A file has an illegal value
[8010] CONFIG (Remote): Access denied (improper privilege)
[8017] CONFIG (Remote): Adapter cannot communicate with module
[8018] CONFIG (Remote): Address does not point to something usable
[8022] CONFIG (Remote): Address reference exist to deleted area
[8023] CONFIG (Remote): Addressing problem
[8025] CONFIG (Remote): Another node is program owner
[8027] CONFIG (Remote): Application layer timeout error
[8038] CONFIG (Remote): Cannot complete request
[8039] CONFIG (Remote): Cannot execute command
[8052] CONFIG (Remote): Command cannot be executed
[8055] CONFIG (Remote): Command execution failure for unknown reason
[8067] CONFIG (Remote): Communication zone problem
[8070] CONFIG (Remote): Condition already exist
[8071] CONFIG (Remote): Condition cannot be generated
[8080] CONFIG (Remote): Data conversion error
[8090] CONFIG (Remote): Data or file is too large
[8111] CONFIG (Remote): Duplicated label
[8112] CONFIG (Remote): Duplicated node detected error
[8113] CONFIG (Remote): Duplicated token holder detected error
[8140] CONFIG (Remote): File is open (another node owns it)
[8141] CONFIG (Remote): File is wrong size
[8152] CONFIG (Remote): Function disallowed
[8156] CONFIG (Remote): Hardware fault
[8157] CONFIG (Remote): Histogram overflow
[8158] CONFIG (Remote): Host could not complete function
[8159] CONFIG (Remote): Host has a problem and will not communicate
[8165] CONFIG (Remote): Illegal command or format (try using less values)
[8169] CONFIG (Remote): Illegal data type
[8197] CONFIG (Remote): Invalid parameter or data
[8204] CONFIG (Remote): Less levels specified in address
[8206] CONFIG (Remote): Link layer error
[8208] CONFIG (Remote): Local port is disconnected
[8216] CONFIG (Remote): More levels specified in address
[8218] CONFIG (Remote): No access
[8240] CONFIG (Remote): Not used
[8274] CONFIG (Remote): Processor is in program mode
[8297] CONFIG (Remote): Remote node cannot buffer command
[8298] CONFIG (Remote): Remote node host is missing or shut down
[8299] CONFIG (Remote): Remote node problem
[8315] CONFIG (Remote): Scanner not able to communicate with 1771 module
[8326] CONFIG (Remote): Station is offline
[8328] CONFIG (Remote): Symbol is of improper format
[8329] CONFIG (Remote): Symbol not found
[8338] CONFIG (Remote): Transaction size plus word address is too large
[8347] CONFIG (Remote): Unknown error